You are on page 1of 10

Summary The parameters that should be considered at the design stage of a combined heat and power

(CHP) project have been determined for situations when absorption refrigeration is to be used. Single
and double stage chillers are considered together with system features such as hot water, steam or heat
recovery driven, in terms of the hot temperature heat source from the CHP plant. Finally the chiller effi-
ciency, plant size and the electric consumption of cooling towers and condenser water pumps are
analysed to achieve an energy efficient system design.

Absorption chillers applied to CHP systems


R Tozer† MSc CEng MCIBSE and R James‡ BSc MEng PhD CEng FIMechE MCIBSE FInstR
&dag er; Waterman Gore, Mechanical & Electrical Consulting Engineers, Bastille Court, 2 Paris Garden, London SE18ND, UK
&Dag er; School of Engineering Systems and Design, South Bank University, London, UK

List of symbols Absorption chillers driven by hot water and steam were mar-
keted seriously in the 60s until the energy efficiency issues
a Thermodynamic ratios ruled this technology out for most of the world in the 1970s.
A Difference The exception was Japan, which due to a gas expansion poli-
cop Coefficient of performance cy, bought the absorption technology and developed two
c Specific heat capacity (kj kg-1K-l) stage and direct fired units, to become world leaders in this
j Cycle work (kJ kg-i) technology. A reflection of this was that in 1984, about 900
MW of absorption cooling capacity was sold in Japan, with
lt Specific enthalpy (kJ kg’K’) machine size ranging from 140 to 1400 kW of cooling capaci-
HDRHeat dissipation ratio
no Mass flow rate (kg s-1) ty, employing lithium bromide/water technology(2). The
absorption market in North America is rapidly growing, from
Q Heat (kW) $17 million in 1989 to $61 million in 1992. The market for
S Entropy (kJ kg’K-’) cogeneration equipment to the year 2000 has been estimated
T Absolute temperature(K) at $30 billion by Frost and Sullivan, a major market research
firm~3~.
Suffixes
a Absorber The structure of electricity costs, with high maximum
c Condenser demand and availability charges, prioritising primary energy
cc Cooling cycle consumption with respect to final energy consumption, polit-
ical commitments and financial help, together with environ-
comp Compressor mental issues such as the ozone depletion potential (ODP),
cond Condensate
dc Driving cycle global warming potential (GWP) and acid emissions have
motivated designers to reconsider the absorption refrigeration
e Evaporator options available on the market. These are the single and
eg Exhaust gases double stage direct fired absorption chillers either with
ei Exhaust gases into chiller heaters4 which fire on natural gas, propane, kerosene or oil or
eo Exhaust gases out of chiller fired by other means as used for CHP projects. These include
fg Refers to change of phase at constant pressure the single stage hot water or steam fired chiller, the double
g Generator stage steam fired chiller and the double stage heat recovery
hw Hot water supply chiller. This last group of chillers, that is not directly gas
jw Jacket water fired, is used on CHP projects and is the one whose design
p Pump aspects are considered in relation to the overall CHP plant.
s Solution
st Steam
2 Ideal absorption cycles
1S Single stage
2S Double stage
In order to set the criteria for selection and operation of
1 Introduction absorption chillers, it is necessary to understand the theoreti-
cal principles of the ideal cycles. This aids the understanding
of the way real systems operate.
The absorption principle of refrigeration was amply demon-
strated by Faraday in his expcriment with the bent glass tube The single-stage absorption chiller schematic is shown in
charged with ammonia and silver chloride in 1824. The affin- Figure 1 and the ideal cycled is represented in Figure 2.
ity of some vapours, such as ammonia for water, or water for
lithium bromide, is the basis of absorption designs. These The only correct way to represent absorption cycles such as
were first applied in industry by Nicolle who patented his ice that shown in Figure 1 on the T - S diagram is to represent
making machine in 1861. The units operated on ammonia the cycle with a single closed line as in Figure 2. Detailed
and were first used for freezing meat for shipping from information on the ideal assumptions claimed for such a rep-
Sydney, Australia to Europe and had very low cops « 0.2)’>. resentation are outside the scope of this present work.

