Professional Documents
Culture Documents
I. INTRODUCTION
.
1328 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
Fig. 4. Energization with flux increase after the transformer switching on.
Fig. 5. Excessive ultrasaturation after the transformer switching on. Fig. 6. Transformer energization with ultrasaturation (system scheme and con-
ditions as for Fig. 21): (a) HV terminal currents. (b) Second harmonic ratio.
.
WISZNIEWSKI et al.: ULTRASATURATION PHENOMENON IN POWER TRANSFORMERS 1329
where the amplitude and phase of the fundamental component III. NEW APPROACH TO THE ULTRASATURATION PROBLEM
of the flux are given by the formulae
Theoretical analyses of the possible transformer ultrasatura-
(2a) tion have been performed now for the system as shown in Fig. 8.
The most important differences with respect to the study pre-
sented in [3] are that the magnetizing current is negligible
compared with (i.e., , by with almost
(2b) infinite or at least much higher than the impedance ), and that
the secondary side reactance is considered.
the initial value of the component decaying with the time con- The extreme cases of inrush may be expected if the supplying
stant is equal to voltage is
(8)
(10)
.
1330 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
(16)
(17)
(18)
X = 1, X = 2, R = 0:1,
Fig. 9. Flux waveshape according to (11), for
or 0.5, R = 0:5 V=!Z
(flux values relative to ). Substituting (16) into (18) yields
(19)
The flux in the transformer core is then given as
The excessive ultrasaturation takes place if the flux ex-
(11a) ceeds the saturation level , that is, when
(20)
with
Substituting (19) into (20), one obtains the condition of ex-
cessive ultrasaturation
(11b) (21)
The flux increase consists of the ac component and There are two special cases which ought to be considered.
the dc component . The former is The first one, which represents the predominantly reactive load
of the transformer, is the following: , ,
(12) and . For these parameters, the condition of excessive
saturation becomes
while the dc flux increase becomes
(22)
(23)
(14)
Since the left-hand side of (22) is very small, in this case, the
Analysis of (13) indicates that the dc flux component in- excessive ultrasaturation is practically impossible.
creases with time only if
IV. SIMULATION STUDIES WITH EMTP–ATP
(15)
All the above considerations assumed that the magnetizing in-
The formula (15) presents the condition of ultrasaturation. ductance is much greater then the source inductance even
Only when it is satisfied, does the aperiodic flux component start if the magnetic core is fully saturated. However, this is seldom
to rise; otherwise, it decays, as presented in Fig. 9. the case, and often the magnetizing inductance of the saturated
WISZNIEWSKI et al.: ULTRASATURATION PHENOMENON IN POWER TRANSFORMERS 1331
Fig. 10. Flux and magnetizing current waveshapes for the condition of exces- Fig. 12. Flux and magnetizing current waveshapes for the condition of exces-
X = 4:3
X = 10
Fig. 13. Maximum and minimum values of the steady-state flux as a function
Fig. 11. Flux and magnetizing current waveshapes for the condition of exces-
X = 4:3
X = 10
X = ofX X = 4:3
X = 10
R = 0:01
R = 1
9 = 0:79
( , , , , ,
sive ultrasaturation met tangentially (
50
.
, ) and
andV=! = 1:09 ).
transformer is comparable with the source inductance. This ultrasaturation takes place, confirming the analysis presented
affects the inrush phenomenon and conditions of ultrasaturation. in Section III.
The simulation studies have been performed with the If reactances of the saturated transformer are lower, what
EMTP–ATP package, first for a single-phase transformer with is more realistic, the magnetizing current must not be neglected.
the system structure as shown in Fig. 8. The transformer and As a result, the magnetizing flux is not in the saturated region
system parameters were first chosen in such a way that the of the curve all of the time. Since the waveshapes of the
condition of excessive ultrasaturation was met just tangentially, magnetizing current show flat regions in every cycle (Fig. 12),
that is, for ( , , , it means that with the saturation reactance of the transformer
, , ). It has been verified how the decreasing, the probability of excessive ultrasaturation also
value of saturation reactance may influence the possibility decreases.
of excessive ultrasaturation occurrence. In Figs. 10–12, the However, even in cases of very small values of , the
obtained waveshapes of flux and magnetizing current are shown amount of the second harmonic in the magnetizing currents is
for three chosen values of the transformer saturation reactance very low (see Figs. 13 and 14).
(1000, 50, and 5 ), respectively. From Fig. 10, it can be seen Another set of simulations was performed for the conditions
that for a high saturation reactance value , leading to distinct excessive ultrasaturation (Figs. 15 and 16, pa-
the magnetizing current is very small; however, the excessive rameters under the figures). Under such conditions, the second
.
