You are on page 1of 8

An Overview of the Distributed Generation

(DG) Connected to the GRID


Debabrata (Debu) Kundu, Senior Member, IEEE

* While working with Innisfil Hydro, there had been


Abstract-- The author worked on distributed generation (DG) involvement in connecting and approving two Wind
connected to the transmission and distribution GRIDS of Generation projects. A case study on one of the
Ontario Hydro, from 1985 to 1999. During that period, he has projects with a flow chart would be discussed in this
experienced lots of technical problems in connecting to the paper showing the methodology / procedures
GRID. In this paper, he would discuss his experiences with the
following topics: currently followed in approving DG connection to
-Types of DG's, including sources of prime power (e.g. water, the Hydro One T&D GRID.
gas, wind, solar, etc.) in brief * Conclusions
-Methodology of connection to the GRID minimizing the cost
impact to the customers II. TYPES OF GENERATION IN USE - GENERATORs/ROTATING
-System Groundings and transformer connections MACHINES
-Faults and their effects
-Protective relaying There are two types of rotating machines used as
-Control and metering generators, induction machines and synchronous machines.
-Harmonics and Resonance Smaller machines are often of the induction type, whereas
-Benefits of DG connecting to the GRID and operating in the larger installations usually use synchronous machines.
Micro-GRID format
The paper will be concluded with a case study of connecting a A. Direct Current Sources
DG to the GRID, and conclusions. Photovoltaic cells generate DC through direct conversion of
Index Terms - Connection to the GRID, Distributed solar energy to electric energy. Solar cells only work in the
Generation (DG), Faults and their Effects, Harmonics, Micro- sunlight and have maximum conversion efficiency when
GRID, Protective Relaying, Resonance, System Groundings, and
Transformer Connections. sunlight falls perpendicular to the cells surface and is not
obstructed by clouds or other objects. Some solar systems
I. INTRODUCTION
concentrate sunlight and track the sun's path to ensure
conversion efficiency is maximized throughout the day.
THIS paper contains experiences with DG connection to Fuel cells also generate DC and it produces energy from the
the GRID and it would include the highlights of the reaction of hydrogen or a hydrocarbon fuel in a cell
followings: containing electrodes and an electrolyte.
* Brief discussions of types of Generations in use in
the Province of Ontario connected to the Hydro B. Prime Movers
GRID
* Methodology of connection to the GRID and its Various types of turbines and engines are available
impact on system stability associated with various energy sources. These are described
* System groundings and transformer connections here very briefly.
* Faults and their effects
* Requirements of protective relaying to avoid DG C. Hydraulic Turbines
islanding
* Harmonics and resonance Hydraulic turbines are either horizontal or vertical types.
* Benefits of connecting DG to the T&D GRID and Vertical turbines are normally associated with larger power
operating in the Micro GRID format units operating at higher heads (water drops). Except for
larger units, most DG installations involve horizontal units
since they are generally lower in cost due to the smaller
The author retired form Ontario Hydro/ now Hydro One in the amount of civil works typically required.
year 2000; since then, he has been working as a Consultant to
a number of Utilities and most recently with Innisfil Hydro D. Steam Turbines
Distribution Systems. (e-mail: debu kunduIhotrnai1 om)
Thermal units, except gas turbines (combustion turbines
978-1-4244-1762-9/08/$25.00 C2008 IEEE units), use steam as their working fluid operating in a close
loop system. Steam is produced in a boiler fired by some sort

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
of fuel, such as coal, oil, natural gas and methane gas from stal n sorvMi

garbage dump and sewage treatment plants.


