18
Product Information Section
Product Identification tntormation
station 17 oes
12 Lead Deta Configuration
“oxminals T6 and TS become the neural connections when the
terminals ae Sed futher and when the erminals are ground,
“This relocs the terminal T2 and T10 connection ashe high phase
Grounding the Frame
In any generator set installation, the frame of the
Generator must be positively connected to an earth
Ground or the frame of the generator must be
Positively connected to the hull of a vessel. This
Connection is the first connection that should be
‘made at the installation. This connection is the
last connection that should be removed, If the
generator Set is on flexible pads or resilient pads,
the ground connection must be flexible in order to
avoid possible breakage in later operation
Ground connection cables oF straps should have at
least the current carrying capacity of the largest
line lead to the connected load, Joints in cables or
straps must be clean, free of electrical resistance,
and protected trom possible oxidation. Bolted
‘ground connection joints eventually oxidize, These
Joints are also frequent sources of radio frequency
interference (RFI). Joints should be silver soldered
and joints shautd also be bolted, These bolts will be
elecitically reliable and mechanically reliable.
Neutral Connections
(On Wye Configuration Generators, the neutral lead
should be attached to ground. This connection
should be made at installation. The neutral lead is
rounded in order to prevent load-side equipment
damage
If the neutral wire is grounded and one of the
phase feads becornes grounded, the excessive
Current will open 4 load circuit breaker. In addition,
this excessive current will cause the generator
voltage to collapse. The result depends on the
folowing factors: the particular generator's electrical
characteristics, type of fault, and trip rating of the
circuit breaker. An undervoltage device may be
required in order to provide an adequate short
circuit protection.
‘There are some instances when the neutral wire
should not be grounded. An ungrounded generator
nnoutral fead is acceptable when measures have
been taken in order to prevent grounds to the
phase leads, An example of such meagures are
ground fault protective circuits. When ground
fault protective circuits are used, the entire group
of distribution circuits should be studied. The
entire group of distribution circuits should then be
uteated as a system, If a new distribution system
' being Geveloped, the owner should confer with
2 consultant that is cerified and registered. fan
existing system should be modified for ground faut
protection, the owner should also confer with a
consultant that is Certified and registered.
Single Units
In a three-phase, four-wire system, the neutral
‘wire should be grounded according to local wiring
codes.
When definite measures need to be taken in order to
prevent grounds to the load leads, an ungrounded
neutral can be used, Be sure to check yaur local
wiring codes.
Multiple Units
Whee multiple generators are operated in parallel,
all the neutral connections may be grounded. In
this case, there may be circulating current through
the neutral connections. In order to eliminate the
possibility of circulating currents, ground the neutral
af only one generator. If multiple generators are
alternated on a line, a switch should be installed
in each generator's neutral ground circuit. In this
case, all neutral ground circus except one can
bbe opened. Be sure that one of the neutral ground
circuits is closed.16
Product Information Section
Product Identitication information
Parallel to a Utility
There will be occasions when @ Wye connected
generator is paralleled with a utiity system (infinite
bus). On these occasions. the utility system's
step-down transformer may also have 2 Wye
connection. The grounding of both of the Wye
neutral connections may result in circulating
currents through the neutral connections. The
coordination of ground fault protection requires
sludy of the entire system. This study should be
done by a consultant that is familiar with generator
systems. This consultant should be registered and
cerlified. This study will determine the grourding
method that should be used
overeat
Voltage Connections
SMCS Code: 4450
Three-Phase Voltage Connections
The Wye Configuration and the Delta Configuration,
are given in the following diagrams.
The terminals must be connected securely. The
terminals must also be insulated with a good quality
electrical tape.
If a Delta Configuration is being used, the generator
winding pitch must be two-thirds, If the generator
winding pitch is not two-thirds, there will be
cireuiating current within the Delta. This circulating
current will cause aditional heat in the generator
siator. In such cases, the generator must be
erated
Wye Configuration Diagrams
6 Lead Generators
\
_
gh ‘tov
of,
he
|
stb
_ 7
core
ustraton 18
“Typical ye Conquration (60 Hz Si Lead)
10 Lead Generators
| 480v
eee
inastraon 18 oases
“Typical Serias Wye Configuration (60 He Ten Lead)
(nly for 38068 generator sets and 3408C generator sts
This is typi Fgh wokage connection,17
Product Information Section
Product Identification Information
24ov
| 2a0v
usration 20 =
“pica Parallel Wye Configuration (60 Hz Ten Lead)
(Only for 33068 and 34060 generator sets
‘This typical low vetage conection,
12 Lead Generators
uswation 21 ESTs
“Wpical Series Wye Contigration (60 Hz wove Lead)
‘Only or 34066, 36120, and 3500 series generator sets
‘This i atypical hgh vltage connection.
musta 22 oo
“Typical Paralll Wye Configuration (60 He Twelve Lead)
(Onl for 34086, 34120, and 3500 series generator sats
‘Tiss atypical hgh vltage connection.
Delta Configuration Diagrams
6 Lead Generators
Imusraton 23 soars
‘Typical Delia Configuration (60 He Six Lean)