Range code Measurement Power supply 1st output (pulse)
Input Specifications
Accuracy (48 to 62 Hz) Un: 250V (AV5), 400V (AV7) Rated input
In: 5A Current 2 inputs (one/three-phase
Voltage/current balanced load)
(@ 25°C ± 5°C, R.H. ≤ 60%) ±0.5% f.s. (0 to 1.2 In, 6 inputs (one/three-phase
0.5 to 1.2 Un) unbalanced load)
Active power/energy Voltage 2 inputs (one/three-phase
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s. (PF ≥ 0.7 L/C, balanced load)
0 to 1.2 In, 0.5 to 1.2 Un) 4 inputs (one/three-phase
Reactive power/energy unbalanced load)
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s. (PF ≥ 0.7 L/C, Insulation among the voltage and the
0 to 1 In, 0 to 1 Un) current inputs: 2000Vrms;
Power factor (PF) among the current inputs:
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s., PF ≥ 0.7 L/C, 2000 Vrms
(0.6 to 1.2 In, 1 to 1.2 Un) Temperature drift ±250 ppm/°C
Additional errors Display Backlighted LCD, h 13mm,
Humidity < 0.3% f.s., 60% to 90% R.H. 3-dgt (instantaneous meas.)
Power supply ±0.5% rdg, -15 +10% p.s.
6-dgt (energies)
Magnetic field < 0.1% f.s. @ 400 A/m
Output Specifications
Pulse output (on request)
Static type From 0.1 to 999.9 pro- Data (bidirectional)
(according to DIN 43864) grammable pulses for kWh, Dynamic (reading only) System variables:
KVArh, open collector (NPN P, Q, PF, VL-L,
transistor) energies,
VON 1.2 VDC/ max. 100 mA Single phase variables:
VOFF 30 VDC max. PL1, QL1, PFL1, VL1-N, AL1,
Relay type 1 x SPDT PL2, QL2, PFL2, VL2-N, AL2,
AC 1 - 8A, 250VAC PL3, QL3, PFL3, VL3-N, AL3
DC 12 - 5A,24VDC Static (writing only) All programming data, reset
AC 15 - 2.5A, 250VAC of energy:
DC 13 - 2.5A, 24VDC - partial kWh
Pulse duration 200 ms (ON), ≥ 200 ms (OFF) - partial kVArh
Insulation By means of optocouplers, - total kWh
4000 Vrms output to - total kVArh
measuring input, Stored energy (EEPROM)
4000 Vrms output to ≤ 999999 kWh
supply input. ≤ 999999 kVArh
Serial output (on request) Data format 1-start bit, 8-data bit, no
Type RS422/RS485; parity/even parity, 1 stop bit
Multidrop bidirectional (static Baud-rate 1200, 2400, 4800 and 9600
and dynamic variables) selectable bauds
Connections 2 or 4 wires, max. distance Insulation By means of optocouplers,
1200m, termination directly 4000 Vrms output to
on the module measuring inputs
Adresses 1 to 255, selectable 4000 Vrms output to
by key-pad supply input
Protocol MODBUS/JBUS
Software Functions
Password Numeric code of max. 3 di- Example: the CT is a
gits; 2 protection levels of 100A/5A so the ratio is 20,
the programming data consequently the maximum
1st level Password “0”, no protection counted energy is 299980
2nd level Password from 1 to 255, all kWh or kVArh.
data are protected Single phase: Active power (kW),
Measurement scrolling reactive power (kVAr),
System: Active power (kW), power factor (cos ϕ),
reactive power (kVAr), current (A),
power factor (cos ϕ), phase-neutral voltage (V)
current (A), Transformer ratio For CT up to 5000 A
average phase-phase volt- Programmable ratio 0.1 to 999.9
age (V)
total and partial active ener- Digital Filter
gy (kWh), Filter operating range 0 to 100% of the
total and partial reactive input electrical scale
energy (kVArh) Filtering coefficient 1 to 64
Partial energy meters: Filter action On the display and on the
the counters of kWh and variable being transmitted
kVArh are automatically by the serial communication
reset when the energy port.
reaches the value
(14999*CT).
