Project Number : 66-6380-700 Date

Prepared by DSP Checked by RC


WIND LOAD CALC

Height of structure 8m

Wind load intensity (ref design criteria) Pd 1.5 KN/m²

Slope of roof a 20.14 degrees

Spacing of Purlin 1.4 m.

Wind load for roof


w

E G

Wind F H
q l

l 18 m

h 8 m

w 12.00 m

h/w 0.67

l/w 1.50
Internal pressure coeff, Cpi
Wind angle θ=0 θ=90
Wall face area 144 m² 96 m² 480
Opening area 52.2 m² 34.8 m² 174
% Opening 36.3 36.3 36.3
Cpi ± 0.7 ± 0.7 + 0.7
- -0.7

Wind load for roof

(Ref cl 6.2.2.2 of IS:875 Part 3)


External pressure coeff, Cpe
Wind angle Wind angle
θ=0 θ=90
a EF GH EG FH
20 -0.7 -0.5 -0.8 -0.6
30 -0.2 -0.5 -0.8 -0.8
For
20.14 -0.69 -0.50 -0.80 -0.60

For wind angle q=0

-0.69 -0.50 -0.69 -0.50


EF GH EF GH

0.7 -0.7

Resultant wind pressure(Cpe-Cpi) for wind angle θ=0, in KN/m²

-1.39 -1.20 0.01 0.20


EF GH EF GH

F=(Cpe-Cpi) A Pd on Purlin

-2.93 -2.52 0.01 0.42


EF GH EF GH
For wind angle q=90
-0.80 -0.80 -0.80 -0.80
E G E G

0.7 -0.7

-0.60 -0.60 -0.60 -0.60


F H F H

0.7 -0.7

Resultant wind pressure(Cpe-Cpi) for wind angle q=90, in KN/m²

-1.50 -1.50 -0.10 -0.10


E G E G

-1.30 -1.30 0.10 0.10


F H F H

F=(Cpe-Cpi) A Pd on Purlin

-3.15 -3.15 -0.21 -0.21

-2.74 -2.74 0.20 0.20


Wind load for walls
(Ref cl 6.2.2.1 of IS:875 Part 3)
Spacing of Cladding Along Side A. 1.2 m.

Spacing of Cladding Along Side C. 1.2 m.

External pressure coeff, Cpe for h/w<1/2 ,3/2<l/w<4

Wind Angle Cpe for wall Surface


A B C D
θ=0 0.70 -0.25 -0.60 -0.60
θ=90 -0.60 -0.60 0.70 -0.25

External pressure coeff, Cpe


For wind angle q=0
-0.6 -0.6
C C

0.70 -0.25 0.70 -0.25


A 0.7 B A -0.7 B

D D
-0.6 -0.6

Resultant wind pressure(Cpe-Cpi) for wind angle q=0, in KN/m²

-1.3 0.1
C C

0.00 -0.95 1.4 0.45


A B A B

D D
-1.3 0.1

F=(Cpe-Cpi) A Pd on cladding F/2 F/2


F/2c
F/2 2
-2.34 0.18
F/2
F/2 F/2 F/2

0.00 -1.71

2.52 0.81

F/2
F/2 F/2 F/2

-2.34
F/2 F/2
F/2 0.18
F/2
For wind angle q=90

0.7 0.7
C C

-0.6 -0.6 -0.6 -0.6


A 0.7 B A -0.7 B

D D
-0.25 -0.25

Resultant wind pressure(Cpe-Cpi) for wind angle q=90, in KN/m²

0.0 1.40
C C

-1.30 -1.30 0.10 0.10


A B A B
D D
-1.0 0.45

F=(Cpe-Cpi) A Pd on cladding F/2


F/2
F/2 F/2
0.00 2.52

F/2 F/2 F/2


F/2

-2.34 -2.34

0.18 0.18

F/2
F/2 F/2 F/2

-1.71 0.81
F/2 F/2
F/2
F/2

Notes
1) Positive force indicates the force acting towards the structure .
2) Negative force indicates the force acting away from the structure .