E. Turbo Expanders

Turbo expanders can be used in place of pressure regulators


whenever it is necessary to drop the pressure of a gas stream.
A typical, installation would be where natural gas is taken
from a transmission pipeline for distribution within town or to
a large industrial complex. ad ty Fare
systm y W

F. Gas Turbines (Combustion Turbine Units)

There are two types of turbines. The first is the aero-


derivative wherein the compressor stage and the output
turbine stage are decoupled. Typically, they can be brought to
full load from a cold start in about 1 minute and they are
therefore often used for standby purpose.
* It separates the generator from the grounding system
G. Wind Turbines on the utility. Generators are normally ungrounded or
Wind turbines for electrical generation are either of grounded through an impedance to limit fault values
horizontal axis or vertical axis design. Modern wind turbine and harmonic currents whereas utility distribution
capacities could run up to 1.5 to 2.0 MW and they are systems are normally multi-grounded to serve single-
equipped with synchronous generator. The variations in wind phase load.
velocity are accommodated through control of blade pitch, * The power transformer provides power to station
thus allowing speed control for synchronizing. Power auxiliaries when the generator is off-line.
generated by wind turbines corresponds to the instantaneous Igt provides a measure of protection to the generator
wind speed, and cannot therefore be controlled. from incoming surges originating from the utility
system.
H. Diesel engines The voltage variations in North America are maintained
between ± 600.
Diesel engines, although of vastly different design, can be The type of transformer used for connecting a generator to
used instead of gas turbines in many applications. They are a utility system is very important. Normally, the transformer is
normally fueled with oil distillates. typically connected in a A-configuration on the generator side.
On the utility system side, the transformer is almost always Y-
III. METHODOLOGY OF CONNECTION TO THE GRID AND ITS connected, and normally grounded and this connection
IMPACT ON SYSTEM STABILITY primarily dependent upon the utility and not the DG. Usually
on-load tap changers are not required for transformers
Fig. 1. is a schematic representation of the elements of a connected to generators since the same function can be
typical utility connection. Normally, provision will me made achieved much more economically through the generator
to completely isolate all parts of the DG installation form the excitation control system. Off-load taps covering a ± 5%
utility system under any operating or fault condition. This range are usually adequate for the purposes of voltage
dictates that the installation connected to the utility system matching.
through a switching device (a fuse or circuit breaker (CB))
capable of interrupting only load currents. For example, a load B. Line Connection to the Utility
break switch (LBS) may suffice if the end of the utility-owned
connecting line remote from the DG connects into the rest of The DG developer will often be responsible for
the utility system via a CB and the line serves no intermediate constructing a connecting line from the DG location to the
loads. The remaining of the equipment shown above in Fig. 1 designated connection point into the utility system.
is part of the DG facility and will depend on the specific
characteristics of each installation. C. Protection, Metering, Control and Synchronizing Systems

A properly designed protection system must be installed on


the DG generator, transformer and connection line to ensure
that if there is a fault within the DG facility, it will be
disconnected form the utility system. Such a protection
scheme must be defined at least in general terms by the utility
to ensure compatibility of the DG with the utility system.

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
been proven by studies performed in the reference paper [2]
D. Internal DG Faults [1] written by the author.

