You are on page 1of 1

TEST REPORT

TEST REPORT NO : ETS/46-71/11/2017 DATE OF REPORT :08-11-2017


WATERSAMPLE ANALYSIS REPORT
Name And Address of Customer : M/S SUDHA STEEL MANUFACTURER PVT. LTD
K.NO.525, CHAPRAULA, GREATER NOIDA, GAUTAM BUDDH NAGAR
Date of Sampling : 03-11-2017
Analysis Start Date : 03-11-2017
Analysis End Date : 08-11-2017
Sample ID No : 46-71/11
Sampling Done By : ETS STAFF
Sampling Description : GROUND WATER
Sampling Location : BORWELL
Sampling Method : ETS/STP/WATER-01
Sampling Quantity : 2.0+0.5 Lt.
Packing Condition : SEALED
Packed In : P.V.C. CANE
Drinking Water Standards / Limit
S. No. Test Parameters Unit Result (IS:10500 2012 ) Test Method
Desirable Permissible
1. Colour Hazen <5.0 5 15 IS:3025 (Pt-4)
2. Odour --- Agreeable Agreeable Agreeable IS:3025 (Pt-5)
3. pH --- 7.25 6.5 - 8.5 No Relaxation IS:3025 (Pt-11)
4. Taste --- Agreeable Agreeable Agreeable IS:3025 (Pt-8)
5. Turbidity NTU <1.0 1 5 IS:3025 (Pt-10)
6. Total Dissolve Solid (TDS) mg/L 469.2 500 2000 IS:3025 (Pt-16)
7. TotalHardness(CaCO3) mg/L 195.0 200 600 IS:3025 (Pt-21)
8. Chloride (Cl) mg/L 46.2 250 1000 IS:3025 (Pt-32)
9. Calcium (Ca) mg/L 32.6 75 200 IS:3025 (Pt-40)
10. Sulphate (SO4) mg/L 18.3 200 400 IS:3025 (Pt-24)
11. Conductivity (25 °C) mS/ cm 702.0 Not Specified Not Specified APHA-2510

12. E. Coli Coli/100ml Absent Shall Not Be --- IS:1622-1981


Detectable
****End of Test Report****

Page 1 of 1
FOR ENVIRO-TECH SERVICES

CHECKED BY AUTHORIZED SIGNATORY


Format no ETS /LAB/TR-09 Issue No 04 dt 01/06/2016 Rev No 03 dt 01/06/2016