You are on page 1of 7

TEMPERATURE PROFILES

HAZARDOUS LOCATION LIGHTING


In the following Temperature Profile Data Charts, when a column is headed “Tested Lamp Envelope Surface
Temperature in °C @ 40°C Maximum Ambient,” the data (in degrees Celsius) was obtained in a 40°C ambient
under normal gravity conditions.
In the following Temperature Profile
Data Charts, when a column is TEMPERATURE CODE
headed “Maximum Luminaire External
IDENTIFICATION IDENTIFICATION
Surface Temperature in °C,” the data NUMBER DEGREES C NUMBER DEGREES C
(in degrees Celsius) was obtained
under a dust blanket at 40°C ambient MAXIMUM T1 450 T3A 180
under normal gravity conditions. TEMPERATURE T2 300 T3B 165
RANGE T2A 280 T3C 160
In the following Temperature Profile IDENTIFICATION T2B 260 T4 135
Data Charts when a T code is used, NUMBER T2C 230 T4A 120
this chart explains the temperature T2D 215 T5 100
maximum (in degrees Celsius). T3 200 T6 85

POWR•GARD® H9 LUMINAIRE TEMPERATURE PROFILE DATA


OPTICAL CONFIGURATION QUARTZ OPTION
Data applies to Globe and Guard with or without Standard Automatically switched quartz. Available
only with lamp types and wattages
Dome or Angle Dome Reflector (Class I and II), Deep Dome shown below. Maximum ambient is 40°C.
(Class I only). Limited to 150-watt quartz lamp. Cannot
be used for Paint Spray area.
OPTICAL CONFIGURATION
Data applies to Globe and Guard with or
MOUNTINGS without Standard Dome or Angle Dome
Reflector (Class I and II), Deep Dome
Pendant Angle Stanchion Floodlight (Class I only).
Flexible Pendant
Wall MOUNTINGS
Pendant Straight Stan-
Ceiling Flexible Pendant chion
Straight Stanchion Wall Angle Stanchion
Ceiling
CLASSIFICATIONS Straight Stanchion
Class I, Class II, Class I, Class II, Class I, + Other OPTICAL CLASSIFICATIONS
+ Other OPTICAL Division 1 Division 1 Division 1 Division 1 Division 1 Class I, Division 1 Class II, Division 1
CONFIGURATIONS
CONFIGURATIONS listed Groups C,D Groups E,F,G Groups C,D Groups E,F,G Groups C,D listed Groups C,D Groups E,F,G
Lamp Max Ambient Temp Temp Temp Temp Temp Lamp Max Temp Temp
Wattage °C Code Code Code Code Code Wattage Ambient°C Code Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 55 T5 T4 T5 T4 T4 50 40 T3C T3C
70 55 T5 T4 T5 T4 T4 70 40 T3C T3C
100 55 T5 T4 T5 T4 T4 100 40 T3C T3C
150 55 T4A T4 T4A T4 T4 150 40 T3C T3C
200 55 T3C T3 T3C N/A T3C 200 N/A N/A N/A
250 55 T3C T3 T3C N/A T3C 250 N/A N/A N/A
400 40 T3* N/A T3A* N/A T3A* 400 N/A N/A N/A
METAL HALIDE METAL HALIDE
100 55 T4A T4A T4A T4A T4 175 40 T3C T3C
175 55 T4 T3B T4 T3B T3B* 250 N/A N/A N/A
250 55 T3C N/A T3C N/A T3B* 400 N/A N/A N/A
400 40 T3A N/A T3A N/A T3* MERCURY
MERCURY 100 40 T3C T3C
100 55 T4 T3B T4 T3B T3A* 175 40 T3C T3C
175 55 T4 T3B T4 T3B T3A* 250 N/A N/A N/A
250 55 T3B* N/A T3B* N/A T3A* 400 N/A N/A N/A
400 40 T2D* N/A T2D* N/A T2C*
NOTE: *CAUTION: Operating temperatures exceed safe temperatures for some Group C materials.
To prevent fire or explosion install only as intended.