Protection must be provided to isolate the DG when fault IV. SYSTEM GROUNDINGS AND TRANSFORMER CONNECTIONS
occur within the DG installation. This protection usually takes [2], [3]
the form of differential protection covering the generator and
sometimes the transformer. This protection is backed up by The need for system grounding, characteristics of various
some form of over current relaying. Further internal types of transformer connections, their effects on the flow of zero
relaying can include generator loss of field relays, over/ under sequence currents, and the methods of system grounding for
(O/U) voltage relays, over/ under(O/U) frequency relays, over DG installations are discussed in this section.
temperature relays for transformer and generator, transformer Grounding a power system is achieved intentionally and
gas protection and ground fault protection. permanently connecting its neutral system to the ground at
one or more points. The connection of the neutral to ground
E. External Faults [1] may be made either through a solid connection or through a
known value of low impedance. The reasons for grounding
To eliminate the fault in feed from the generator, the DG are as follows:
installation must also be isolated in the event of certain faults * Improved personnel and equipment safety
or abnormal conditions on the utility system. In general, the * Protection against temporary over voltages
protection outlined in the above section will protect the * Improved service reliability due to improved ground
system against most infeeds. Additional protection schemes, fault detection
such as like pilot wire scheme for transfer tripping should be * Reduced cost of connecting single-phase loads
considered for larger DG. In some industrial application, to detect grounding for
motors etc, the system is installed ungrounded. But it is better
F. Metering Systems to ground the system at least using impedance to improve the
system reliability.
All DG will be paid for power production, revenue The design of the transformer connecting the DG
metering will have to be installed to meter energy delivered to installation to the utility is closely related to the grounding
the utility system. Some form of reactive power monitoring requirements in both the DG plant and the utility. Different
may also be needed. As the DG will require power for start- transformer core and winding configurations will have
up, a separate set of revenue metering will be required for different effects on the flow of zero sequence currents and
metering the power consumed by the DG. hence the operation of the two grounding systems.
G. Synchronizing Systems A. System Grounding Characteristics
A method of synchronizing the DG to the utility will be Utility grounding standards are well established, i.e. neutral
required in all cases. The synchronizing system for system is a multi-grounded system. DG grounding is normally
synchronous generators will normally consist of a connected through impedance.
synchroscope and two voltmeters. The system will allow
frequency matching prior to closing the CB to the utility B. Temporary Over voltages (TOV)
system. For using induction generators, all that is needed to
synchronize is to properly match the speeds of the generator System grounding reduces the impact of transient over-
and the system and then close the CB. voltages generated by various sources including
* Line-to-ground (L-G) faults
H. DG Isolation at the Point of Connection * Resonance
* Contact of line conductor with higher voltage system
In addition to the fault interruption device, an additional
During a L-G fault on one of the phases of three-phase (3-
device is usually required to isolate the entire DG, including P) system, the voltage w.r.t. ground of the two healthy phases
transformer from the system for "Work Protection". increases to as much as the full phase-to-phase(P-P) voltage.
On an ungrounded system the over voltage will be the full
I. Synchronous Stability 173% of the normal value. On a grounded system, however,
the over voltage is reduced since the neutral is held at a near
When power is transmitted over a line, a phase shift occurs ground potential. The over voltages in ungrounded systems
between the voltages at the receiving end and sending end. may build up to many times the nominal voltages during
The total allowable phase shift over the line is limited by the arcing line-to-ground faults.
requirements to maintain the generator synchronized to the
power system during system disturbances. Synchronous C. Ground Fault Detection
stability is usually not a problem with respect to small
generators connected to the infinite GRID system. This has Ground faults in a grounded system have relatively high
faults currents compared to the ungrounded system. This

