You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/267563667

Corona Losses Dependence from the Conductor Diameter

Article · October 2011

CITATIONS READS

0 654

2 authors, including:

Vjollca Shaib Komoni


University of Prishtina
23 PUBLICATIONS   38 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

studying signals of certain biomarkers using living stains View project

Photovoltaic systems View project

All content following this page was uploaded by Vjollca Shaib Komoni on 01 April 2014.

The user has requested enhancement of the downloaded file.


Recent Researches in Power Systems and Systems Science

Corona Losses Dependence from the Conductor Diameter


ISUF KRASNIQI,
VJOLLCA KOMONI
Faculty of Electrical and Computer Engineering
University of Prishtina,
Bregu i diellit p.n. 10000 Prishtina
AVNI ALIDEMAJ
KEK- Kosovo Energy Corporation J.S.C.
GAZMEND KABASHI
KOSTT - Transmission System and Market Operator of Kosovo
KOSOVO
isuf.krasniqi@uni-pr.edu, vjollca.komoni@uni-pr.edu, avni.alidemaj@kek-energy.com,
gazmend.kabashi@kostt.com

Abstract: - This paper presents possibility to decrease the corona power losses in overhead transmission lines.
Corona power losses can be reduced by increasing the diameter of the conductor and used bundled conductors
per phase. The objectives were to determine the corona power losses depend on conductors diameters. The
simulation is completed using the corona model for one 400 kV and 220 kV overhead transmission line is
developed in Matlab/Simulink. The objectives are to determine the corona effect in high voltage transmission
lines, and to identify factors of decreasing the corona losses, such as increasing the diameter of conductors, and
thus have to increase the critical disruptive voltage. The paper describes the analytical approach, computational
tools and simulations models.

Key-Words: - Electric discharge, Electric field, Corona model, Critical disruptive voltage, Power losses,
Transmission line.

1 Introduction 2 Corona in transmission line


2.1 Critical disruptive voltage
During the unusual situation in the overhead
transmission line when the intensity of the electric If one-phase transmission line shown in Fig.1.
field exceeds the dielectric strength of air, then Let r be the radius of each conductor and d the
around the conductor is electric drilling, which distance between the conductors such that d >> r. In
causes increasing losses and increasing the apparent this single-phase transmission line, let q be the
conductivity. This phenomenon is called the corona. charge per unit length on one of the conductors and
Therefore, corona, defined as a self-sustained hence – q on the other. If the operating voltage is U,
electric discharge in which the field intensified the potential of conductor A with respect to neutral
ionization is localized only over a portion of the plane N will be U/2 and that of conductor B will be
distance between the electrodes. When the voltage - U/2.
higher than the critical voltage is applied between to
parallel polished wires, the glow is quite even. After
operation for a short time, reddish beads or tufts A N B
form along the wire, while around the surface of the q r p -q
wire there is a bluish white glow.
The a.c. corona viewed through a stroboscope x
has the same apperance as direct current corona.
As corona phenomenon is initiated a hissing d
noise is heard and ozone gas is formed which
can be detected by its chracteristic colour.
Fig. 1 1-ph transmission line

ISBN: 978-1-61804-041-1 112


Recent Researches in Power Systems and Systems Science

The electric field intensity at P due to the both smaller diameter then the conductor as a whole. The
line charge will be potential gradient for such conductor will be greater
than for the equivalent smooth conductor. The
q1 1  irregularities on the surface are increased further
Ex =  +  (1) because of the deposition of dust and dirt on its
2π ε 0  x d − x 
surface and the breakdown voltage is further
reduced. Average value for the ration of breakdown
The potential different between the conductors voltage for such conductor and a smooth conductor
lines between 0.85, and is denoted by m0.
r
q d −r The final expression for the critical disruptive
U =− ∫ E x dx = π ε 0 ln r
(2)
voltage after taking into account the surface of the
d −r conductor is given by:
Since r is very small as compared to d, d
d − r = d . Substituting for q from the above U 0 = r g 0 δ m0 ln [kV ] (8)
r
equation,

