Instrumentation Cable

Flame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 V
RE-2Y(St)YQY-fl TiMF (I3X)
Application
For transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙ
classified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mains
electricity supply.
Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.
Construction
Conductor.............. plain annealed copper, solid, size: 1.0 mm²
Insulation............... polyethylene PE
Colour code........... black / white / red;
with numbered tape under separator tape of the triple screen
Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drain
wire, 0.5 mm²
Wrapping................ at least 1 layer of plastic tape
Collective screen... 24 µm aluminium / PETP tape over tinned copper
drain wire, 0.5 mm²
Bedding.................. polyvinyl chloride PVC, black
Armour................... galvanized steel wire braid, opt. coverage 80% (min.) over a
stranded tinned copper drain wire with the same cross section as
the conductors
Outer sheath.......... polyvinyl chloride PVC, blue for
intrinsically safe systems
Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 RP
Technical Data Abbreviations
Flame retardancy: IEC 60332-1 Temperature range: RE- instrumentation cable
Flame propagation: IEC 60332-3 cat. A -40°C up to +70°C 2Y insulation of PE
(during operation) (St) collective screen
Outer sheath: - 5°C up to +50°C Y bedding & outer sheath
Amount of halogen acid gas: max. 17% of PVC
(during installation)
(IEC 60754-1) Q galv. steel wire braid
Limiting Oxygen Index (LOI): min. 30% Min. bending radius: -fl reduced flame
(IEC 60332-3 annex B) 8 x cable-Ø propagation
Temperature index (TI): min. 300°C TiMF triple screen
(ASTM-D-2863)
Sunlight resistance: (UL 1581 section 1200)
Oil resistance: (ICEA S-82-552)

Electrical data at 20°C


Character Unit Values
Conductor size nom. mm² 1.0
Conductor resistance max. Ω/km 18.4
Insulation resistance min. MΩ x km 5000
Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115
Capacitance unbalance at 1 kHz max. pF/250 m 250
L/R (ratio) max. µH/Ω 25
Test voltage Urms core : core V 1000
Urms core : screen V 1000
Rated voltage U0 / U V 300/500

RH/I3X/29.05.01 Page 5
© KERPENWERK GmbH & Co. 2001
Instrumentation Cable
Flame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 V
RE-2Y(St)YQY-fl TiMF (I3X)

Geometrical data
No. of RT of RT of Dia. over Dia. of RT of Overall Weight Item No.
triples insulation bedding bedding armour outer Diameter
wire sheath
nom. nom. approx. nom. nom. approx. approx.
(mm) (mm) (mm) (mm) (mm) (mm) (kg/km)
1.0 mm²
2 0.6 1.2 13.3 0.3 1.5 17.6 12
5 0.6 1.2 16.8 0.3 1.6 21.3 13

RT = radial thickness

RH/I3X/29.05.01 Page 6
© KERPENWERK GmbH & Co. 2001