LIMITATIONS H8 HAZARDOUS LOCATION INCANDESCENT LUMINAIRE


H9 luminaires are UL Listed for Class I, Division 1, Group C (180°C YOU MUST USE TEMPERATURE PROFILE UL844
max) and Group D (280°C max) luminaire surface temperature. H9 DATA TO PROPERLY SELECT LUMINAIRE
luminaires are not listed for Groups A and B. TEMPERATURE PROFILE (25°C AMBIENT)
DATA APPLIES TO ALL MOUNTINGS
WARNING–Do not use GE Multi-Vapor II MXR175 lamps in explosion
®

Maximum Wattage
proof or hazardous duty fixures because they have higher bulb
temperatures than standard 175-watt metal halide lamps and may No Standard Angle Temp
exceed the temperature rating of these fixture types. Classification Group Reflector Reflector Reflector Code
Class I, Division 1 C, D 300 300 300 T3C
Class I, Division 1, 2
D (Paint 75 N/A N/A T4A
Spray)
Class II, Division 1 E, F 200 150 200 T3
Class II, Division 1 E, F, G 100 N/A 150 T3C
Class II, Division 2 G 100 N/A 150 T3C
NOTE: N/A=Not Applicable
® Registered Trademark of General Electric Company
Data subject to change without notice GE Lighting Systems, Inc. March 2001/H-7
FILTR•GARD H2 AND H2U ®

LUMINAIRE TEMPERATURE PROFILE DATA


HAZARDOUS LOCATION LIGHTING

OPTICAL CONFIGURATION OPTICAL CONFIGURATION


Large Globe and Guard (Type FG) (with or without Standard Dome or Angle Dome Large Globe and Guard (Type FG) (with Deep
Reflector) 250 Watts Maximum Dome Reflector) 250 Watts Maximum
MOUNTINGS
All Mounting Usable with all H2 Mounting Arrangements except NOT FOR ANGLE STANCHION
Arrangements mounting unless following conditions are met: For Class II and Class III, Divisions 1 MOUNTINGS
and 2, angle stanchion can be used with globes in combination with 50-, 70- and All Mounting Arrangements
100-watt High Pressure Sodium light source only. Temperature code is T3C except
with deep dome (see data) with small or large globe. No other High Intensity Discharge
(HID) light source can be used with angle stanchion and globe for this classification.

CLASSIFICATIONS ▼ CLASSIFICATIONS
Class I, Division 2 Class II, Division 1, Groups E, F, G; Class II, Class I, Division 2 Class II, Division 1
+ Other OPTICAL Division 2, Group G; and Class III, + Other OPTICAL
CONFIGURATIONS Divisions 1, 2 CONFIGURATIONS
listed Groups A, B, C, D Groups E, F Group G listed Groups A, B, C, D Groups E, F
Max Max * Max * Maximum Max Maximum Max Maximum Max
Ambient Ambient Ambient Luminaire Ambient Luminaire Ambient Luminaire Ambient
Lamp 40°C 55°C 65°C External 40°C External 40°C Lamp Maximum External 40°C
Wattage Temp Temp Temp Surface Temp Surface Temp Wattage Ambient 40°C Surface Temp
Code Code Code Temp (°C) Code Temp (°C) Code Temperature Code Temp (°C) Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T3A T3 T3 160 T3C 160 T3C 50 T3C 200 T3
70 T3A T3 T3 160 T3C 160 T3C 70 T3 200 T3
100 T2D T2C T2C 160 T3C 160 T3C 100 T2B 200 T3
150 T2A T2 T2 200 T3 N/A N/A 150 T2B 200 T3
250 T1 N/A N/A N/A N/A N/A N/A 250 T1 N/A N/A
METAL HALIDE METAL HALIDE
100 T2A N/A N/A 200 T3 N/A N/A 100 T2 N/A N/A
175 T2A N/A N/A 200 T3 N/A N/A 175 T2 N/A N/A
250 T1 N/A N/A N/A N/A N/A N/A 250 T1 N/A N/A
400 N/A N/A N/A N/A N/A N/A N/A 400 N/A N/A N/A
MERCURY MERCURY
100 T2B T2A T2A 160 T3C 160 T3C 100 T2B N/A N/A
175 T2 T1 N/A 200 T3 N/A N/A 175 T2 N/A N/A
250 T1 N/A N/A N/A N/A N/A N/A 250 T1 N/A N/A
400 N/A N/A N/A N/A N/A N/A N/A 400 N/A N/A N/A

OPTICAL CONFIGURATION OPTICAL CONFIGURATION


Small Globe and Guard (Type GG) (with or without Standard Dome or Angle Dome Small Globe and Guard (Type GG) (with Deep
Reflector) 175 Watts Maximum Dome Reflector) 250 Watts Maximum
MOUNTINGS
All Mounting Useable with all H2 Mounting Arrangements except NOT FOR ANGLE STANCHION
Arrangements mounting unless following conditions are met: For Class II and Class III, Divisions 1 MOUNTINGS
and 2, angle stanchion can be used with globes in combination with 50-, 70- and
100-watt High Pressure Sodium light source only. Temperature code is T3C except All Mounting Arrangemnets
with deep dome (see data) with small or large globe. No other High Intensity Discharge
(HID) light source can be used with angle stanchion and globe for this classification.