π ε0 U 2.2 Corona loss


q= (3)
d
ln
r In high voltage transmission line when the
applied voltage exceeds a critical disruptive value,
U'd the thin layer of air around the transmission line
Ex = (4) ionizes. This ions result in space charges which
d
x (d − x )ln move round the conductor. To remain the charges in
x
the motion required the energy derived from the
supply system. To maintain the flow of energy over
Where U’ is the line to neutral voltage of the
the conductor it is necessary to supply this
systems.
additional loss from the supply system. This
Critical disruptive voltage is defined as the
additional power is referred to as corona loss.
voltage at which complete disruption of dielectric
Peek study the effect of various parameters on
occurs. This voltage corresponds to the gradient at
the corona loss and he deduced an empirical
the surface equal to the breakdown strength of air.
relation:
This dielectric strength is denoted by g0 and is equal
to 30 kV / cm peak at NPT i.e., 250C and 760 mm
of Hg. P = 241×10 −5
(f + 25) r
(
U p −U 0 )2 kW / km (9)
At any other temperature and pressure δ d

Where f is the frequency supply (Hz), δ the air


g 0' = g 0 δ (5)
density correction factor, Up the operating voltage in
kV, U0 the critical disruptive voltage (kV), r radius
Where is the air density correction factor and is of the conductors (m) and d spacing (or equivalency
given by spacing) between conductors (m).
In overhead transmission line the following
3.92 b factors affect corona los: (i) electrical factors, (ii)
δ= (6)
273 + t atmospheric factors and (iii) factors connected with
the conductors.
Therefore the critical disruptive voltage is given by Electrical factors, referring to the equation (9) it
is seen that the corona loss is a function of
d frequency. Thus higher the frequencies of supply
U 0 = r g 0 δ ln [kV ] (7) and the losses are higher due to corona. This means
r
that d.c. corona loss is less as compared with a.c.
corona loss. This is because during the corona
For high voltage transmission line the ACSR
phenomenon of a.c. is always present third
conductors are used. The cross-section of such
harmonics and hence frequency is not only 50 Hz
conductors a series of arcs of circles each of much
but it is contains also third harmonic component.

ISBN: 978-1-61804-041-1 113


Recent Researches in Power Systems and Systems Science

Atmospheric Factors, consist in air density and


weather condition. Air density affects the generation P=k
r
d
(
U p −U 0 )2 kW / km (11)
of corona sources as demonstrated by Peek
empirical equation (9). From this equation the losses
From this expression shows that the first losses
are a function of air density correction factor δ . The
are proportional to the square root of the diameter of
lower value of δ causes the higher the loss, because the conductor, if the diameter of conductor are
appears directly in the denominator of the equation larger, then the loss will be larger. Secondly, since
and indirectly in the value of critical disruptive U0 is approximately directly proportional to the
voltage. diameter of the conductor, hence larger the size of
the conductor now the critical disruptive voltage has
d
U 0 = 21.1m0 δ r ln [kV ] (10) to be large and hence smaller will be difference
r between the operate and critical disruptive voltage.
Number of conductors is an input into the
For the lower value of δ losses will be higher, calculation of the electric field at the surface of
because the lower value of δ , will be have the lower conductors. For operating voltage 400 kV and above
value of U 0 and hence higher the value of it, is found that one conductor per phase gives large
corona loss and hence large radio interference (RI)
(U − U )2 , where U is the operating voltage in kV.
0 level which interferes with the communication lines
During the bad weather conditions such as rain, which are normally run parallel with the power
snow and hailstorm will diminish the critical lines. Most research has shown that the RI does not
disruptive voltage and hence increase the corona increase with the number of conductors for a fixed
loss. These is due to the fact that rain droplets on the conductor diameter [3].
transmission line conductors can be viewed as sharp The higher the corona losses in the power
edges which enhances the electric field and transmission lines with one conductor is solved with
therefore reduces the corona disruptive voltage and by using two or more than two conductors per phase
hence increase the corona power loss. Corona or as they are known as bundling of conductors. By
generation increases whenever moisture bundling the conductors the self geometric mean
accumulates on the conductor. Conductor current, if distance (GMD) of the conductors is increased
it heats the conductor, discourages the formation of thereby; the critical disruptive voltage is increased
water drops during fog and during high humidity, and hence corona loss is reduced.
but has little effect during heavy rain and snow. To reducing corona loss can be used following
Corona loss observations in the operating lines methods: (i) large diameter of conductors (ii)
during the hoarfrost have shown that the highest hallows conductors, (iii) bundled conductors.
corona losses occur when hoarfrost accumulates on With the aim to reduce the corona power losses,
a cold conductor, during the nigh time hours, when have been made experiments and research how
load currents are not sufficient to warm the affects have the larger diameter and bundled
conductors enough to melt the hoarfrost [3]. conductors.
Wind speed has been found to have a very small If conductor radius is larger, surface field
effect on corona generation unless the wind is intensity is less and hence corona losses are lower.
blowing particles onto conductors. For the same current carrying capacity, an ACSR
Factor connected with conductors consist in conductor has larger radius, therefore the
conductor surface conditions, conductor diameter transmission lines with ACSR conductors have
and number of conductors. lower corona loss. Also, for bundled conductors
The conductors are exposed to atmospheric lines effective radius is larger and hence corona loss
conditions; the surface would have dirt etc. is less.
deposited on it which will lower the disruptive Corona losses do not generally play an important
voltage and increase corona loss. Audible noise is role in the overall design of transmission lines. With
primarily a foul-weather phenomenon therefore most computer programs that evaluate only the cost
conductor-surface conditions are important only of resistive losses in overhead transmission lines.
inasmuch as they affect water drop formation. But, there are conditions where corona losses may
From the equation (9) for corona loss shows that influence the economic choice of conductors, and
the conductor size appears at two places and the compact lines may be one of those conditions. The
other parts of equation are assumed constant, so: cost of transmission line conductors, usually
expressed in terms of an annualized cost, is made up