179
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
cally be achieved for a single stage unit. Also to maximise the
COP, both the evaporator and absorber temperatures will have
to be close. This is similar to a vapour compression cycle
where the cop of the Carnot ideal cycle improves as the hot
and cold source temperatures converge.
A high generator temperature will not have any effect on the
ideal cycle other than elevating the condenser temperature. In
a real system the COP will decrease although a smaller chiller
could sometimes be selected due to increased temperature dif-
ferences in the generator and condenser.
For the following formulae developed the relationship of
evaporator and absorber absolute temperatures have been
chosen to represent the thermodynamic ratio a. The single-
stage cop is given by

The heat dissipated by a high-temperature cycle condenser


can be used to drive a generator of a low temperature cycle,
and thus for the double-stage absorption chiller:

The double-stage absorption chiller schematic can be seen in


Figure 3 and the ideal cycle($,’) is represented in Figure 4
Similarly, for further stages using the condenser heat to drive
the generator of a lower-temperature cycle:
Triple-stage cop:
Figure 1 Schematic of single-stage absorption chiller

N-stage cop:
, ... , . ,.

Superficial examination of the above indicates that the maxi-


mum ideal cop is equal to the number of stages N and that to
improve any of these ideal cycles the difference between the
evaporator and absorber temperatures (or generator and con-
denser temperatures) has to decrease.
Other ideal multistage cycles have been developed using the
absorber heat from high temperature cycles to drive genera-
tors of lower temperature cycles. These have the same perfor-
mance as the cycles previously described and equations 4 to 7
also apply. Many combinations are possible but not commer-
cially available(’,).

3 Real absorption cycles


Figure 2 Single-stage, idealised absorption cycle on the
temperature-entropy diagram
3.1 Absorption cycles on PIX diagrams
However information is available(’-6) and a summary is given In practice the pressure-temperature-concentration chart
in Appendix 1. (PTX) is widely used for representing absorption cycles work-
The work of the two sub-cycles Fdc and Fcc are equal and ing with the LiBr/water binary mixture. These charts have
therefore the four process temperatures cannot be arbitrarily the advantage of representing refrigerant and solution paths
chosen but are related by: and specially the crystallisation sector. Figures 5 and 6 repre-
sent a single and the paraflow double stage cycles on the PYX
diagrams:
The ideal cop (reversible cycle) is a function of the thermody- Absorption technology is rapidly developing and when deal-
namic ratio defined as: ing with real cycles it is suggested that these should be dis-
cussed in detail with the manufacturers at the initial design
stage. Important topics to be considered are:
And the ideal cop is defined as: --

Adequate chiller selection (single/double stage, series


1/11/paranow, heat source) _

If the temperature ratios are considered it is clear that the -


Chilled and condenser water temperatures, flow rates and
limiting value of unity is the maximum cop that can theoreti- volumes

180 Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015


Figure 3 Schematic of double-
stage paraflow absorption chiller

-
Hot water supply (temperature, control, simultaneous
with chilled water)
-

Cooling (condenser) water, cooling tower by-pass


-

Crystallisation prevention involving consideration of the


dilution cycle, non-condensable gas purging, avoiding
low condenser water temperatures.
-

Purging system
-
Performance (part loads, varying condenser and chilled
water temperatures)
-

Scope of supply: control valves, lagging (hot and cold


surfaces), antivibration mounts
-
Control system (pneumatic, electronic, microprocessor)
and BEMS interface and strategy.
Figure 4 Double-stage, idealised absorption cycle on the -