CLASSIFICATIONS ▼ CLASSIFICATIONS
Class I, Division 2 Class II, Division 1, Groups E, F, G; Class II, Class I, Division 2 Class II, Division 1
+ Other OPTICAL Division 2, Group G; and Class III, + Other OPTICAL
CONFIGURATIONS Divisions 1, 2 CONFIGURATIONS
listed Groups A, B, C, D Groups E, F Group G listed Groups A, B, C, D Groups E, F
Max Max * Max * Maximum Max Maximum Max Maximum Max
Ambient Ambient Ambient Luminaire Ambient Luminaire Ambient Luminaire Ambient
Lamp 40°C 55°C 65°C External 40°C External 40°C Lamp Maximum External 40°C
Wattage Temp Temp Temp Surface Temp Surface Temp Wattage Ambient 40°C Surface Temp
Code Code Code Temp (°C) Code Temp (°C) Code Temperature Code Temp (°C) Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T3A T3 T3 160 T3C 160 T3C 50 T3C 200 T3
70 T3A T3 T3 160 T3C 160 T3C 70 T3 200 T3
100 T2B T2C T2C 160 T3C 160 T3C 100 T2B 200 T3
150 T2A T2 T2 200 T3 N/A N/A 150 T2B 200 T3
250 N/A N/A N/A N/A N/A N/A N/A 250 N/A N/A N/A
METAL HALIDE METAL HALIDE
100 T2 N/A N/A N/A N/A N/A N/A 100 T2 N/A N/A
175 T2 N/A N/A N/A N/A N/A N/A 175 T2 N/A N/A
250 N/A N/A N/A N/A N/A N/A N/A 250 T1 N/A N/A
400 N/A N/A N/A N/A N/A N/A N/A 400 N/A N/A N/A
MERCURY MERCURY
100 T2B T2A T2A 160 T3C 160 T3C 100 T2B N/A N/A
175 T2 T1 N/A N/A N/A N/A N/A 175 T2 N/A N/A
250 N/A N/A N/A N/A N/A N/A N/A 250 T1 N/A N/A
400 N/A N/A N/A N/A N/A N/A N/A 400 N/A N/A N/A
* Standard max Ambient Temp is 40°C — for 55°C or 65°C, contact factory. ® Registered Trademark of General Electric Company
Data subject to change without notice

H-8/March 2001
GE Lighting Systems, Inc.
FILTR•GARD H2 AND H2U ®

LUMINAIRE TEMPERATURE PROFILE DATA

HAZARDOUS LOCATION LIGHTING


OPTICAL CONFIGURATION OPTICAL CONFIGURATION
8-in. (203mm) Glass Refractor and Guard (Type V5G and V2G) 175W max 12-in. (305mm) Glass Refractor and Guard (Type R5G and R2G) 400W max
MOUNTINGS MOUNTINGS
All Mounting Arrangements All Mounting Arrangements
CLASSIFICATIONS CLASSIFICATIONS
Class I, Division 2 Class II, Division 1, Class I, Division 2 Class II, Division 1,
Groups E, F, G; Class II, Groups E, F, G; Class II,
Division 2, Group G; & Division 2, Group G; &
Class III, Divisions 1, 2 Class III, Divisions 1, 2
Groups A, B, C, D Groups E, F, G Groups A, B, C, D Groups E, F, G
Max Max * Max * Maximum Max Max Max * Max * Maximum Max
Ambient Ambient Ambient Luminaire Ambient Ambient Ambient Ambient Luminaire Ambient
Lamp 40°C 55°C 65°C External 40°C Lamp 40°C 55°C 65°C External 40°C
Wattage Temp Temp Temp Surface Temp Wattage Temp Temp Temp Surface Temp
Code Code Code Temp (°C) Code Code Code Code Temp (°C) Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T3B T3A T3 160 T3C 50 T3B T3A T3 160 T3C
70 T3B T3A T3 160 T3C 70 T3B T3A T3 160 T3C
100 T3 T2D T2D 160 T3C 100 T3 T2D T2D 160 T3C
150 T2B T2A T2A 160 T3C 150 T2B T2A T2A 160 T3C
250 N/A N/A N/A N/A N/A 250 T1 N/A N/A 160 T3C
400 T1 N/A N/A 160 T3C
METAL HALIDE
100 T2B N/A N/A 160 T3C METAL HALIDE
175 T2B N/A N/A 160 T3C 100 T2B N/A N/A 160 T3C
250 N/A N/A N/A N/A N/A 175 T2B N/A N/A 160 T3C
400 N/A N/A N/A N/A N/A 250 T2A N/A N/A 160 T3C
400 T2A N/A N/A 160 T3C
MERCURY
100 T2C T2B T2B 160 T3C MERCURY
175 T2A T2 N/A 160 T3C 100 T2C T2B T2B 160 T3C
250 N/A N/A N/A N/A N/A 175 T2A T2 N/A 160 T3C
400 N/A N/A N/A N/A N/A 250 T1 N/A N/A 160 T3C
400 T1 N/A N/A 160 T3C

