You are on page 1of 1

1.

I/O CONFIGURATIONS
CPCO medium/Large FanWall Management- EBM I/O configuration

Analog inputs Description Type


U1 Prefilter differential pressure 4-20mA
U2 Final filter differential pressure 4-20mA
U3 Hepafilter differential pressure 4-20mA
U4 Gasphase filter differential pressure 4-20mA
U5 Total Static pressure 4-20mA
U6 Airflow setpoint 4-20mA

Digital inputs Description Type


ID1 Remote On/Off NO/NC
ID2 Fire alarm NO/NC

ID3 Alarm reset NO/NC

ID4 Damper interlock NO/NC

ID5 Emergency stop NO/NC

Digital outputs Description Type


NO1 Prefilter status NO
NO2 Final filter status NO

NO3 Hepa filter status NO

NO4 Gasphase filter status NO

NO5 TSP status NO

NO6 General alarm NO

NO7 Motor alarm general NO

NO8 Damper control NO

Analog outputs Description Type


Y1 Airflow feedback 0-10V