Factory location, delivery, shipping, vessel codes, test


temperature-entropy diagram certificates

Figure 5 Single-stage real cycle


on the prx diagram

Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015 181


0

Figure 6 Double-stage real cycle


(parailow) on the PTX diagram
-
Internal pumps (life, change-over, replacements, electric temperatures. If Figure 5 is referred to, it can be seen that the
supply) cycle has to work with lower concentrations to allow lower
generator temperatures. As the weak solution concentration is
4 Combined heat and power (cop) practically determined by the cooling medium of the
absorber, the difference of both solution concentrations is fur-
ther reduced from the usual design value of 6%, the difference
A gas utility(9) is promoting the use of absorption refrigera-
between 64% and 58%. This in turn means that a larger circu-
tion. It has described a CHP system of British Gas North
lation of solution between the generator and absorber is
Western as a site with a parallel need for electricity, office
space heating and computer suite cooling. The cooling for the
required for the same amount of refrigerant (water), which
computer suite is provided by a combination of electric and
requires the use of larger chillers. For this very reason the hot
water temperature difference between inlet and outlet is small
absorption chiller units. An overall efficiency for the CHP sys- at low temperatures, i.e. 5K at 80°C, and larger at higher tem-
tem of 90% and a payback period of four years is claimed.
peratures, i.e. 17.5K at 130’C. Using these values an average
One of the major advantages of absorption chillers is the great temperature difference can be expressed in terms of the inlet
flexibility that they offer. To run the refrigeration cycle the hot water temperature as:
only major requirement is heat, which can be supplied in var-
ious forms according to the power plant. Double-stage units
offer an attractive higher cop and the ability to consume This temperature relationship is specific to single stage
higher temperature heat than the single stage absorption absorption chillers and will not necessarily coincide with
units. Absorption chillers can be used with CHP systems as those of the engine jacket water.
shown in Table 1.
The amount of available cooling Qe is given by equation 12
Table 1 Use of absorption chillers with CUP systems . which is derived as follows:

4.1 Single-stage chillers 4.2 Double-stage steam-dri1)81Z chillers .

Although single stage absorption chillers can be fired on low


pressure steam, the most common application is to use the
Many cogeneration systems involve the use of steam at
engine jacket cooling water. Hot water temperatures are avail- approximately 8-15 bar, i.e. hospitals and industrial applica-
able between 70°C to 140°C but although the heat energy .
tions, which is very suitable for steam driven double stage
available will depend on the flow and temperature rise of hot absorption units that are designed for steam at 8 bar. A typical
water, the supply and return temperatures themselves have a cycle is represented in Figure 6.
significant influence on the size of the absorption chiller. These have the further advantage of higher efficiencies due to
Low hot water temperatures require the use of very large the use of a steam condensate cooler employed to preheat the
chillers, when compared to selections with higher hot water refrigerant solution in the low-temperature stage of the
182 Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
absorption unit (Figure 3). The amount of available cooling is such as cooling tower fans and cooling water (absorber and
determined in terms of the available latent and sensible heat: condenser) pumps should also be considered. Appendix 2
gives details of the heat dissipation ratio (HDR), which corre-
sponds to the ratio of cooling tower heat with respect to the