OPTICAL CONFIGURATION OPTICAL CONFIGURATION


Universal Refractor with Guard (Type W5G) 175 Watts Maximum ®
ALGLAS finished Enclosed Reflector and Guard (Type EG) 400 Watt Max
MOUNTINGS MOUNTINGS
All Mounting Arrangements All Mounting Arrangements
CLASSIFICATIONS CLASSIFICATIONS
Class I, Division 2 Class II, Division 1, Class I, Division 2 Class II, Division 1,
Groups E, F, G; Class II, Groups E, F, G; Class II,
Division 2, Group G; & Division 2, Group G; &
Class III, Divisions 1, 2 Class III, Divisions 1, 2
Groups A, B, C, D Groups E, F, G Groups A, B, C, D Groups E, F, G
Max Max * Max * Maximum Max Max Max * Max * Maximum Max
Ambient Ambient Ambient Luminaire Ambient Ambient Ambient Ambient Luminaire Ambient
Lamp 40°C 55°C 65°C External 40°C Lamp 40°C 55°C 65°C External 40°C
Wattage Temp Temp Temp Surface Temp Wattage Temp Temp Temp Surface Temp
Code Code Code Temp (°C) Code Code Code Code Temp (°C) Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T2D T3 T3 100 T5 50 T3B T3A T3 160 T3C
70 T2D T3 T3 100 T5 70 T3B T3A T3 160 T3C
100 T2D T2C T2C 100 T5 100 T3 T2D T2D 160 T3C
150 T2A T2 T2 160 T3C 150 T2B T2B T2A 160 T3C
250 N/A N/A N/A N/A N/A 250 T1 N/A N/A 160 T3C
400 T1 N/A N/A 160 T3C
METAL HALIDE
100 T2A N/A N/A 160 T3C METAL HALIDE
175 T2A N/A N/A 160 T3C 100 T2B N/A N/A 160 T3C
250 N/A N/A N/A N/A 175 T2B N/A N/A 160 T3C
400 N/A N/A N/A N/A 250 T2A N/A N/A 160 T3C
400 T2 N/A N/A 160 T3C
MERCURY
100 T2B T2A T2A 120 T4A MERCURY
175 T2 T1 N/A 160 T3C 100 T2D T2B T2A 160 T3C
250 N/A N/A N/A N/A 175 T2 T2 N/A 160 T3C
400 N/A N/A N/A N/A 250 T1 N/A N/A 160 T3C
N/A = Not Applicable
400 T1 N/A N/A 160 T3C
® Registered Trademark of General Electric Company * Standard max Ambient Temp is 40°C — for 55°C or 65°C, contact factory.
Data subject to change without notice