1332 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
Fig. 14. Maximum values of the magnetizing current and second harmonic Fig. 16. Maximum values of the magnetizing current and second harmonic
X X = 4:3
X = 10
R = 0:01
ratio as a function of X (X = 10
, X = 10
, R = 0:01
, R = 1
,
ratio as a function of ( , , ,
R = 1
9 = 0:79
, V=! = 1:09
, and ). 9 = 0:79 , V=! = 0:89 ).
Fig. 15. Maximum and minimum values of the steady-state flux as a function
ofX X = 10
X = 10
R = 0:01
R = 1
9 = 0:79
( , , , , ,
Fig. 17. Approximation error of minimum flux in relation to values obtained
X = 4:3
X = 10
R = 0:01
R = 1
andV=! = 0:89 ).
from simulation (
9 = 0:79 V=! = 1:09
, ).
, , , ,
harmonic ratio becomes negligible when the excessive ultrasat- This yields
uration takes place, which is the case for higher than some
25 (see Fig. 16).
By studying the plots presented in Figs. 13 and 15, one may
observe that a good correlation of analytical formulae and sim-
ulation results may be obtained, while calculating (19) in-
stead of and , one uses corrected values and (27)
(24)
A comparison of the minimum flux obtained from sim-
(25) ulation runs and calculated with the formula (27) is shown in
Figs. 17 and 18 for both cases presented in Figs. 13 and 15,
where respectively (i.e., with being equal to 4.3 and 10.0 ). The
values of corrective coefficient for both cases are given graph-
(26) ically in Fig. 19. One may observe that the flux approximation
quality is very good in the wide range of .
WISZNIEWSKI et al.: ULTRASATURATION PHENOMENON IN POWER TRANSFORMERS 1333
from simulation ( , , , ,
9 = 0:79 V=! = 0:89
, ).
Fig. 21. Flux waveshape and transformer input current (primary), for X =
0:5X , X = 0:5X , R = 0:1X , X = 2X , V = V , and 9 =
0:79 .
Fig. 19. Corrective coefficient k according to (26) for two chosen values of the
reactance X .
Fig. 22. Flux waveshape and transformer input current (primary), for X =
0:5X , X = 0:5X , R = 0:1X , X = 2X , V = 1:2V , 9 =
The approximation formulae for fluxes , , and 0:79 .
can be easily derived, analogously as for . Analyses
have indicated that the accuracy of such equations is similar to
(27). Several cases of transformer energization were simulated for
Further simulation studies have been performed for a three- various impedances and , residual fluxes , saturated
phase power transformer ( , , transformer reactances , and system voltages . An ex-
YNd11 connection, , , five-leg core) ample is presented in Fig. 21 and it is a case of excessive ul-
and two structures of the system, namely: trasaturation. One may note that in the time span between 0.05
1) basic structure, as given in Fig. 8 (supplying system, trans- and 0.3 s, the transformer inrush current (dashed curve) has a
former, load); very low second-harmonic component. Therefore, the differen-
2) alternative structure, as presented in Fig. 20 (supplying tial relay operation is not blocked by the second harmonic re-
system, transformer—unloaded or loaded, additional line, straint. The situation is even worse if, for some reason (e.g.,
or load from the supplying side). emergency excitation buildup in the generator during a fault),
The system shown in Fig. 20 is highly unfavorable, since par- the supplying voltage is higher than nominal. In such a case
ticularly in such a configuration, the ultrasaturation may appear, (Fig. 22, increased by 20%), the flux induced after trans-
during voltage jumps caused by disconnection of a nearby short former energization is much higher and the resulting inrush cur-
circuit. rent contains almost no second harmonic at all.
1334 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
V. CONCLUSION [6] Y. C. Kang et al., “Transformer protection relay based on the increment
of the flux linkages,” presented at the CIGRE Study Committee B5
Ultrasaturation poses a great problem for protective relaying Colloq., Calgary, AB, Canada, Sep. 2005, paper 108.
of power transformers. The work presented here concentrates [7] B. Kasztenny, E. Rosolowski, M. M. Saha, and B. Hillstrom, “A com-
parative analysis of protection principles for multi-criteria power trans-
on the phenomenon itself, trying to explain when excessive flux former relaying,” in Proc. 12th Power Systems Computation Conf.,
without zero crossing may appear. Knowing why and when the Dresden, Germany, Aug. 19–23, 1996, pp. 107–113.