evaporator cooling load. Typical values of HDR of 2.5, I.9 and
4.2 Hot-gas driven double-stage chillers 1.25 correspond to single stage absorption, double stage
In the case of gas turbines and reciprocating engines, the hot absorption and mechanical compression chillers (i.e. centrifu-
gas exhaust can be used directly with hot-gas driven double- gal, screw and reciprocating) respectively. This indicates that
stage absorption units. A typical exhaust gas temperature is single stage absorption chillers are in addition to the lower
500°C for these plants, but a range of temperatures between COP, penalised by a larger HDR on initial and operating costs,
280-800°C (T,) can be used with these hot gas driven absorp- i.e. cooling tower, condenser pumps and pipework.
tion chillers. This has been the advantage of not requiring HDR is useful as a means for checking the data supplied by
heat exchangers, condensate pumps or other steam related manufacturers. There has to be a correlation between the HDR
equipment and is mostly used in conjunction with gas tur- calculated directly from condenser and chilled water tempera-
bines. The exit gas temperatures from the absorption chiller tures and flow rates with respect to the HDR calculated in
generator range between 180-200°C (T ), which determines terms of the cop. Appendix 3 can be referred to for more
the lower limit of heat available from the exhaust gases. details.
The amount of available cooling is determined in terms of the
heat contained in the exhaust gases at the inlet and outlet of
the absorber chiller generator: 5.2 Cooling water flaw rate
A series of absorption chiller selections was carried out for a
range of design parameters(10). Figure 7 represents the varia-
4.3 Two-phase driven double-stage chillers tion of cop of a 1400 kW (400 TR) single-stage absorption
unit for two hot water temperatures in terms of the cooling
A unique, two-phase, double stage absorption unit has been water flow rate expressed as a function of the temperature rise
developed(3) that operates simultaneously on two different across the absorber/condenser. These figures also indicate the
sources of energy; exhaust heat is captured and drives the
relative size of the cooling water pumps and cooling tower
high temperature (first-stage) generator while engine jacket fans in terms of their electric power, detailed in Appendix 4.
water circulates through a separate hot water heat exchanger
If the size of the cooling towers and condenser water pumps is
connected to the low temperature (second-stage) generator. assumed to vary linearly with the power consumed by each
This solution is commercially available and is desirable when
one, Figure 7 indicates both capital costs and operating costs
a single chilling plant is required. Nevertheless, for large
of the pumps and cooling tower in terms of the cop variation.
installations, it has been found that cheaper options are possi- It should be noticed that relatively high capital investments
ble if a double stage hot gas driven unit is used for the exhaust and electric operating costs are required to achieve a relatively
heat and a separate single stage hot water driven unit is used small cop improvement, this additional electric power is sup-
for the jacket water. Equations 12 and 14 can be used with a
conservative margin for chiller losses to estimate available plied by the cop plant. The cooling water temperature differ-
ence is equal to the cooling water temperature leaving the
cooling. condenser minus the temperature of the water entering the
absorber. The cop variation with the change of cooling water
z

5 Applications flow rate is due to the evaporator to absorber and condenser


to generator temperature ratio variation.
5.1I Heat dissipation ratio (HDR)
HDR is the ratio of absorber and condenser heat dissipated in
5 3 Absorption optimisation criteria with cHp
the cooling tower with respect to the evaporator heat (cooling
load). Not only should the absorption chiller be considered Figure 8 indicates the most common absorption chillers used
but the energy consumption of significant ancillary plant in cogeneration applications(&dquo;).

Figure 7 Chiller cop and electric


power consumption versus cooling
water flow rate

Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015


183
These types of units are indicated in terms of the temperature tend to the alternative use of steam at the equivalent tempera-
of the heat source and include: ture.
-

Single-stage, hot water fired If a pressurised hot water system is to be used, above 100°C,
-

Double-stage, steam fired from an efficiency point of view the optimum selection is at
115°C as indicated in Figure 8. At higher hot water tempera-
-

Double-stage, hot gas fired. tures it is possible to select a smaller, more economic machine
The heat source temperatures refer to supply hot water tem- despite a lower cop. This has the further disadvantage of
peratures for the single stage chillers, equivalent steam satura- operating the generator at higher temperatures in the pres-
tion temperatures for the double stage steam chillers, and ence of LiBr/water solution, which can accelerate corrosion