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
allows rapid detection, isolation and repair. Grounding contribution from the generator will not be restricted by the
therefore results in generally shorter fault durations. generator grounding impedance. To limit the DG contribution
to fault current, the grounding impedance must be connected
D. Single-Phase (1-P) Loads to the neutral of the DG transformer primary.
The effectiveness of grounding for a DG installation is
The cost of serving 1-P loads on a utility distribution measured by its XO/X1 ratio, where XO and XI respectively
system is less if they are connected line-to-neutral instead of are the zero sequence and positive sequence reactance values
line-to-line (L-L). The savings results from the lower for DG installation at its point of connection to the
insulation costs for the transformers and the need for only one distribution feeder.
set of primary fusing disconnect and surge arrester equipment.
To achieve this advantage, the neutral system must be VI. FAULTS AND THEIR EFFECTS
grounded.
The system faults are of different kinds and they will be
V. SYSTEM GROUNDING METHODS discussed here briefly to provide some highlights to the
reader.
A. Solid Grounding
A. Three-Phase (L-L-L) Faults
A power system is considered solidly grounded, when the
neutral is solidly connected to ground without the introduction Only positive sequence currents flow during a 3-phase fault
of impedance. For solidly grounded distribution systems, the and their values are determined solely by the positive
ground fault currents are limited by the natural zero sequence sequence impedances of the circuit. The characteristics of a 3-
impedance of the system only, and are in the order of 60% to phase fault may be summarized as follows,
150% of the 3-P fault currents. The following aspects of a (a) The fault currents contain only positive sequence
solidly grounded DG should be carefully examined before it is currents, since the short circuit currents supplied
adopted. from both the DG source and utility are
* From the utility perspective, a solidly grounded DG balanced.
is may not be desirable since it will result in a (b) Connection of the DG installation to the
reduction of the fault current contribution from the distribution feeder will result in an increase in
utility system for L-G faults on the distribution the fault current magnitude on the utility system.
system. (c) For zero or low impedance faults on the main
* From DG's perspective, it should be ascertained that feeder trunk, connecting the DG installation will
the ground fault current contribution from the not cause a change in current contribution from
generator will not exceed its maximum design limits. the utility system.
(d) If induction generators are employed at the DG
B. Impedance Grounding installation, they will contribute currents into a
3-phase fault only during the sub transient stage.
By connecting the DG neutral to ground through an (e) If, as is generally the case, Z1 (+ve sequence
impedance, it is possible to obtain many of the advantages of impedance) is lower than the value of ZO (zero
grounded system while controlling the prospective line-to sequence impedance), the 3-phase fault
ground (L-G) faults current to lower and less damaging levels. condition results in the highest short circuit
The impedance used can be either resistive or a reactor. currents when compared to other types of faults.
Reactor grounding is generally preferred over resistive
grounding to avoid heat dissipation. It has the following B. Line-to Ground (L-G) faults
specific benefits to the utility:
* DG ground fault contribution to ground faults on the The following are the conclusions:
utility system can be limited so that it will not (a) During a L-G fault, the fault currents supplied
interfere with the utility operation. from the DG and the utility sources will be
* Impedance grounding results in lower transformer highly unbalanced and will potentially contain
in-rush currents. positive, negative and zero sequence
components.
C. Method of Connection (b) Connecting of the DG installation will result in
an increase in the maximum fault current
When the generator is connected to a A-transformer magnitude.
winding of a Y-Delta transformer, connecting the impedance (c) Because the value of zero sequence impedance
in the generator neutral will control the amount of zero- depends on system grounding arrangements,
sequence current through the generator only for those faults grounding resistances and transformer winding
that occur between the generator and the transformer. For configurations, it can vary over a much broader
ground faults on the distribution system, the fault current range than the positive and negative sequence
impedances. The short circuit currents during an

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
L-G fault can therefore also vary over a broad VII. PROTECTIVE RELAYING [1], [2]
range.
The function of protective relays at a DG installation is to
C. Line-to-Line (L-L) Faults detect system faults and malfunctions both within the DG
installation as well as on the distribution feeder. On the
The following are the conclusions: detection of fault, the relays trip the appropriate CB's to
(a) During an L-L fault, the fault current will isolate the faulty equipment in order to
contain positive sequence and negative sequence -minimize equipment damage and safety hazards during
components which are equal in magnitude. No electrical faults
zero sequence currents exist. -maintain power supply continuity on healthy parts of the
(b) Connecting a DG installation to the distribution system.
feeder will increase the maximum short circuit
current for a L-L fault. A. Protective Relays Characteristics
(c) For a zero or low impedance L-L fault on the
main feeder line, the fault current contribution The necessary characteristics for a protective relaying
from the utility source will not be reduced by system are:
connecting the DG facility. Reliability - the ability to always operate when a system fault
(d) For faults on the distribution feeder, the sub- occurs and to never operate under normal system conditions.
transient positive sequence impedance and the Selectivity - the ability to distinguish between faults within
negative sequence impedance are nearly equal the intended zone of protection from those outside the zone.
since the line and transformer impedances Speed - a measure of the time taken to detect a fault.
dominate the generator impedances. High speed detection and clearing of faults is desirable
because it
D. Line-to-Line-to-Ground (L-L-G) faults - limits damage caused by faults
- helps achieve better selectivity
The following are the conclusions: reduces likelihood of loss of generator synchronism
(a) The fault currents supplied from both the DG
B. Protective Zones
and the utility sources will be unbalanced and
will include positive, negative and zero sequence - In order for protective relays to provide the desired
components. degree of selectivity and sensitivity, the following
(b) Connecting the DG installation to a distribution two conditions should be met.
feeder will increase the maximum fault current - Zones of protection must overlap each other, leaving
level. no unprotected blind spots.
(c) If the value of zero sequence impedance for the - Zones of protection should be established to
DG installation is relatively low as compared to selectively de-energize only the facilities necessary
zero sequence impedance of the utility source, to remove the fault. Care should particularly be
connecting DG facility will reduce the zero exercised to preclude possible disconnection of
sequence current contribution from the utility facilities that may be of assistance in improving
substation while increasing the contribution from system stability during post fault conditions.
the generator.
(d) If the value of ZO is less than ZI, L-L-G fault C. Types ofRelays Used in DG Installations
condition will be the worst case fault condition
resulting in the highest values of short circuit Protective relays used in DG installations include:
(S/C) current. If the values of zero sequence - generator protection relays
current are very low, fault current values can be - transformer protection relays
up to 173% of those for 3-P faults. - switchgear protection relays
- feeder protection relays
E. Effect on System Voltages - auxiliary transformer protection relays
The relays commonly employed in DG installations
In the case of a L-L fault, the arc resistance, aside from its include:
effect on the fault currents, also affects the phase angle and - differential relays
magnitude of the system voltages as seen by the protective - over-current relays
relays at the DG installation. The arc resistance causes voltage - voltage restrained over-current relays
to be higher in magnitude than the reference voltage whereas - distance relays
two voltages would be equal if arc resistance were zero. If the - reverse power relays
voltage restrained overcurrent relays is employed, the relay - negative sequence relays
may operate incorrectly. However, this can avoid by changing - over/ under voltage relays
the voltage relay coils connection arrangement of the voltages. - over/ under frequency relays
- direct-current ground fault relays