Supply Specifications
AC voltage 230 VAC (standard), 90 to 260VDC/AC
-15%+10% 50/60 Hz Power consumption ≤ 30VA / 12W (90 to 260V)
24 VAC, 48 VAC, 115 VAC ≤ 20VA / 12W (18 to 60V)
(on request),
-15%+10% 50/60 Hz
18 to 60VDC/AC
General Specifications
Operating temperature 0° to +50°C (32° to 122°F) Safety standards IEC 61010-1, EN 61010-1
(R.H. < 90% non-condensing) Other standards Pulse output: DIN43864
Storage temperature -10° to +60°C (14° to 140°F) Approvals UL (pending)
(R.H. < 90% non-condensing) CSA (pending)
Insulation reference voltage 300 Vrms to ground
Connector Screw-type,
Insulation 4000 Vrms between all inputs/ max. 2.5 mm2 wires x 2
outputs to ground
Housing
Dielectric strength 4000 Vrms for 1 minute Dimensions 96 x 96 x 140 mm
Noise rejection Material ABS,
CMRR 100 dB, 48 to 62 Hz self-extinguishing: UL 94 V-0
EMC EN 50 081-2, EN 50 082-2 Degree of protection Front: IP65
Weight Approx. 500 g
(packing included)
Mode of Operation
Accuracy class of the instrument as a relation of PI/Pn and cos ϕ (power factor)
2%
2%
1%
1%
5%
AV5 Un: 250 V Un: 430 V In: 5 A UI = 400 V (delta voltage) UI = 230 V
II = 265 A (single phase cur- II = 110 A (CT=300A)
rent)
Cos ϕ = 0.85 (system power Cos ϕ = 0.85 (sin ϕ = 0.52)
factor) (CT=300A) Un = 250 V
Un = 430 V In = 5 A
PI/QI (installation power) Pn /Qn (rated power of the In = 5 A
CT (ratio) = 300
One phase system: instrument): A
5 A = 60
PI = UI · II · cos ϕ One phase system: CT (ratio) = 300
5 = 60
QI = UI · II · sin ϕ Pn = Qn = Un · In · CT(ratio)
Qn = 3 · UI · II · sin ϕ
Three phase, 3-wire system: Three phase, 3-wire system: PI = √3 · UI · II · cos ϕ = 3 · 230 · 110 · 0.52
= √3 · 400 · 265 · 0.85 = 39.46 kvar
PI = √3 · UI · II · cos ϕ
Pn = Qn = √3 · Un · In · CT(ratio) = 155.87 kW
QI = √3 · UI · II · sin ϕ Qn = 3 · Un · In · CT (ratio)
Three phase, 4-wire system: Pn = √3 · Un · In · CT (ratio) = 3 · 250 · 5 · 60
Three phase, 4-wire system:
Pn = Qn = 3 · Un · In · CT(ratio) = √3 · 430 · 5 · 60 = 225 kvar
PI = 3 · UI · II · cos ϕ = 233.17 kW
QI = 3 · UI · II · sin ϕ where: PI 155.87 PI 39.46
Un = the rated input voltage = = 0.698 = = 0.175
where: Pn 223.17 Pn 225
of WM2-96.
UI = the real star voltage of
In = the rated input current of
the electrical system being WM2-96. In both examples the accura-
measured. CT (ratio) = the value of the
cy of the measurement is
I = the maximum phase cur- 1% f.s. when considering the
current transformer ratio.
rent of the electrical system changing of the measured
being measured. voltage from 0.9 Un to 1 Un
Cos ϕ = the average cos ϕ of and the measured current
the electrical system being from 0.1 In to 0.9 In with a
measured. cos ϕ of 0.85 (sin ϕ 0.52).
Wiring Diagrams
Single phase input connections
Fig. 1 Fig. 2
2. Display
Instantaneous measurements:
1 - 3-digit (maximum read-out 999)
Energies:
- 6-digit (maximum read-out 999999).
” ” and ” ”
- To scroll all the basic measurements (system variables)
- To increase or decrease programming values
V L1 - L2 - L3 V L1 V L2 V L3
(average)
L (V L1-N ) L (V L2-N ) L (V L3-N )
I L1 L2 L3 L I L1 L I L2 L I L3
kW L kW L kW L2 L kW L3
L1
L1 L2 L3
kWh kWh
total
L partial
kVARh L kVARh
total partial
Dimensions
Terminal boards
AR1034
RS485 output