GE Lighting Systems, Inc. March 2001/H-9


FILTR•GARD H2 AND H2U ®

LUMINAIRE TEMPERATURE PROFILE DATA


HAZARDOUS LOCATION LIGHTING

OPTICAL CONFIGURATIONS OPTICAL CONFIGURATIONS OPTICAL CONFIGURATIONS


Acrylic or Polycarbonate 12-inch Acrylic or Polycarbonate 12-inch Acrylic or Polycarbonate 12-inch
(305mm) Refractor Type V (A5G, L5G) (305mm) Refractor Type V(A5G, L5G) and (305mm) Refractor Type V (A5G, L5G) and Type II (A2G, L2G)
and Type II (A2G, L2G) Type II (A2G, L2G)
MOUNTINGS
MOUNTINGS MOUNTINGS All Mounting Arrangements
All Mounting Arrangements All Mounting Arrangements
CLASSIFICATIONS
CLASSIFICATIONS CLASSIFICATIONS Non-Hazardous Areas–
Class I, Division 2, Groups A, B, C, D Class II, Division 2, Group G UL1598 Suitable for Wet Locations
GROUPS A, B, C, D GROUP G PARAMETERS FOR USE
Max Luminaire Max Amb In non-classified areas these refractors may be used
Lamp External Surface 40°C with high intensity discharge (HID) lamps up to 150
Wattage Max Amb 40°C Temp Code Temp °C Temp Code watts maximum.
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T2C 120 T4A
70 T2C 120 T4A
100 T2C 120 T4A
WARNING–Do not use GE Multi-Vapor® II
150 T2C N/A N/A MXR175 lamps in explosion proof or hazardous
MERCURY MERCURY duty fixtures because they have higher bulb
temperatures than standard 175-watt metal
100 T2C 120 T4A halide lamps and may exceed the temperature
rating of these fixture types.
LIMITATIONS
Under the appropriate conditions, H2 and H2U luminaires present. H2 and H2U luminaires are UL Listed for Class I, Divi-
may be used in a Class I, Division 2 location as follows: sion 2 and comply with NEC Article 501-9(b)(2) as “tested and
H2 and H2U Filtr•Gard® luminaires are suitable for use when, found incapable of igniting the gas or vapor if the ignition
under normal conditions, the maximum lamp temperature temperature is not exceeded”.
does not exceed the ignition temperature of the gas or vapor

OPTION–AUTOMATICALLY SWITCHED QUARTZ*


Available for Class II, Division 1 and 2 and Class III Only
OPTICAL CONFIGURATIONS OPTICAL CONFIGURATIONS CLASSIFICATIONS
8-inch (203mm) glass refractor 12-inch (305mm) glass refactor and Non-Hazardous Areas–UL1598 Listed
(V5G and V2G) guard (R5G and R2G) Suitable for Wet Locations
MOUNTINGS MOUNTINGS OPTICAL CONFIGURATIONS
All mountings except All mountings except
low profile low profile Small Globe with Guard H2000-GG
Large Globe with Guard H2000-FG
CLASSIFICATIONS CLASSIFICATIONS
Class II, Division 1, Groups E, F, G Class II, Division 1, Groups E, F, G
Class II, Division 2, Group G Class II, Division 2, Group G
Class III Class III Small Refractor with Guard H2000-V5G,
H2000-V2G
GROUPS E, F, G GROUPS E, F, G Large Refractor with Guard H2000-R5G,
H2000-R2G
Max Maximum Luminaire Max Maximum Luminaire
Lamp Amb External Surface Temp Amb External Surface Temp
Wattage °C Temperature in °C Code °C Temperature in °C Code Industrial Reflector with Guard H2000-EG
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS) MOUNTINGS
50 40 160 T3C 40 160 T3C All mountings except
70 40 160 T3C 40 160 T3C low profile
100 40 160 T3C 40 160 T3C
150 N/A N/A N/A 40 165 T3B PARAMETERS FOR USE
250 N/A N/A N/A 40 165 T3B
400 N/A N/A N/A 40 165 T3B 1. Small Globe with Guard H2000-GG can be used up to
175 watts HID
METAL HALIDE METAL HALIDE
2. Large Globe with Guard H2000-FG can be used up to
175 N/A N/A N/A 40 165 T3B 250 watts HID
250 N/A N/A N/A 40 165 T3B
400 N/A N/A N/A 40 165 T3B 3. Small Refractors (8-inch)(203mm) with Guard
H2000-V5G and H2000-V2G can be used
MERCURY MERCURY up to 175 watts HID
100 N/A N/A N/A 40 165 T3B 4. Large Refractor (12-inch)(305mm) with Guard
175 N/A N/A N/A 40 165 T3B H2000-R5G and H2000-R2G, and
250 N/A N/A N/A 40 165 T3B Industrial Reflector with Guard H2000-EG can be used
400 N/A N/A N/A 40 165 T3B up to 400 watts HID