ultrasaturation may occur, one may better understand the pos- [8] B. Kasztenny, E. Rosolowski, M. M. Saha, and B. Hillstrom, “A self-
organizing fuzzy logic based protective relay—An application to power
sible cases of the differential protection maloperation. The out- transformer protection,” IEEE Trans. Power Del., vol. 12, no. 3, pp.
comes of this paper may be also treated as hints for substation 1119–1127, Jul. 1997.
personnel, defining the system configurations, and parameters
Andrzej Wiszniewski received the Ph.D. and D.Sc.
that should be avoided in order to be on the safe side should un- degrees and the professorship in Electrical Engi-
favorable energization occur. neering from the Wroclaw University of Technology,
It is clear that the explanation of the ultrasaturation and ex- Wroclaw, Poland, in 1961, 1967, and 1972, respec-
tively. He has worked in the field of power apparatus
cessive ultrasaturation phenomena is only the first step toward and systems as a specialist in the protection and
developing new ideas and criteria for more reliable transformer control of power systems. He is an author of nine
protection that would better handle such unusual cases than cur- books and more than 130 scientific publications. He
was Rector of the university for two terms (from
rently employed relaying equipment. It seems that improvement 1990 to 1996). He was Minister for Science for four
of the protection operation would be possible with the intro- years, beginning in 1997.
duction of new, modified, or extended criteria. The protection Prof. Wiszniewski is a Distinguished Member of CIGRE and Honorary
Member of the Polish Institution of Electrical Engineers.
criteria should, on one hand, carry enough information on the
event to be distinguished and, on the other hand, ensure appro-
priate stabilization for other events for which protection opera-
tion is undesirable. Certain proposals of such new criteria can Waldemar Rebizant (M’00–SM’05) was born in
Wroclaw, Poland, in 1966. He received the M.Sc.,
be found in the literature, such as a complex second harmonic Ph.D., and D.Sc. degrees from the Wroclaw Univer-
restraint [5], flux restraint (estimated on basis of voltages) [6], sity of Technology (WUT), Wroclaw, in 1991, 1995,
or current waveshape analysis [7]; others still wait for their in- and 2004, respectively.
Since 1991, he has been a faculty member with the
ventors. It is believed that a lot of improvement can be reached Electrical Engineering Faculty at the WUT and is cur-
with the introduction of adaptivity in the differential protection, rently Assistant Professor and Vice Dean for Faculty
a simple example of which is to use adaptive thresholds as well Development and International Cooperation. His re-
search interests are digital signal processing and AI
as adaptive measurement procedures. It has also been proved techniques for power system protection purposes.
that considerable improvement of the operation and quite simple
achievement of adaptive features of protection functions may
be obtained with the use of various artificial-intelligence tech-
Daniel Bejmert was born in 1979 in Walbrzych,
niques. An example of using a fuzzy-logic technique for the re- Poland. He graduated from the Electrical En-
alization of fuzzy differential protection is given in [8]. There gineering Faculty of Wroclaw University of
is hope that an appropriate combination of classical and intelli- Technology, Wroclaw, Poland, in 2004, where he is
currently pursuing the Ph.D. degree at the Institute
gent techniques should bring additional benefits; therefore, fur- of Electrical Power Engineering.
ther investigations on the subject are desirable. His research interests include application of in-
telligent algorithms in digital protection and control
systems.
REFERENCES
[1] A. Wiszniewski, H. Ungrad, and W. Winkler, Protection Techniques in
Electrical Energy Systems. New York: Marcel Dekker, 1995.
[2] “Numerical Differential Protection Relay for Transformers, Genera-
tors, Motors and Mini Busbars,” SIEMENS AG, 2006, 7UT613/63x Ludwig Schiel was born in Weimar, Germany,
V.4.06 Instruction Manual, Order . C53000-G1176-C160-2. in 1957. He received the Dipl.-Ing. and Dr.-Ing.
[3] X. N. Lin and P. Liu, “The ultra-saturation phenomenon of loaded degrees from the Institute of Technology Zittau,
transformer energization and its impacts on differential protection,” Zittau, Germany, in 1984 and 1991, respectively.
IEEE Trans. Power Del., vol. 20, no. 2, pt. 2, pp. 1265–1272, Apr. 2005. In the 1991, he joined the Department of Power
[4] “EMTP-ATP Manuals,” EEUG, 2001. Transmission and Distribution, Energy Automation,
[5] B. Kasztenny and A. Kulidjian, “An improved transformer inrush re- Siemens AG, Berlin, Germany. He is Project Man-
straint algorithm increases security while maintaining fault response ager of transformer differential protection systems.
performance,” presented at the 53rd Annu. Conf. Protective Relay En-
gineers, College Station, TX, Apr. 11–13, 2000.