ISBN: 978-1-61804-041-1 114


Recent Researches in Power Systems and Systems Science

of the annualized cost of capital investment and the particularly for lightly loaded or compact
annual cost of energy losses incurred during the transmission lines in the range of 230–400 kV, lines
operation of the line. The capital cost is almost in traversing regions of high altitude or of extreme
directly proportional to the conductor cross-section, pollution, and also for normally loaded lines at
or to d2, where d is the conductor diameter. In the voltages above 750 kV (3).
absence of corona on conductors, the energy losses The mean annual corona losses of high-voltage
consist mainly of the resistive or I2R losses, where I transmission lines are usually an order of magnitude
is the load current flowing through the line, and R is lower than the resistive losses. However, the
resistance of the conductor. Insulator leakage losses maximum corona losses can be of the same order of
are generally negligible compared to the resistive magnitude as the resistive losses.
losses.
The economic choice of conductors, for a given
transmission voltage and load current, involves 3 Case studies
minimizing the total annualized cost of conductors
over the expected life of the line. Since the capital Matlab/Simulink has been used to develop
cost increases while the cost of resistive energy the corona model for analyzing the corona
losses decreases with d, there is an optimum value
losses in 400 kV overhead transmission line.
of d for which the total cost attains a minimum. In
Figure 2, curve 1 shows the variation of the total Figure 3 shows the block schematic of the
cost as a function of conductor diameter d. presented model in Matlab/Simulink for the
Minimum total cost is obtained for an optimum corona losses in 400kV transmission lines.
conductor diameter d1. For conductor sizes either
lower or higher than d1, the total cost will be higher.
The increase in total cost may become important for 241
lower load currents and/or higher energy costs. konstanta1

1
Divide

50
Prodhimi
frekuenca
Add -K-
25 Dot Product1 Gain
sqrt Humbjet
Konstanta
Math
7.82 Function

rezistenca
Divide1

196.13 2
u -K-
Tensioni i kurores
s Add1

400

Tensioni i linjes (kV)