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
- over temperature relays There are many benefits in connecting DG remotely to the
- gas pressure (Bucholz) relays utility feeder and some of the benefits are as follows:
-DG provides voltage support by providing reactive VAR
D. Generator Protection when DG is a synchronous generator. This VAR is
controllable by varying the generator excitation.
A generator may experience a number of abnormal -In case of emergency when there is failure of prime source of
conditions which might result in the generator being power, then the distribution feeder could be operated remotely
disconnected from the bus. Fault conditions which might also in the MICRO-GRID format.
have some direct electrical effect on the utility system include -In isolated locations, to supply power, MICRO-GRID format
the following: should be used. (See attached reference -5).
- stator winding faults -In remote locations, micro-grid concept will be more useful
- reverse power flow to supply power to the customers. To improve the reliability,
- unbalanced loading this grid eventually could then be connected to the more
- loss of excitation reliable T&D Grid.
- over-speeding
- loss of synchronism X. A CASE STUDY OF A DG TO BE CONNECTED TO THE HYDRO
ONE T&D GRID
E. Protection Against Islanding A. Background

Islanding may be described as the condition in which the Innisfil Hydro Distribution Systems (IHDS) is supplied at
utility feeder breaker has opened but the DG breaker is closed 44 kV from Hydro One Networks Inc. owned transformer
and the generator continues to supply power to the feeder station ( Alliston TS, 230-44 kV). IHDS supplies the Town of
while isolated from the utility source. Islanding can occur for Innisfil with a population of 25,000 people. In recent months,
a number of reasons. Islanding may cause the following: IHDS received two requests to connect 10 MW and 9.0 MW
- damage utility equipment Wind Power Generations respectively. The author reviewed
- create unsafe conditions for utility personnel and both projects and was involved in carrying out a detailed
public at large. report, which outlined requirements for Sky Power -Innisfil
Under no circumstances, this islanding will be allowed to Wind Farm to connect to the Hydro One owned GRID, was
persist in an operating system. To avoid this situation, submitted to Hydro One. The steps and the process followed
appropriate relays (e.g. O/U - frequency and O/U- voltage for this project are described in brief in this paper. Some
relays must be installed in addition to the other protective highlights are provided on the connection requirements by a
relays). hosting utility, such as IHDS to Hydro One owned GRID.

