Active Power Voltage Current cos Ɵ

Main Trafo Net #1 (20 kV) 7877kw 20.14 kV 226.93 0.995

Generator #1 (from GCB 6.3 kV) 8800 kw 6310 V 823A 0.978

UAT #1 (from 400 V) 837 kw 390 V 1433 A 0.86

Common 400 V 457 kw 393 V 772 A 0.86

APC Estimate = Auxiliary + (1/2 x common) = 837 + (457/2) = 1065.5 kw

Active Power Voltage Power Factor


Auxiliary Unit 2 total
837 390 0.86

Current Voltage Calculate active power


BFP 1A 168 390 97.59
BFP 1B 163 390 94.69
BFP 1C 175 390 101.66
SAF 1A 28 390 16.27
SAF 1B 20 390 11.62
IDF 1A 97 390 56.35
IDF 1B 92 390 53.44
FDF 1A 40 390 23.24
FDF 1B 36 390 20.91
CWP 1A 225 390 130.71
CWP 1B 223 390 129.54
MCC TURBINE 171 390 99.34
MCC ESSENTIAL 28 390 16.27
MCC BOILER 4 390 2.32

Active Power Voltage Power Factor


Common 400 V
729 390 0.86

Current Voltage Calculate active power


MCC Compressor 40 393 23.42
MCC Water system 22 393 12.88
Ship Unloader 0 393 0.00
Cooling Tower 1 127 393 74.34
Cooling Tower 2 125 393 73.17
Cooling Tower 3 138 393 80.78
Drain Pump 1 0 393 0.00
Drain Pump 2 0 393 0.00
MCC WTP 2 393 1.17
Turbine Over Head Crane 0 393 0.00
MCC WWTP 0 393 0.00
MCC BOP Service 56 393 32.78
MCC Coal Handling 65 393 38.05
DB 7 (Fan MPB) 70 393 40.98
DB 6 (MPB street Lioghting) 2 393 1.17
DB 4 (Boiler 1,2) 0 393 0.00
DB 3 (laboratory , WTP) 0 393 0.00
DB 2 (Warehouse WWTP) 0 393 0.00
DB 1 (Admin,mosque,guardhouse) 17 393 9.95
DB 5 Main Building Plant 0 393 0.00
MCC Fly Ash Handling 86 393 50.34