*LIMITATIONS–AUTOMATICALLY SWITCHED QUARTZ 5. With automatically switched quartz, some ballast types are not
1. 40°C Maximum Ambient available depending on voltages, wattages and lamp type. We will
2. Cannot use low profile mounting use the ballast type available. If a certain type of ballast is re-
3. 150 watt maximum quartz with HID wattage 50–250 quested by the customer, check the factory as we may not have
4. 250 watt maximum quartz with HID wattage 400 that type available for automatically switched quartz.
N/A = Not Applicable
® Registered Trademark of General Electric Company

H-10/March 2001
GE Lighting Systems, Inc. Data subject to change without notice
MINI•GARD TM LUMINAIRE
TEMPERATURE PROFILE DATA

HAZARDOUS LOCATION LIGHTING


OPTICAL CONFIGURATION
Small Globe and Guard (Type GG) (with or without Standard Dome, Angle Dome or Deep Dome Reflector)

MOUNTINGS
All Mounting Arrangements

CLASSIFICATIONS
Class I, Division 2 (Tested Lamp Envelope Class II, Division 1, Groups E, F, G; SIMULTANEOUS PRESENCE
Surface Temperature) Class II, Division 2, Group G; and Class III
Class I, Division 2 (Tested Class II, Division
+ Other OPTICAL Lamp Envelope Surface 1 or Class II,
CONFIGURATIONS Temperature) Division 2
listed Groups A, B, C, D Groups E, F Group G Groups A, B, C, D Groups
Max Max Max Maximum Max Maximum Max Max
Ambient Ambient Ambient Luminaire Ambient Luminaire Ambient Ambient
Lamp 40°C 55°C 65°C External 40°C External 40°C 40°C
Wattage Temp Temp Temp Surface Temp Surface Temp Temp
Code Code Code Temp (°C) Code Temp (°C) Code Code
HIGH PRESSURE SODIUM (HPS)
50 T2C T2C T2C 165 T3B 165 T3B T2 Groups E,F,G
70 T2C T2C T2C 165 T3B 165 T3B T2 Groups E,F,G
100 T2A T2A T2A 165 T3B 165 T3B T2 Groups E,F,G
150 T1 T1 N/A 200 T3 N/A N/A T1 Groups E,F
METAL HALIDE
70 T2B T2B T2B 160 T3C 160 T3C T2A Groups E,F,G
100 T2B T2B N/A 160 T3C 160 T3C T2A Groups E,F,G
175 T1 N/A N/A 200 T3 N/A N/A T1 Groups E,F

OPTICAL CONFIGURATION
8-in. (203mm) Glass Refractor and Guard (Type V5G and V2G)
MOUNTINGS
All Mounting Arrangements
CLASSIFICATIONS
Class I, Division 2 (Tested Lamp Envelope Class II, Division 1, SIMULTANEOUS PRESENCE
Surface Temperature) Groups E, F, G; Class II,
Division 2, Group G; & Class I, Division 2 (Tested Lamp Class II, Division 1 or
Class III, Divisions 1, 2 Envelope Surface Temperature) Class II, Division 2

Groups A, B, C, D Groups E, F, G Groups A, B, C, D Groups


Max Max Max Maximum Max Max
Ambient Ambient Ambient Luminaire Ambient Ambient
Lamp 40°C 55°C 65°C External 40°C 40°C
Wattage Temp Temp Temp Surface Temp Temp
Code Code Code Temp (°C) Code Code
HIGH PRESSURE SODIUM (HPS)
50 T2D T2D T2C 135 T4 T2 Groups E,F,G
70 T2D T2D T2C 135 T4 T2 Groups E,F,G
100 T2A T2A T2A 135 T4 T2 Groups E,F,G
150 T2 T2 N/A 135 T4 T1 Groups E,F,G
METAL HALIDE
70 T2C T2C T2C 160 T3C T2A Groups E,F,G
100 T2B T2B N/A 160 T3C T2A Groups E,F,G
175 T1 N/A N/A 160 T3C T1 Groups E,F,G
N/A = Not available

LIMITATIONS
Under the appropriate conditions, MGH and MGHU exceed the ignition temperature of the gas or vapor present.
Mini•Gard luminaires may be used in a Class I, Division 2 Mini•Gard luminaires are UL Listed for Class I, Division 2 and
location as follows: comply with NEC Article 501-9(b)(2) as “tested and found
Mini•Gard luminaires are suitable for use when, under nor- incapable of igniting the gas or vapor if the ignition tempera-
mal conditions, the maximum lamp temperature does not ture is not exceeded”.