Figure 3. Simulation corona model for 400kV


transmission line

With simulation the corona model and applying


Fig. 2 Economic choice of conductors the Peek expression are calculate the corona loss.
The effects of critical disruptive voltage in the
In the presence of corona on conductors, the corona loss are shown in Figure 4.
mean annual corona losses should be added to the
resistive losses to determine the annualized the Humbjet nga efekti kuror

energy losses. As in the case of resistive losses, 5.25

corona losses decrease as d increases. This is 5.2

illustrated by curve 2 of Figure 2, which differs 5.15


k w /k m

from curve 1 at lower values of d and merges 5.1

5.05
asymptotically with curve 1 for the increased value 5
of d. The minimum total cost of curve 2 occurs at a
20

21

22

23

24

25
.2
.4
.6
.8

.2
.4
.6
.8

.2
.4
.6
.8

.2
.4
.6
.8

.2
.4
.6
.8
01
20
20
20
20

21
21
21
21

22
22
22
22

23
23
23
23

24
24
24
24
E+

slightly larger diameter d2.


00
2.

Tensioni (kV)

With the increasing cost of energy, studies


carried out in several countries have shown that it is
important to take into account the cost of corona Figure 4. Corona losses in 400kV transmission line
losses in the economic choice of conductors,

ISBN: 978-1-61804-041-1 115


Recent Researches in Power Systems and Systems Science

In the case, where the critical disruptive voltage corona losses in 400kV transmission lines depend of
is less, the difference between the operating voltage the conductor diameter.
Up and critical disruptive voltage U0 is the largest,
hence the corona losses are larger. During the foul 241

weather, especially when there is fog, the dielectric Constant

1
strength is less hence the critical disruptive voltages Divide

are less. In opposite, during the fair weather, the 50 Prodhimi

dielectric strength is larger hence the critical Frekuenca

25 Add Dot Product1


-K-

Gain

disruptive voltages are larger. Constant3 sqrt


Dot Product3 Humbjet

Similar calculations were made for 230 kV rrezja


Math
Function1
2
u -K-

transmission line, in this case corona loss are lower 196.13


Divide1
400
Add1 Math
Function
Gain2

than the corona losses in the 400 kV transmission S Tensioni i linjes[kV]

lines. -K-

The effects of critical disruptive voltage in the Rrezja[mm] 36.5

kons
-K-

mp
mp1

corona loss, in the 220 kV transmission lines, are Dot Product2 Dot Product4

shown in Figure 5. 15140


ln
D[mm]
Math
Divide2
Function2

1.98 Figure 6. Simulation corona model for transmission


1.96 line depend of conductor diameter
P k [k W /k m ]

1.94
1.92 The effects of increase the conductor diameter to
1.9 decrease the corona loss, in the 400 kV transmission
1.88 lines, are shown in Figure 7.
1.86
1 0 .8
1 1 .2
1 1 .6
1 2 .0
1 2 .4
1 2 .8
1 3 .2
1 3 .6
1 4 .0
1 4 .4
1 4 .8
1 5 .2
1 5 .6
1 6 .0
1 6 .4
1 6 .8
1 7 .2
1 7 .6
1 8 .0
1 8 .4
1 8 .8
1 9 .2
1 9 .6
2 0 .0

Varshmëria e humbjeve të Kurorës ndaj rrezës së përçuesit


Uk (kV)
6
5
4
kW /cm

Figure 5. Corona losses in 230kV transmission line 3


2
While, lower corona losses in the 230kV 1
transmission lines than the corona losses in the 0
15.3
15.4
15.5
15.7
15.9
16
16.2
16.3
16.5
16.7
16.8
17
17.1
17.3
17.5
17.6
17.8
17.9
18.1
18.3
18.4
18.6
18.7
18.9
19.1
19.2
400kV transmission lines, are presented in Figure 6.
mm
Critical disruptive voltage is defined as the
voltage at which the gradient at the surface equal to
the breakdown strength of air equal to 30 kV/cm. So,
Figure 7. Corona losses in 400kV transmission line
if the operates voltage less than critical disruptive depend of the conductor diameter
voltage, then corona will not appear. However, if the
operates voltage is larger than the critical disruptive Similarly the effects of increase the conductor
voltage, then will corona appears. Corona discharge diameter to decrease the corona loss, in the 230 kV
is the greater if the difference between operating Varshmëria e Humbjeve të Kurorës ndaj rrezës së përçuesit
voltage and the critical disruptive voltage is larger. Corona losses depended from conductor cross section
From the expression (8) of critical disruptive voltage 2
1.8
is seen that to increasing the critical disruptive 1.6
1.4
voltage can be done by increasing the diameter of 1.2
kW /cm

