Professional Documents
Culture Documents
ABSTRACT
In this paper, a steady state simulation model of an based on the physics of the process(analytical modeling).
actual vapor compression water-to-water heat pump Examples of experimental modeling is Kiatsiriroat et al.
unit using R-134a as a refrigerant is presented. The [1] who developed model equations from experimental
model is based on the performance characteristics of data for three main components of the vapor-compression
all components involved as well as thermodynamic refrigeration system, which were the compressor,
properties of R-134a and water. The simulation model condenser and evaporator. Modeling of each components
is able predict the system performance by supplying of the system is performed for the evaporator temperature
the water temperature and water mass flow rate range of -20°C to 10°C and the condensing temperature of
entering the evaporator, cooling water temperature 20°C to 60°C. The performance of the system, using R12
and cooling water mass flow rate entering the as refrigerant, was simulated at different refrigeration
condenser as inputs. To validate the simulation results, loads and operating conditions. The simulation results
a prototype water-to-water heat pump was deviated from the experimental results up to 9.8 %.
constructed for heating water from ambient Another experimental model was by C. Cecchini and D.
temperature 30 ˚C to temperatures greater than 80°C Marchal[2] who presented a simulation model of
using a recovery heat source of about 50˚ C. System refrigerating and air-conditioning equipment under steady
thermal performance was determined by measuring state condition based on experimental data. Their model is
refrigerant and water flow rates, temperatures and based on a mathematical model of the thermodynamic
pressures at numerous points in the system. cycle and on experimental data from equipment testing.
Performance data is presented for the overall heat The accuracy of the model is quite satisfactory, despite
pump system. The actual coefficient of performance of the use of many simplifying assumption.
heating, (COPh) for the system obtained was 4.9. Good From analytical point of view N.B.M. Stefanuk et al. [3]
agreement between model predictions and presented a steady-state model of a water-to-water, vapor-
experimental measurements has been found, despite compression-cycle heat pump operating under superheat
the use of many simplifying assumptions. Simulation control using R22 as refrigerant. Their model is derived
results obtained for characteristic performance entirely from the basic conservation laws of mass, energy,
parameters show an agreement with errors generally momentum, and equations of state as well as fundamental
less than 10%. correlations of heat transfer. Model predictions were
Keywords: Heat pump, R-134a, hot water heating. compared to experimental data. Good agreement was
found for the cases studied. Results indicate that the
superheat of the refrigerant leaving the evaporator and the
1. INTRODUCTION refrigerant charge can be used as control variables to
maximize system performance.
Heat pumps offer the most energy-efficient way to Much investigations were done on the performance of R-
provide heating and cooling in many applications, as they 134a heat pump were on low temperature operation.
can use renewable heat sources from the surroundings. There is no known work on water-to-water heat pumps
Even at temperatures we consider to be cold, air, ground for production of high temperature water until K.S. Ong
and water contain useful heat that's continuously et.al [4] conducted an experiment to investigate its
replenished by the sun. By applying a little more energy, a feasibility. Further experimental investigations were
heat pump can raise the temperature of this heat energy to conducted by Abdesselam et al. [5] on water-to-water
the level needed. Similarly, heat pumps can also use heat pump used to raise water form the ambient
waste heat sources, such as industrial processes, cooling temperature of 28°C to a temperature of 90°C, assisted by
equipment or ventilation air extracted from buildings. a simulated hot water source at 50°C. The actual
Heat pumps have enormous potential for saving energy, coefficient of performance of heating, COPh, for the
particularly in industrial processes. They are capable of system obtained was 4.9. The aim of this paper is to study
recovering low temperature waste heat, which would the performance of a high temperature water-to-water
otherwise be discharged to air or water, in an efficient heat pump.
way and rising it to high temperature heat energy that can
be utilized for various applications. There are two
approaches in heat pumps steady state modeling, the first
one is based on empirical data and the second one is
Industrial and Commercial Use of Energy Conference 2004
The refrigerant evaporates at a constant pressure; its From the first law of thermodynamics for a heat pump
temperature is constant only in the evaporating portion. system
Assuming that the refrigerant entering evaporator is Qc = Qe + Qw (12)
saturated mixture, the distribution of temperature will be
as shown in figure4.1. The temperature difference Thermodynamic properties for refrigerant-134a.