supply exhaust gas temperature for double stage heat recovery processes. Both the design and materials of the generator
chillers. tubes should be considered in terms of higher temperatures if
the chiller life is not to be reduced.
The same cooling capacity of 1400 kW was assumed for all
cases, the total capacity cost of absorption chillers, cooling If the hot water is supplied at a relatively high temperature
water pumps (2 no.), and cooling towers is indicated together say 130°C and returns at a temperature below the optimum
with the heat and electric energy required by the plant. The 115°C, the use of a mixing valve and pump is strongly recom-
objective of this figure is to indicate the variation of the para- mended to mix the supply hot water temperature to 115°C. It
meters relative to the absorption unit when these are consid- will enable the absorption chiller to have maximum efficiency
ered within the context of a cogeneration design with absorp- and the sizing of it should not be affected as the return tem-
tion cooling. Refer to Appendix 5 for details. Figure 8 gives perature remains the same with this mixing arrangement. An
details of: option is to increase the jacket water flow rates that would
lower the outlet temperatures and another option is to use
-
Plant costs (absorption chiller, two condenser water
pumps and cooling tower)
parallel flow through the jacket and hot gas recovery coils as
this would increase the flow rate, maintain the same pressure
-

Heat power consumed by the absorption chiller drop and reduce the outlet temperature with an increase of
recovered heat.
-
Electric power consumed by absorption chiller, con-
denser pumps and cooling tower fans.
5.S Optimisatimi criteria for double-stage steam fired chillers
The best selection is at 8 bar, although chillers can be selected
5.4 Optimisation criteria far single-stage chillers to work at 9 bar sometimes to reduce the size of the chiller. If
the choice is between using steam for a single or double stage
Although Figure 8 refers to hot water temperatures, a slightly chiller, overall cogeneration economics should be consid-
more economic chiller can be selected if these units are dri- ered(&dquo;). For ideal cycles the overall thermodynamic perfor-
ven on steam at approximately 0.8 bar. mance of both options is identical<12>.
On the basis of hot water, the first decision is whether pres-
surised hot water is to be considered for temperatures above 5.6 Optimisation criteria for double-stage hotga5 driven chillers
100°C. If it is decided to work below 100°C, it is recommend-
ed to design hot water temperatures near to 100°C. Although This unit operates on hot gas exhaust fumes from engines or
Figure 8 refers only to the supply hot water temperature, the turbines, which have much higher temperatures (i.e. 500°C)
chiller selection depends more on the leaving hot water tem- than those of the absorption chiller generator (i.e. 160°C).
perature. Therefore both supply and return hot water temper- Therefore the selection of absorption chillers is independent
atures should be as high as possible. In other words, 93/88°C of the hot gas temperatures. It is very important to check the
is a better selection that 96/85°C due to a higher return tem- hot gas temperature difference and mass flow rate to ensure
perature of 88°C. As the difference of supply and return hot enough available heat can be supplied to the absorption
water temperatures tend to zero, the chiller selection will also chiller in terms of the required cooling load.