WARNING–Do not use GE Multi-Vapor® II MXR175 lamps in explosion proof or


hazardous duty fixtures because they have higher bulb temperatures than stan-
dard 175-watt metal halide lamps and may exceed the temperature rating of these
fixture types.

TMTrademark of General Electric Company


Data subject to change without notice GE Lighting Systems, Inc. March 2001/H-11
MINI•GARD TM LUMINAIRE
TEMPERATURE PROFILE DATA
HAZARDOUS LOCATION LIGHTING

OPTION–AUTOMATICALLY SWITCHED QUARTZ* * LIMITATIONS–AUTOMATICALLY SWITCHED QUARTZ


Available for Class II, Division 1 and 2 and Class III Only 1. 40°C Maximum Ambient
OPTICAL CONFIGURATIONS 2. With automatically switched quartz, some ballast types are
8-inch (203mm) glass refractor (V5G and V2G) not available depending on voltages, wattages and lamp type.
We will use the ballast type available. If a certain type of
MOUNTINGS ballast is requested by the customer, check the factory as we
All mountings may not have that type available for automatically switched
CLASSIFICATIONS quartz. (Use one 100 watt single-ended DC [Double Contact]
Class II, Division 1, Groups E, F, G bayonet base lamp.)
Class II, Division 2, Group G
Class III

GROUPS E, F, G
Max Maximum Luminaire
Lamp Amb External Surface Temp
Wattage °C Temperature in °C Code
HIGH PRESSURE SODIUM (HPS)
50 40 160 T3C
70 40 160 T3C
100 40 160 T3C
150 40 160 T3C

MINI•GARD FLUORESCENT LUMINAIRE


TEMPERATURE PROFILE DATA
OPTICAL CONFIGURATIONS
Large globe and guard (type FG) with or without standard dome,
angle dome, or deep dome.
MOUNTINGS
All mounting arrangements

CLASSIFICATIONS SIMULTANEOUS PRESENCE


Class I, Division 2, Groups A,B,C,D Class II, Divisions 1 and 2, Class I, Division 2, Groups Class II, Divisions 1
(Tested Lamp Envelope Surface Groups E, F, G A,B,C,D (Tested Lamp and 2,
Envelope Surface Temp) Groups E, F, G
Temp)

GROUPS A,B,C,D GROUPS E,F,G


Maximum Maximum Luminaire Maximum
Lamp Ambient 40°C External Surface Ambient 40°C Maximum Ambient 40°C
Wattage Temperature Code Temperature (°C) Temperature Code Temperature Code
FLUORESCENT
13 T2D 85 T6 T2D
26 T2D 85 T6 T2D
52 T2D 85 T6 T2D

TEMPERATURE CODE
IDENTIFICATION IDENTIFICATION
NUMBER DEGREES C NUMBER DEGREES C
T1 450 T3A 180
MAXIMUM T2 300 T3B 165
TEMPERATURE T2A 280 T3C 160
RANGE T2B 260 T4 135
IDENTIFICATION T2C 230 T4A 120
NUMBER T2D 215 T5 100
T3 200 T6 85

TMTrademark of General Electric Company

H-12/March 2001
GE Lighting Systems, Inc. Data subject to change without notice
PERMA•GARD AND H4 FLUORESCENT ®

