Professional Documents
Culture Documents
Proceedings of the 1st International Conference of P42-1 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
substation, horizontally open isolating switch are mostly type. The lightning arresters are mounted on steel
used. structures and fitted with a pressure relief device. Surge
counters are supplied.
(5) Lightning arresters: These are for protecting the main 1.6. Conductors
electrical equipment against possible danger due to
sudden surges and lightning discharges. The lightning
arresters are preferably be of the gapless metal oxide
Proceedings of the 1st International Conference of P42-2 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
The same type of conductor is used for the overhead probably never exceeds 500,000V. Studies reveal that
earth wires, the cross-section being at least the equivalent about 80% of lightning overvoltages are caused by
of 95mm2 copper. induced overvoltages on distribution lines.
The metal parts are designed to transmit the mechanical For the protection of electrical installations against
stresses to the porcelain by compression and to develop damage caused by overvoltage surges, lightning arresters
maximum and uniform mechanical strength of the or surge arresters are used.
insulator. Surge arresters are the basic protective devices against
system transient overvoltage that may cause flashovers
1.8 Circuit Breakers and serious damages to equipments. They establish a
baseline of transient overvoltage above which the
Circuit breaker is a device for automatically making arrester will operate to protect the equipment. When
breaking the normal current in a circuit or the current transient overvoltages appear at on arrester location, the
which may flow under fault conditions such as short arrester conduct internally and discharge the surge
circuit. In Aung Pin Lae substation, oil circuit breakers energy to ground. Once the overvoltage is reduced
(OCB) and gas circuit breakers (GCB) are used. 2500A, sufficiently, the arrester seals off, or stops conducting,
40KA,ASEA circuit breakers and 1250A, 25KA,SF6 the flow of power follow current through itself and the
circuit breaker in 132KV side and 2500A, 40KA, HLR- circuit is returned to normal. As voltage sensitive devices,
145/250/E1 circuit breakers are used in 33KV and 11KV arresters have to be carefully selected to correlate
sides. properly with the system operating voltages.
Proceedings of the 1st International Conference of P42-3 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
may be used.
FeederProtec
Feede tion
2.7. Distribution Apparatus Protection r Trips CBs
1*2
6 1
Most of the equipment on distribution system is located
on poles or in enclosures, and each piece of equipment CBs 1 To 9
are
has its own overvoltage protection, generally provided 5
Automatic
2
capacitors.
To other
Section
2.8. Busbar Protection Feeder
The problem of busbar protection has been partly solved “Figure 2.2. Mesh Protection”
by dispensing with busbars and grouping the circuits in
ring form, or mesh connection. The circuit breakers are 2.9. Buchholz Protection
connected in the ring main, and it is necessary for two to
trip to disconnect any circuit automatically. Typical This is a special type of protective device, which may be
protection schemes as applied to electrical systems are fitted to transformers. A fault-throwing device can be
shown in the following figures. used when pilot cables are not available. When a
Buchholz relay is fitted, it can be arranged to operate
simultaneously the local circuit breaker (A) trip coil and
the release coil (B) of the fault throwing switch. The
latter is connected between any one phase of the feeder
and earth. This affords a second earth at full phase
voltage and produces adequate fault current to operate
the remote protective devices fitted to circuit breaker (B)
should the lack of fault current be due to a high neutral
resistance, the fault-throwing switch should be connected
between any two phases of the feeder.
Proceedings of the 1st International Conference of P42-4 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
Equation (5)
= 3535 Amps
Proceedings of the 1st International Conference of P42-5 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
132 KV 33 KV 11 KV
The breaking capacity, MVA = 3 × I s × KV
Switching surge voltage 512.16 128.04 42.68
Equation (6)
(100%)
= 202.05 MVA
Power frequency over 312.84 78.21 26.07
voltage (75%)
Therefore 250 MVA, Minimum oil circuit breaker is
chosen.
Power frequency over 333.96 83.49 27.83
voltage (80%)
3.2. Minimum Insulation Level of Lightning
Arrester Power frequency over 303.6 75.9 25.3
voltage (100%)
If lightning causes any component of substation,
lightning surges, switching surges and power frequency
over voltage can occur. So the minimum level is needed
to calculate. Discharge factor of arrester is 2.4 to 3 and the average
value is 2.7.
Impulse surge = 1.15 (1.1EA + 40) KV
Equation (7)
3.3. Choice of Power Fuse For Transformer
Switching surge = 3.88E KV Equation (8)
132/33 KV, 15MVA transformer
Power frequency over voltage
High voltage side of transformer
= 2.37 EL(75%) Equation (9)
Rated current = 65.608 Amps
Power frequency over voltage
= 2.53EL(80%) Equation (10)
Maximum short circuit current on high voltage side
Power frequency over voltage
= 2.37 EL(100%) Equation (11) Transformer KVA × 100
=
% Impedance × 3 × KVH.Vside
Discharge voltage
Equation (13)
= discharge factor × rated voltage
Equation (12) = 937.257 Amps
“Table 3.1. Result Data for Insulation Level of Lightning The high voltage fuses is selected 120 Amp fuse for
Arrester” 937.257 Amp take pre arcing time of 0.09 sec.
Continue;
Proceedings of the 1st International Conference of P42-6 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
Proceedings of the 1st International Conference of P42-7 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008
Session 5
5. Reference
Proceedings of the 1st International Conference of P42-8 ©2008, the Institution of Engineering & Technology
the IET Brunei Darussalam Network, 26-27 May 2008