Figure 8 Plant costs and


heat/electriral energy’ consumption

184
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
6 Selection criteria for absorption chillers with CHOP 8 Alefeld G Double effect, triple effect and quadruple effect absorption
machines Proc. 16th Int. Cong. Refrig., Paris, 1983 vol. 2 pp951-956
criteria to optimise the absorption 9 Combined heat and power, the way to lower your energy costs in Gas in
Having established the Industry and Commerce (British Gas)
chiller selection once the unit has been determined, it now
10 Tozer R M Absorption refrigeration (principles, cycles and applica-
remains to determine the criteria for selecting the type of tions to cogeneration), Proc. Cogeneration 92, Madrid (28-30 October
absorption chiller. The principal features are summarised in 1992)
Table 2. 11 Hufford P E Absorption chillers maximise cogeneration value
ASHRAE Trans. NY-91-2-3 428-433 (1991)
Table 2 Features of &OElig;P absorption chillers 12 Tozer R and James R A review of absorption refrigeration applications
Proc. GIBSE Nat. Conf., Brighton vol 1, pp 155-160 (1994)
13 Tozer R M and James R W Thermodynamics of absorption refrigera-
tion (ideal cycles) Proc. ASME Int. Absorption Heat Pump Conference 94,
Louisiana, New Orleans (January 1994)
14 Felli M Absorption refrigeration thermodynamics ASHRAE Trans.
IA 89189-204 No 2748 (1983)
15 Wilkinson W H What are the performance limits for double-effect
ASHRAE Trans. part 2 NT 87-29-3 2429-2441 (1987)
absorption cycles
16 Kumar P and Devotta S Study of an absorption refrigeration system
for simultaneous cooling and heating ASHRAE Trans. 96(2) 291-298
No. 3415 (1990)
17 Gommed K and Grossman G Performance analysis of staged absorp-
tion heat pumps, water LiBr systems ASHRAE Trans. 96(1) 1590-1597
Paper No. AT-90-30-6 (1990)
If the initial cost is the highest priority, the single stage 18 Arh S and Gaspersic B Development and comparison of different
option is the most adequate, as long as enough heat energy is advanced absorption cycles Int. J. Refrig. 13(1) 41-50 (1990)
available. The decision to use pressurised hot water
(HW> 100°C) or not is also related to the CHP jacket condi- Appendix 1: Thennodynamics of absorption refrigeration
tions.
If a higher coP is required or if a limited amount of heat ener- To analyse absorption cycles, it is necessary to review driving
gy is available in terms of the cooling load, double stage units cycles in conjunction with cooling cycles and therefore a
will be required. The option of steam or hot gas fired will summary of these cycles is given as follows.<12>
depend on whether a steam installation is required for other
purposes and the difference of steam plant costs when com- AI.l Driving cycles
pared with the incremental price of a hot gas fired absorption The ideal driving cycle is the Carnot cycle which consists of
chiller. two isothermal and two isentropic transformations. Heat is
consumed at a high temperature, part of this heat is released
6 Conclusions at a lower temperature and net work is obtained. For a gas the
following reversible processes take place: an isothermal
Following the critical review relating to CHP systems and expansion, an adiabatic expansion, an isothermal compres-
absorption chillers, information has been correlated in a use- sion and an adiabatic compression.
ful manner. This covers single and double stage chillers with
system features such as hot water, steam and combustion A1.2 Coolingcycles (mechanical compression
products heat recovery. The combined CHP and absorption This is also known as the reverse Carnot cycle, the cycle is
plant is shown to have a number of advantages, the optimisa- anticlockwise on the T-S diagram and requires net work to
tion of which depends on requirements; single stage if the
transport heat from a low temperature source to a high tem-
main design criteria is initial cost and double stage if higher
perature sink. The reversible processes that take place in the
absorption cooling efliciencies are a requirement. reverse Carnot cycle for vapour are: an isentropic compres-
sion (compressor), an isothermal heat rejection (condenser),
an isentropic expansion (expansion engine) and an isothermal
heat addition (evaporator).
References
A1.3 Absorption iycles
1 Higham D W The absorption systems of Eugene Dominique Nicolle
(1823 -1909) innovator and engineer extraordinary Proc. Inst. Reftig. 77 The ideal absorption cycle is a combination of a Carnot dri-
40-47(1980-81) ving cycle and a reverse Carnot cooling cycle. As multi-stage
2 Perez Blanco H and Radermacher R Absorption: an updateASHRAE
absorption cycles based on these principles have not been
J. 28(11) 25-26 (November 1986) widespread, a brief summary of work by Eber<5) and Tozer
3 Fallek M Absorption chillers for cogeneration applications ASHRAE
and James<6>13> is presented. Work by Felli(14), Wilkinson~),
92(1B) 141-148 (1986)
Trans.
4 Tozer R M and James R W Absorption refrigeration, large scale direct fired
Kumar and Devota(16) and Gommed and Grossman(17) is also
chillers Technical memorandum 132 (London: South Bank University available on absorption thermodynamics.
Institute of Environmental Engineering) (Jan 1992)
5 Eber N Recent developments in the thermodynamics of absorption AI.4 Single stage thernwdynarrtic analysis
refrigeration Sartryek ur Kylteknisk Tidskrift 2 (Stockholm) (April 1969) The schematic of the unit can be seen in Figure 9. The refrig-
6 Tozer R M and James R W Thermodynamics of absorption refrigera-
tion Technical memorandum 137 (London: South Bank University erant is water and the solute is LiBr and other systems utilise
Institute of Environmental Engineering) (Aug 1992) NH3 as a refrigerant dissolved in water. From Figure 1 it can
7 Ziegler F and Alefeld G Coefficient of performance of multistage be seen that the generator, absorber and heat
exchanger are
absorption cycles Int. J.Refrig. 10(5) 285-296 (1987) the components that carry out the function of a compressor.