between the refrigerant and the cooling fluid is
represented by Logarithm Mean Temperature Difference, Correlations of saturated pressure, Psat in the function of
(TLMTD) e. saturated temperature, Tsat is expressed as following. The
pressure is in bar and the temperature is in Kelvin
Industrial and Commercial Use of Energy Conference 2004
−8 4
Psat = 6.22135417 × 10 Tsat − 6.53438906 × 10 Tsat
−5 3 For the superheated vapor enthalpy, hsh, the correlation in
(13) the function of superheated entropy ssh and the respective
2
+0.02747455Tsat − 5.3551506Tsat + 401.19683848 pressure, Psh is presented as follows:
2 2 2
Correlation of saturated vapor enthalpy, hsat_v in the hsh = 114.42062246 s sh Psh − 0.0777645 s sh Psh − 1978.24775 s sh
function of saturated temperature, Tsat is expressed as 2
+ 0.05509426 Psh − 399.85351241s sh Psh + 353.07425491Psh
( ) ( )
4
Tsat 3 Tsat
hsat _ v = −222.46230595 1 − − 4.00777424 1− + 7.29082819 × 10 s sh − 6.397156454 × 10
3 3
374.15 374.15
(20)
( ) ( )
2 1
Tsat 3 Tsat 3
− 211.99781373 1 − + 231.70083594 1 − The correlation for superheated temperature, Tsh in the
374.15 374.15 function of superheated enthalpy, hsh and the respective
+ 276.37114917 pressure, Psh is expressed as
(14)
Correlation of saturated liquid enthalpy, hsat_l in the Tsh = 0.9814 Psh + 0.8488hsh + 40.5262 (21)
function of saturated temperature, Tsat is expressed as
THERMODYNAMIC PROPERTIES FOR WATER
( ) ( )
4
( ) ( )
2 1
calculated by increase the T4 with 0.01°C every loop 4. EXPERIMENTAL EQUIPMENT AND
until the pressure ratio calculated was fall within a PROCEDURE
given range. This gave a new T4.
The experimental equipment is shown schematically in
4. With the new T4, refrigerant mass flowrate, mr and Fig. 1. It consisted mainly of a 3-phase x 1.7 kW
saturated liquid enthalpy of refrigerant at condenser compressor supplying R-134a refrigerant to a plate-type
outlet, h34 were calculated. By assuming the h34 heat exchanger as condenser and another plate-type heat
equals to the refrigerant enthalpy of expansion exchanger as evaporator. The condenser was cooled using
device inlet, h3, therefore the h4 can be found by a once-through flow of cold water at ambient temperature.
assuming h4 equals to h3. Heat to the evaporator was supplied by circulating hot
water from a hot water storage tank. The water in the tank
5. Simulate the evaporator. If the calculated heat was heated using 3 x 2.5 kW immersion heating elements.
transfer rate Qe by equation 15 is within a Temperature control in the tank was via a bimetallic
prespecified error tolerance of the calculated Qe by thermostat. The mean water temperature in the tank was
equation 17, go to step 6. Otherwise, update T12 by measured by two Cu-Con thermocouples inserted inside
increase 0.01°C and repeat step 5. the tank.
The refrigerant flow-metering device was a conventional
6. After the new T12 was obtained, some parameters thermostatic externally equalized expansion valve. Sight
can be calculated such as T1, T2, T23, h1, h2 and h23. glasses located in the liquid line allowed the state of the
refrigerant to be determined. Cu-Con thermocouples held
7. Simulated the condenser. If the calculated heat in close surface contact with and attached to the pipe
transfer rate Qc by equation 18 is within a walls were located at the various points shown in Fig. 1.