1
the conductor. 0.8
0.6
Also, to show the reduction of corona losses with 0.4
0.2
increasing diameter of conductor are used 0
13.6
13.7
13.8
14
14.2
14.3
14.5
14.6
14.8
15
15.1
15.3
15.4
15.6
15.8
15.9
16.1
16.2
16.4
16.6
16.7
16.9
17
17.2
17.4
17.5

MATLAB/ SIMULINK to develop the corona


mm
model for analyzing the corona losses in 400 kV
transmission lines, are shown in Figure 8.
overhead transmission line depend of the diameter
of conductors. Figure 6 shows the block schematic
of the presented model in Matlab/Simulink for the Figure 9. Corona losses in 230kV transmission line
depend of the conductor diameter

ISBN: 978-1-61804-041-1 116


Recent Researches in Power Systems and Systems Science

4 Conclusion [3] EPRI, Transmission Line Reference Book – 115-


230kV Compact Line Design, Electric Power
In this paper has been presented the effects of Research Institute 2007.
conductor diameter in critical disruptive voltage and [4] D. Das, Electrical Power Systems, New Age
in the corona losses. Matlab/Simulink model has International Publishers, New Delhi, 2006.
been used to analyzing the corona power losses [5] F.W. Peek, Dielectric Phenomena in High
depends of the critical disruptive voltage or for the Voltage Engineering, McGraw-Hill, 1929
diameter of conductors. [6] A. Ersoy, A. Kuntman, An Experimental
The results obtained from the simulation have Study on Corona Losses in Conductors,
shown that corona losses are larger, where the Journal on Electronics and Electrical
critical disruptive voltage is less; hence the Engineering, Vol. 3, No. 1, Pages 352-354.
difference between the operating voltage Up and [7] Cem Eroncel, Suat Ilhan, Aydogan Ozdemir,
critical disruptive voltage U0 is the largest. During Adnan Kaypmaz, Corona Onset Voltage and
the foul weather, the critical disruptive voltages are Corona Power Losses an in Indoor Corona
less, and hence the corona power losses are larger. Cage, International Middle East Power
On the other hand, a very efficient measure to Systems Conference, Cairo University,
reduce corona losses is to increase the diameter of December 2010, pages 791-794.
the conductor. By using the Peek empirical formula [8] Z. M. Al Hamouz, Corona Power Loss Versus
the corona power loss is calculated. The results Ohmic power Loss in HVDC transmission lines,
show that corona losses are decrease if the [9] Prof. C. S. Indulkar, Sensitivity Analysis of
conductors’ diameters are increased. Corona and Radio Noise in EHV Transmission
Lines, IE (I) Journal EL, Vol 84, March 2004,
References: Pages 197-200.
[1] Mayen Abdel-Salam, Essam Zaki Abdel-Aziz [10] Raymond Lings, Vermon . Chartier, Sarma
Corona power loss determination on multi- Maruvada, Overview of Transmission Lines
phase power trasmission lines, Electric power Above 700 kV, IEEE PES 2005 Conference and
systems research, volume 58, Issue 2, 2001, Exposition in Africa, Durban, South Africa, 11-
Pages 123-132. 15 July 2005, Pages 33-43.
[2] Enrique E. Mombello, Giuseppe Ratta, Heetar [11] Mehmet Salih Mamis, State-Space Transient
D. Suarez and Federico O. Torres, Corona loss Analysis of Single-Phase Transmission Lines
characteristics of contaminated conductors in with Corona, International Conference on
fair weather. Electric power systems research, Power Systems Transients – IPST 2003, New
volume 59, Issue 2, 2001, Pages 21-29.X1. Orleans, USA,

ISBN: 978-1-61804-041-1 117

View publication stats

You might also like