185
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
Figure 9 Heat dissipation ratio
versus coefiicient of performance

The pressures ot the dnving and cooling cycle depend on the For the generator and absorber processes 1-2 and 7-8 respec-
binary mixture,i.e. 10 and 0.6 kPa (absolute pressure) for tively the differences of entropy 2*-2 and 7*-7 are propor-
LiBr/lI,O systems and 1600 and 450 kPa respectively for tional to the heat of solution Ah..
HzO/NH3 systems at standard AM conditions. The work of Eber<5) had initially considered the absorption
In order to absorption cycle to two Carnot
correlate the cycle to be two separate cycles that were coupled mechanical-
cycles, a driving cycle and a cooling cycle with an ideal refrig- ly :
erantlsolution is considered. Details of the restraints of the The driving cycle 1-2-3-4-1
refrigerant/solution for it to comply with the requirements of
-

(Carnot cycle)
an ideal cycle are available (5,6,13), The refrigerant/solution can The cooling cycle 5-6-7-8-5
-

(reverse Carnot cycle)


be split into two parts. One of these is the refrigerant that
crosses all the process stages: generator, condenser, absorber
The work balance condition requires the driving cycle work
and evaporator, and is the most important part and therefore Fdc to equal the cooling cycle work F :
the only part considered. The other part consists of solution - - , - -,

that circulates between the generator and absorber. This part


is of minor thermodynamic importance and is a liquid that
only undergoes temperature and pressure changes. Under the
theoretical restraints, complete reversibility and infinitely
large heat exchangers, the heat balance of the cycle will not be
influenced by the circulation of solution. Therefore the solu-
tion was not considered further, except for its influence on
the main refrigerant flow. The entropy differences of the driving and cooling cycles are
defined as:
The processes are as follows. - - -.- --~- - ..

8-1:Isentropic heating of refrigerant in the solution


1-2: Heat introduced into the generator:
Heat of
If equations 22 and 23 are substituted into 24 and 25:
evaporation:

The driving and cooling cycle work is given by:


plus heat of solution:
- -

.... 6-- 6

2-3:Isentropic cooling (constant p) down to saturation tem-


perature T of the generator superheated vapour These are equal:
3-4: Condensation


4-5:Isentropic cooling of refrigerant Substituting equations 24 and 25 into 29 gives:
5-6: Evaporation
6-7: Isentropic heating of saturated vapour From this equation the coefficient of performance is derived
as:
7-8 Absorption by the solution of the superheated vapour (of
state 7). Both the heat of solution Ni, and the heat of
evaporation h~ are liberated: This equation that expresses the cop as the product of the
Carnot reverse cooling cycle cop and Carnot driving cycle
efficiency can be found in various published anicles(14,15). If
the temperature equation 26 is substituted into the cop equa-

186
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
tion 31 the following simplified formula is derived in terms of The heat balance of the mechanical compressor cycle indi-
the absolute evaporator and absorber temperatures: cates

..,

The thermodynamic ratio is the ratio of latent heat capacity The compressor energy is:
with respect to the sum of latent and solution heats and is also - _ , ~ -,

equal to the ratio of the absolute temperatures involved in the


driving and cooling cycles.
and, substituting in equation 43 a formula identical to equa-
tion 42 is obtained.
The cop in terms of the thermodynamic ratio a is:
Mechanical compressor cycle:

A1.5 Double and multi-stage From this simple relation it can be seen that high cops have
Multistage absorption cycles are combinations of single stage the benefit of lower heat dissipation ratios, therefore of less
cycles where the initial driving cycle produces a low grade cooling water requirement. This is an additional advantage
heat which is used to power the subsequent stag66,13). For for the double stage unit with respect to the single stage
units available on the market the low grade heat is obtained absorption cycle. This in turn, means smaller condenser
from the condenser but there is also a potential to use heat water pumps, domestic water pumps, condenser water
from the absorber. See references by Ziegler and Alefe1d(7), pipework and cooling towers together with less water loss due
to drift and evaporation and therefore lower chemical require-
Alefeld(8)., and Arh and Gasperic(18).
ments. Additionally, there will be the benefit of smaller oper-
A double stage absorption cycle consists of two single stage ating costs apart from those due to higher cops.
cycles. The cooling cycles of both of these are identical and in
real chillers share the same evaporator and absorber. The dri-
Appendix 3: COP - HDR - energy balance
ving cycle part is different and one cycle has higher tempera-
tures so that the residual condenser heat can be used to drive
the generator of the lower temperature cycle. The tempera- The cop can be derived in terms of the cooling duty and ener-
ture difference between the high temperature condenser and gy consumption data, i.e. evaporator and generator heat. In
low temperature generator is negligible for ideal cycles. the case of a steam fired chiller the sensible cooling of con-
densate has to be taken into account.
Following the same procedure as in the previous section the
following cop formulae are derived(6,IS): rnn - fl /11 - !1 lr-. !1 ~,. A. B1 IAOt

Double stage: The cop can also be derived in terms of the HDR and the ratio
--- . , ,.,t, of pump to evaporator power derived from the chiller energy
balance:
Multi-stage:
--- -- .. -1 . -1 .. _ -.1 ,«,,

Appendix 2: Heat dissipation ratio


The heat dissipation ratio (HDR) is the ratio of heat dissipated
The HDR can be calculated from the chilled and condenser
from the condenser and absorber with respect to the evapora-
water temperatures and flow rates:
tor load, equation 37. This relation is necessary to analyse the
cooling water requirements for different types of absorption .r - - Go’&dquo;
,...I
. -

and mechanical compression (centrifugal/screw/reciprocat-


The data supplied by manufacturers can be tested with equa-
ing) chillers. tions 48 and 52 for coherence.
Absorption cycle:
A3.1 Example
The data of a 700 TR double-stage steam absorption chiller
Taking into account heat balance: are used as an example.

Data:

Therefore the absorption cycle HDR is defined as:

The mechanical compressor chiller is analysed similarly as


follows.

187
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015
Calculating using the above data Pressure differential of systems 100 kPa
Pump efficiency 0.78
Hot water temperature 90°C

The cop difference between 1.205 and 1.181 is only 2% and


can be accounted for by other heat losses not considered.

Appendix 4: Performance variation with cooling water flow


rates

Pressure differential of systems = 100 kPa


Pump efficiency = 0.78
Hot water temperature = 115°C Note$

Total cooling water pressure drop considers the tabulated variation of the
absorber and condenser pressure drop in terms of the flow rate plus a con-
stant pressure drop due to the system pipework and cooling tower.

The cooling tower fan is assumed to vary linearly between the two cooling
towers selected for both extremes tabulated

Appendix 5: CHP absorption chillers


Cooling capacity of absorption chiller = 1400 kW (400 TR)
Chilled water temperatures (return/flow) 12.8/6.7°C
=

Entering condenser water temperature 29.4°C


=

188
Downloaded from bse.sagepub.com at UNIV OF CINCINNATI on March 11, 2015

You might also like