prespecified error tolerance of the calculated Qc by Electronic pressure transducers were employed to
equation 20, go to step 8. Otherwise, update T34 by measure the pressures at these points. Two Schlumberger
decrease 0.01°C and repeat step 7. coriolis-type flowmeter were employed; one connected to
the liquid line after the receiver measured liquid
8. At this point, all of the states in the heat pump cycle refrigerant flow rate to within 0.001 kg s-1 with an
are known and the thermodynamic energy balance is accuracy of within less than + 1% of the flow measured,
satisfied. However, the guess refrigerant specific the other flowmeter measured the water mass flow rates
volume at compressor suction, v1 may not within a to the evaporator. Condenser water mass flow rate was
prespecified error tolerance of the calculated value measured with a manually-read Rotameter. Power
of v1. If the v1 fall within the prespecified error consumption was measured with a Dranetz Power
tolerance, then the operating point has been found, Platform. Dynamic data logging was performed using a
so go to step 9. Otherwise, update the guess value of SR630 logger and LABVIEW. Real-time data and results
v1 and repeat step 3 to step 8. were displayed simultaneously on the PC monitor.
9. Finally, calculate the coefficient of performance In the experiment, water in the hot water storage tank was
(COP) of the heat pump. Output the results. first heated to about 55 oC. Condenser and evaporator
water flow rates were controlled at 0.040 and 0.35 kg s-1,
The following assumptions are made on the system respectively, using the hand valve. Condenser water inlet
throughout the simulation temperature was at 28 oC. The compressor was then
switched on. Data recorded in real-time and displayed on
1. No pressure drop across evaporator. the PC monitor screen after the system had reached the
steady state conditions.
2. No pressure and temperature from evaporator
outlet to compressor suction.
5. RESULTS
3. No pressure drop across condenser.
Four sets of experiments were conducted on the system,
4. No pressure and temperature drop from the namely Run 1, Run 2, Run 3 and Run 4. The objective in
compressor discharge to the condenser inlet. Run 1 is to investigate the performance of the heat pump
system under low evaporating temperature by maintaining
5. Isenthalpic expansion in expansion valve the temperature of the hot water storage tank at 35 °C.
The water storage tank temperature was increased and
6. No temperature and pressure drop from maintained at 55°C in Run 2 to investigate its’
condenser outlet to the inlet of the expansion performance at high evaporating temperature. At Run 3,
valve. the storage tank temperature was kept at 55°C at the
initial stage of the experiment. The speed of the pump
circulating hot water to evaporator was changed during
the experiment in order to investigate the effect of varying
hot water mass flow rate to the performance of the heat
Industrial and Commercial Use of Energy Conference 2004
pump system. Run 4 was carried out to study the effect of [2] C. Cecchini, D. Marchal, “A simulation model of
the cooling water to the performance of the heat pump refrigerating and air-conditioning equipment based on
system by varying the cooling water mass flow of the experimental data”, ASHRAE Transactions, Part 2,
condenser. 388 (1994)
Comparisons between predictions of the model and [3] N.B.M. Stefanuk, J.D. Aplevich, M. Renksizbulut, “
corresponding measurements on the experimental facility Modeling and simulation of a superheat-controlled
were made to determine the accuracy and limitations of water-to-water heat pump”, ASHRAE Transaction,
the steady-state model. It was found that the model is pp172-184 (1994).
generally accurate to within +5% of the experimental [4] K. S. Ong, Abdesselam H., C.Y. Chong,
measurements for all the temperatures as shown in Figure “Performance of an R-134a heat pump for production
2 and figure 3, for the suction and discharge temperature of high temperature water”, Journal-Institute of
respectively. The accuracy was considered to be Engineers, Malaysia. Vol.60, No.4, (1999).
satisfactory for this project. [5] Abdesselam H., Than Cheok Fah, K.S. Ong, “Further
Figure 4 shows the comparison of the calculated experimental results on a performance of an R-134a
coefficient of performance verses the measured one, with heat pump for production of high temperature water”,
the accuracy around +15%. This deviation is due to the Regional Conference on Higher Engineering
assumption mentioned above in the model. In which the Education, pp119-123 (2001)UM, Malaysia
overall heat transfer coefficient of condenser and
evaporator was assumed to be a constant. Although those
values are provided in the heat exchanger catalogues, the 8. AUTHORS
values are actually based on different conditions and
therefore can be changed with respect to condensing and Principal author: Abdesselam Hamlaoui is a lecturer of
evaporating temperatures. On the other hand, the Mechanical Engineering at the University of Malaya
difference between predicted and experimental (Malaysia). He earned Master of Engineering from the
condensing pressure falls within a band of + 10%. This is university of Constantine (Algeria) and a Master of
considered as an acceptable range of deviation. Engineering Science from the University of Malaya both
The reasons for the deviation between the experimental in mechanical engineering.