LUMINAIRES, P-154 AND

HAZARDOUS LOCATION LIGHTING


PF-400 POWERFLOOD FLOODLIGHTS
® ®

TEMPERATURE PROFILE DATA


PERMA•GARD LUMINAIRE PERMA•GARD LUMINAIRE PERMA•GARD LUMINAIRE
OPTICAL CONFIGURATION OPTICAL CONFIGURATION OPTICAL CONFIGURATION
Low Bay Refractor, 15-inch (381mm) (LB5) Angled Low Bay Refractor, 15-inch Globe with/without guard (GN, GG)
(381mm) (ALB5) and/or external reflector
MOUNTINGS MOUNTINGS (DR5, AR5); Low Bay refractor,
15-inch (381mm) (LB5); Low Bay
Rigid Conduit, Vertical Suspension Rigid Conduit, Vertical Suspension refractor, 22-inch (559mm) (TA2);
CLASSIFICATIONS CLASSIFICATIONS Angled Low Bay refractor, 15-inch
(381mm) (ALB5)
Class I, Division 2 Class I, Division 2
MOUNTINGS
GROUPS A,B,C,D GROUPS A,B,C,D + Other OPTICAL
Maximum Maximum Maximum Maximum CONFIGURTIONS Rigid Conduit, Vertical Suspension
listed CLASSIFICATIONS
Lamp Ambient Ambient Lamp Ambient Ambient
40 o C 55 o C 40 oC 55 oC UL1598 listed; UL1598, Suitable for
Wattage Wattage Lamp Wet Locations; UL1598, Outdoor
Temperature Temperature Temperature Temperature Wattage Salt Water
Code Code Code Code
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
50 T2C N/A 50 T2C N/A 50 150 Watts Maximum
70 T2C N/A 70 T2C N/A 70 150 Watts Maximum
100 T2C N/A 100 T2C N/A 100 150 Watts Maximum
150 T2C N/A 150 T2C N/A 150 150 Watts Maximum
METAL HALIDE METAL HALIDE METAL HALIDE
175 N/A N/A 175 N/A N/A 175 175 Watts Maximum (Except ALB5 & LB5)
MERCURY MERCURY MERCURY
100 T2B T2B 100 T2B T2B 100 175 Watts Maximum
175 T2B N/A 175 T2B N/A 175 175 Watts Maximum

PERMA•GARD LUMINAIRE PERMA•GARD LUMINAIRE P-154 POWERFLOOD FLOODLIGHT


OPTICAL CONFIGURATION OPTICAL CONFIGURATION (For Hazardous Locations)
Small Globe (GN) Low Bay Refractor, 22-inch (559mm) (TA2) OPTICAL CONFIGURATION
NOTE: Temperature ratings the same for
globe with/without guard and/or external Optical assembly with heat and
reflector MOUNTINGS shock resistant tempered glass
MOUNTINGS Rigid Conduit, Vertical Suspension CLASSIFICATIONS
Rigid Conduit, Vertical Suspension Class I, Division 2
CLASSIFICATIONS CLASSIFICATIONS Lamp Maximum
+ Other OPTICAL
Class I, Division 2 Wattage Ambient 25 oC
CONFIGURTIONS Class I, Division 2 Temperature Code
listed GROUPS A,B,C,D GROUPS A,B,C,D
HIGH PRESSURE SODIUM (HPS)
Maximum Maximum Maximum Maximum 70 T2A
Lamp Ambient Ambient Lamp Ambient Ambient 100 T2A
Wattage 40 o C 55 o C Wattage 40 o C 55 o C 150 T2A
Temperature Temperature Temperature Temperature 200 T1
Code Code Code Code 250 T1
400 N/A
HIGH PRESSURE SODIUM (HPS) HIGH PRESSURE SODIUM (HPS)
METAL HALIDE
50 T3A N/A 50 T2C N/A
70 T3 N/A 70 T2C N/A 175 T1
100 T2C N/A 100 T2C N/A 250 T1
150 T2A N/A 150 T2C N/A 400 N/A
METAL HALIDE METAL HALIDE
175 T2 N/A 175 T2B N/A
MERCURY MERCURY
PF-400 POWERFLOOD FLOODLIGHT
100 T2 T2 100 T2B N/A
(For Hazardous Locations)
175 T2 N/A 175 T2B N/A OPTICAL CONFIGURATION
Classifications: Class I,
H4 FLUORESCENT LUMINAIRE TEMPERATURE PROFILE DATA 40O C Division 2
Class II Ambient 25°C
Class I Division 1 Simultaneous
Division 1 Groups Presence Lamp Temperature °C
Groups C and D E, F and G Class III Class I and II Lamp Wattage Vertical Horizontal
T6 T6 T6 T6 HIGH PRESSURE SODIUM (HPS)
250 T1 T1
TEMPERATURE CODE 400 T1 T1
IDENTIFICATION IDENTIFICATION METAL HALIDE
NUMBER DEGREES C NUMBER DEGREES C
MAXIMUM T1 450 T3A 180
250 T1 T1
TEMPERATURE T2 300 T3B 165 400 T1 T1
RANGE T2A 280 T3C 160 N/A=Not available
IDENTIFICATION T2B 260 T4 135
NUMBERS T2C 230 T4A 120
T2D 215 T5 100
T3 200 T6 85

® Registered Trademark of General Electric Company