Auto Transformers

Ankit D Mahapatra

School of Electronics Engineering, KIIT University


Bhubaneswar - 751024, Odisha
India
Ankitmahapatra22@gmail.com
907021@kiit.ac.in

Abstract: This paper presents details about


autotransformer, its operation, limitations and
The winding has at least three taps where electrical
applications. connections are made. One end of the winding is

Keywords: Transformer,winding,power usually connected in common to both the voltage


applications,transmission,electrical isolation source and the electrical load. The other end of the

I. INTRODUCTION source and load are connected to taps along the


winding. Different taps on the winding correspond to
An autotransformer (sometimes called autoformer) is different voltages, measured from the common end.
an electrical transformer with only one winding. In a step-down transformer the source is usually
The auto- prefix refers to the single coil rather than connected across the entire winding while the load is
any automatic mechanism. In an autotransformer connected by a tap across only a portion of the
portions of the same winding act as both winding. In a step-up transformer, conversely, the
the primary and secondary winding. load is attached across the full winding while the
source is connected to a tap across a portion of the
winding.
II. OPERATION

As in an ordinary transformer, the ratio of secondary


to primary voltages is equal to the ratio of the number
of turns of the winding they connect to. For example,
connecting the load between the middle and bottom
of the autotransformer will halve the voltage.
Depending on the application, that portion of the
winding used solely in the higher-voltage (lower
current) portion may be wound with wire of a smaller
gauge, though the entire winding is directly
connected.

Fig 1.Single-phase tapped autotransformer with output voltage

range of 40%–115% of input


III. LIMITATIONS IV. APPLICATIONS

An autotransformer does not provide electrical Autotransformers are frequently used


isolation between its windings as an ordinary in power applications to interconnect systems
transfomer does. A failure of the insulation of the operating at different voltage classes, for example
windings of an autotransformer can result in full 138 kV to 66 kV for transmission. Another
input voltage applied to the output. This is an application is in industry to adapt machinery built
important safety consideration when deciding to use (for example) for 480 V supplies to operate on a 600
an autotransformer in a given application. V supply. They are also often used for providing
Furthermore, if the "neutral" side of the input is not at conversions between the two common domestic
ground voltage, the "neutral" side of the output will mains voltage bands in the world (100-130 and 200-
not be either. 250). The links between the UK 400 kV and 275 kV
'Super Grid' networks are normally three phase
Because it requires both fewer windings and a
autotransformers with taps at the common neutral
smaller core, an autotransformer for power
end.
applications is typically lighter and less costly than a
two-winding transformer, up to a voltage ratio of On long rural power distribution lines, special
about 3:1 - beyond that range a two-winding autotransformers with automatic tap-changing
transformer is usually more economical. equipment are inserted as voltage regulators, so that
customers at the far end of the line receive the same
In three phase power transmission applications,
average voltage as those closer to the source. The
autotransformers have the limitations of not
variable ratio of the autotransformer compensates for
suppressing harmonic currents and as acting as
the voltage drop along the line.
another source of ground fault currents. A large
three-phase autotransformer may have a "buried" In audio applications, tapped autotransformers are
delta winding, not connected to the outside of the used to adapt speakers to constant-voltage audio
tank, to absorb some harmonic currents. distribution systems, and for impedance
matching such as between a low-impedance
A special form of autotransformer called a "zig zag"
microphone and a high-impedance amplifier input.
is used to provide grounding (earthing) on three-
phase systems that otherwise have no connection to In UK railway applications, it is common to power
ground (earth). A zig-zag transformer provides a path the trains at 25 kV AC. To increase the distance
for current that is common to all three phases (so- between electricity supply Grid feeder points they
called "zero sequence" current). can be arranged to supply a 25-0-25 kV supply with
the third wire (opposite phase) out of reach of the
Like multiple-winding transformers,
train's overhead collector pantograph. The 0 V point
autotransformers operate on time-varying magnetic
of the supply is connected to the rail while one 25 kV
fields and so cannot be used directly on DC.
point is connected to the overhead contact wire. At
frequent (about 10 km) intervals, an autotransformer
links the contact wire to rail and to the second
(antiphase) supply conductor. This system increases
usable transmission distance, reduces induced
interference into external equipment and reduces
cost. A variant is occasionally seen where the supply
conductor is at a different voltage to the contact wire
with the autotransformer ratio modified to suit.

V. CONCLUSION

Operations, limitations and applications of


autotransformer has been presented in this paper.
Autotransformer has many limitations and
advantages over ordinary transformer. It is the
Perfect way to safely troubleshoot power supplies,
regulators, output sections, etc.

ACKNOWLEDGEMENT

The author is grateful to Mr. Debani Prasad Mishra,


Asst. Professor at the School of Electrical
Engineering, KIIT University, Bhubaneswar for
providing a free hand in choosing the topic for our
choice and allowing us to work as per our will for the
completion of this document.

REFERENCES

[1] Autotransformer – Wikipedia

http://en.wikipedia.org/wiki/Autotransformer