VIII. HARMONICS AND RESONANCE B. Step-I

Harmonics may originate in either the voltage or current The formal request came from the developer's and his
waveform but appear simultaneously in both due to Consultant with a "Pre-feasibility Study Reports" with all
interaction with system impedances. Solid state inverter used technical information about the Wind Generator and funds to
in the DG installation may give rise to some harmonics. be paid to Hydro One (HO) to cover their costs.
Therefore, care should be taken to remove these harmonics
from the system diligently. C. Step-2

IX. BENEFITS OF DG CONNECTING TO THE T&D GRID AND IHDS as the hosting utility accepted this request and
OPERATING IN THE MICRO-GRID FORMAT confirming to HO in writing that a request from the developer,
Sky Power has been received and please arrange to put this
The methodology of connecting DG to the Transmission project on the HO priority list. Then a number by the TS name
and Distribution (T & D) GRID has been discussed in section is assigned to the project. Following that IHDS's consultant
3 above. starts working on this project to perform the following:
MICRO-GRIDS comprise low voltage (LV) distribution -Review the pre-feasibility study report for the project
systems with distributed energy sources or Generator (DG) -Gather line data of the 44 kV sub-transmission feeders that
such as wind turbines, fuel cells, photovoltaic (PV) arrays, will connect the distributed generation (DG) as normal and
etc. together with storage devices (i.e. flywheels, energy alternate supplies and to prepare for the "Connection Impact
capacitors, and batteries) and controllable loads offering Assessment (CIA)" study.
considerable control capabilities over the network operation. -CIA studies were performed for various conditions using
These systems are interconnected to the medium voltage CYME International T&D Programs to capture all the
(MV) distribution network. From the customer point of view, scenarios that will arise when the DG will be connected to the
micro-grids provide both thermal and electricity needs and in system. Based on the study results, the recommendation were
addition enhance local reliability. made indicating the types of protection will be required to
protect the DG, e.g. transfer trip, etc.

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
XI. CONCLUSIONS
D. Step-3
Following are the conclusions:
Then the following forms were completed for the DG for -This paper provides a brief overview of the types of DG
HO: available and connected to the old Ontario Hydro and
-Formal agreement form between HO and the hosting utility presently HO Networks producing energy and delivering to
(IHDS) "For the Project to be studied" and to be signed by the the system.
CEO/President of the hosting Utility and a binding authority -It also provides a streamlined methodology of DG connection
of Hydro One. Along with this a cheque to cover the costs for to the GRID.
this study by HO was included. -Protection requirements of DG is a important factor. This
-DG Connection Review Form (Form A), Single Line paper provides a guideline of protection requirements needed
Diagram for the project, CIA Application Form for Sub- to protect the system from any unnecessary outages and
transmission System (form B) and the Generator data inconvenience to other customers.
complete with Generator Connection Assessment review -System groundings for DG is another important factor to
Form for 10 kW to 10 MW were prepared for submission. consider. TOV could be avoided saving the system from
-Then the complete package was submitted to HO for their outages.
review/study and approval. -While installing DG, strict guidelines for harmonics level as
-Upon receiving the approval from HO, the developer was stated in the IEEE Standard 1547-2003 are to be used.
informed to complete their final design for submission to the -There are benefits using DG in a MICRO GRID format at
hosting utility for approval to construct. remote locations to provide continuity of power supply.
-The construction starts and project goes to completion, -The case study as covered in this paper is a good practice by
inspection by IHDS and then in-service. This process takes Hydro One to stream line and unify the DG connection to
about 12 to 18 months from the formal request to the hosting T&D GRID to avoid any tripping and nuisance outages for the
utility. customers.

XII. ACKNOWLEDGEMENT

co-lu0pkie te pott of [W-F H9bIJIN Study The author is grateful to the following persons for their
Ir epor X I& pp Ex;
help and support in presenting this paper at New Delhi.
Miq.
-George Shaparew, President and Wade Morris, Director of
I _ Operations, Innisfil Hydro Dist. Systems for appreciation and
financial support.
-Joanne Bauerlein, Dist. Tech. Secretary of IHDS helping me
pmwsal aiA firosts 6 11ut dr jibintlM~IV:
0IN in organizing this document, formatting, etc.
Jims Barbara Cesarin, Admin. Secretary of IHDS helping me in
L hires a (ct Stsidrta pvrfbnn tlhe 16l1[ring!
*CA Slikd f the pqiut typing parts of this document, and formatting, etc.
C(oititant WinIptes thf CIA Awd& -Joe Bonadie, Ex.Ontario Hydro and presently with Power
Stream, and my past colleague in reviewing the manuscript
and providing valuable suggestions.
-Dr. Kankar Bhattacharya, Professor of Electrical & Computer
# CIA fo)r
Engineering, University of Waterloo in reviewing the
* i40uDil. ii&Ii131 A manuscript and providing valuable suggestions.