and simulated values are also due to the experimental Mr. Hamlaoui joined the university of Malaya in 1996.
uncertainties and in the calculated values of the His research interests include renewable energy
thermodynamic properties. This are added to the applications, refrigeration, thermal sciences, and energy
modeling equations which are only applied for steady conservation.
state flow processes. Mr. Hamlaoui is a registered Professional Engineer and is
a member of the American Society of Heating,
Refrigeration, and Air Conditioning Engineers
6. CONCLUSIONS (ASHRAE) and the Society of Automotive Engineering
International (SAE)
Hot water temperatures up to 90 oC was obtained from the E-mail: Hamlaoui@um.edu.my
present water to water heat pump equipment. Results
show that it is possible to operate the R-134a water-to- Co-authors: Than Cheok Fah, Associate Professor
water heat pump from a heated water source at about Mechanical Engineering at the University of Malaya
50oC to produce hot water at 90oC with a COPh of 4.9. (Malaysia) B.Eng.(Hons), M.Eng.Sc.(Mal)University of
Steady state model and simulation algorithm for a water- Malaya, Ph.D. (WPI)USA
to-water heat pump has been presented with the Expertise: Thermo-fluids, Fire safety, Risk assessment,
knowledge of the performance characteristics of all solar energy
components involved as well as thermodynamic Research: Development Of Solar Heater (Solar water
properties of R-134a and water. The simulation program heater, solar air heater and solar assisted heat pump, heat
could predict the system performance by supplying the pipes).A Fracture Behaviour of Window Glass Wide
hot water temperature entering evaporator, T7/K, hot Controlled Heating ondition. Development Of Oil Spill
water mass flow rate, mew/kgs-1, cooling water Contingency Management System for Strits Of Malacca.
temperature entering condenser, T5/K and cooling water E-mail: thancf@um.edu.my
mass flow rate, mcw/kgs-1. The results from the simulation Hazem Mohamed is a lecturer of Mechanical Engineering
studies are generally relevant. at the University of Malaya (Malaysia)
B.Sc. (Hons) Mechanical Engineering (Zagazig
University Egypt), M.Eng. Sc. Of Engineering ( Uni. Of
7. REFERENCES Malaya)
His research interests include Mechatronics - Control
[1] T.Kiasiriroat, K.Chouwcheun and P.Wibulswas, Engineering- Modeling
“Simulation of A Standard Vapor-Compression E-mail: hazem@um.edu.my
Refrigerant System”, ASEAN J.Sci. Technol.
Develop. 11(1) 1994. Presenter:
The paper is presented by Hazem Mohamed.
Industrial and Commercial Use of Energy Conference 2004
Compressor
Pump
Flow Meter
T5 T6
Evaporator
P3
Condenser
T2 Receiver Tank
T34 T23
P2
Hot Water Tank
TXV
Water Storage
T1
Charging Head
P1
H. Pressure
L. Pressure
T8 T7
Valve-Opened
Ttank
Valve-Closed
Check Valve
Fig.1. Schematic Diagram of the Water to Water Heat Pump System . Filter Drier
Rotameter
Industrial and Commercial Use of Energy Conference 2004
320
+ 3%
318 Unity
calculated suction temperature T1 (K)
316
314
312
310
308
306
304
302
300
300 302 304 306 308 310 312 314 316 318 320
measured suction temperature T1 (K)
380
Unity
375
calculated discharge temperature T2 (K)
370
365
360
355
- 5%
350
345
340
340 345 350 355 360 365 370 375 380
measured discharge temperature T2 (K)
5.8
Unity
5.6
5.4
calculated COP
5.2
4.8
4.6
4.4
4.2
4
4 4.2 4.4 4.6 4.8 5 5.2 5.4 5.6 5.8 6
measured COP