i
IXt cdimpkleti thc i'1la0it2g.
MANk1 [It egct fi:1h wiffi; OU the deWIAlSp
XIII. REFERENCES
Appleko kfm. [1] D. Kundu, "Technical Requirements to connect parallel generators to the
LD 1adsfJihei u11pkie pacige milh
di a ntartubalA ii a CK fb- d1) Ontario Hydro Distribution Electricity Systems", IEEE Trans. Energy
Conversion, vol.7, no. 1, Mar 1992.
[2] D. Kundu, E.G. Neudorf, Norm Perris, L. M. Szeto and D. V. Krause,
"Electrical Impact of a NUG under 5 MW rating when connected to a
- 1ttl W1Iw hitW tpp
p AXbl distribution feeder with various transformer connections", 94CH3425-6,
* l);\dujr ampkhe2te d8grhthw 1994 IEEE Industrial and Commercial Power Systems Technical Conf,
ajAi.rov1lf 1m I,I)c adprdkn Irvine, California.
lvfh the cofistruefi(l
[3] "Connecting Small generators to the utility distribution systems,
Prepared by Canadian Electrical Association, #123 D 767, June 1994.
[4] "Wind Integration Driving Technology, Policy, and Economics", IEEE
Power & Energy Magazine, vol. 5, no. 6, November/December 2007.
Fig. 2. Flow chart for the DG Application to Implementation. [5] "Unlocking the Potential The Power Microgrids", IEEE Power &
Energy Magazine, vol. 6, no. 3, May/June, 2008.
Note: LDC - Local Distribution Company [6] IEEE Standard for Interconnecting Distributed Resources with Electric
Power Systems, IEEE Std. 1547-2003.

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.
[7] IEEE Guide for Monitoring, Information Exchange, and Control of From 1968 to 1970, he worked with English Electric Company, Stafford,
Distributed Resources Interconnected with Electric Power Systems, England in System Studies. He worked with Totten Sims Hubicki &
IEEE Std. 1547.3-2007. Associates, Consulting Engineers, Cobourg, and Ontario from 1970 to 1974.
After working for a brief period with the Government of Ontario, he joined
XIV. BIOGRAPHY Ontario Hydro in 1975 as a Distribution Planning Engineer - Projects and
since 1978 to 1995; he has been working as Distribution Application
Engineer. Then in 1995, he went to the Regions to work as a Lines Engineer
Debabrata (Debu) Kundu (M '86 & SM '89) responsible for Dundas, Simcoe and Lincoln Areas. From 1997, he moved to
was born in India. He graduated from the Orangeville, and he was responsible for Guelph, Orangeville, Newmarket and
University of Jadavpur, Calcutta, India, in 1965 Alliston Areas. At that time he was involved in mitigating lighting outages on
with B.E.E. degree in Electrical Engineering and 44 kV circuits supplying Alliston Honda Plant. In 2000, he took the early
received the M. Sc. degree in Electrical Power retirement package after working for 26 yrs. with Ontario Hydro.
Systems Engineering from the University of He is the author and co-author of numerous IEEE, CEA and other technical
Manchester Institute of Science and Technology, papers on series capacitors, Non-utility Generation, Ferro-resonance and
UK, 1968. Surge Arresters application to mitigate lightning outages. He was also a
He worked with Beni Limited, Calcutta from member of various working groups with CEA and IEEE. He is a registered
1965 to 1966 in developing rotating machines. Professional Engineer in the Province of Ontario and a senior member of
IEEE.

Authorized licensed use limited to: The National Institute of Engineering. Downloaded on August 16,2010 at 12:03:50 UTC from IEEE Xplore. Restrictions apply.

You might also like