UPS A1 & A2

Quick Guide
User’s Manual
A1 & A2 QUICK GUIDE

1. Table 1 Safety Symbols and Means


Safety Symbols Means

Secure alarm

Risk of electric shock

2. Table 2 UPS Main Performance Index

Index Model A1 A2
Rating voltage (V) In range 160~290V full load
Characteristic

Rating frequency (Hz) 50±5%


Input mode Single-phase three-line
Input

Battery voltage (V) 36 72

Capacity (VA/W) 1000/700 2000/1400


Voltage (V) 230±2%
Frequency (Hz) 50±0.2% (Battery mode)
Output Characteristic

Waveform Sine wave


Voltage distortion
THD < 3% (Linear load)
factor
Power factor 0.7 (Lag)
Switching time (ms) 0
Overload capacity 105%~130% Load, lasting 60 seconds. 135%~150% Load, lasting 30 seconds.≥150%
lasting 300 milliseconds
Output mode Sockets
5 minutes 5 minutes
Spare time
(PC LOAD) (PC LOAD)
Charge recovery time <12 hours (Standard time delay model)
A1 & A2: RS232 & USB interface
Communication
RS232 interface supports UPS power management software UPSilon 2000 and SNMP
Other Characteristics

interface
adapter
Panel display LED displays operation status of UPS
Warning function Battery low voltage, abnormal power supply, UPS malfunction
Protection function Battery low voltage protection, overload protection, short-circuit protection and excess
temperature protection
Frequency noise (dB) < 45
Working temperature 0 ~ 40℃
Relative humidity 0 ~ 95%, No condensation
Size (mm)(H × W × D) 88×440×500
Weight (kg) 14 11

◆Specifications are subject to change without prior notice.

15]
Copyright AST 2010 www.ast-global.com
A1 & A2 QUICK GUIDE

3. Rear Panel

BREAKER RS232 PORT USB PORT FAN

FUSE USB
RS232

AC INPUT
A C O U T P U T

/DC INPUT

(REAR PANEL)
AC INPUT DC INPUT AC OUTPUT
TERMINAL SOCKET
A1 Rear Panel

BREAKER RS232 PORT USB PORTFAN FAN AC OUTPUT SOCKET

FUSE RS232 USB

AC INPUT
AC OUTPUT

(+) BATTERY (-)


DC INPUT

REAR PANEL
AC INPUT DC INPUT
TERMINAL A2 Rear Panel

15]
Copyright AST 2010 www.ast-global.com
A1 & A2 QUICK GUIDE

(REAR PANEL)
(REAR PANEL)

AC OUTPUT
AC OUTPUT

AC OUTPUT

AC OUTPUT
SOCKET SOCKET

FAN
FAN

(+) BATTERY (-)

USB PORT
DC INPUT
USB

USB PORT DC INPUT


USB

/DC INPUT

LINE BAR AC INPUT


RS232 PORT DC INPUT
RS232

RS232 PORT TERMINAL


RS232

AC INPUT

AC INPUT
AC INPUT

SOCKET BREAKER
FUSE
FUSE

BREAKER

Horizontal A1 Horizontal A2

4. Preparations before First Start-up

To ensure normal operation of UPS, please confirm the following before use:
A. Correct installation of input and output.
B. If supply terminals connect to the rated power. .
C. Confirm that UPS output does not short circuit, and the load capacity does not exceed UPS capacity.
D. Confirm if computer or other instrument is turned off.
E. Confirm if battery voltage is normal.
F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by
electric network directly.

15]
Copyright AST 2010 www.ast-global.com
A1 & A2 QUICK GUIDE

5. UPS Start-up Sequence

After confirming all the above, please start the machine by following means:

A. Press the "POWER" button on the UPS panel to start UPS, the "INV" indicator light will light up. After
retardation time, the "BYP." light goes out and the UPS is changed inversion power supply. By this time, the
start-up is completed and the equipment starts operation. Wait for about 20 seconds after normal no-load
operation to turn on the computer or other instrument. Start the load in the sequence of high-power to low
power, first start the high-power equipment then in turns start equipment with lower power.

B. Start computer or other equipment.

6. Daily Start-up and Shutdown

During daily operation, operate as per the following for start-up or shut down:
A. Press the "ON" button on the UPS panel to start UPS, after 20 seconds, turn on the computer or other
instrument.
B. Normally, only when the UPS has been started and is working stably, can the loading equipment
power switch be turned on. First turn on high-power equipment, then the equipment with lower power.
Some equipment has large start current (such as monitors of some brands). When starting such equipment,
overload protection (such as bypass operation) may occur. In this case, it's recommended to start this type
of equipment before other equipment.
C. Before shutdown, turn off the computer and other instrument first. Then press the "OFF" button on the
panel for
seconds.

7. Maintenance Guide

The correct maintenance, including the preventative maintenance and remedial maintenance, is the key to the

best operation and longer usage life of the UPS. The preventive maintenance includes some regular programs

to avoid the faults of the power system and reach maximum efficiency. The remedial maintenance includes the

probing of the power system fault for the effective maintenance.

8. Safety Precaution
For safe and smooth maintenance on the power system, you must follow the related safety precautions,
prepare the necessary gears and testing equipments and operate under the eligible maintainer’s control. Pay
attention to the following safety operation regulations:

A. Do remember there always exits hazardous voltage inside UPS even when UPS do not run.
B. Make sure persons manipulating or maintaining UPS are familiar with the manual and instrument.
C. When UPS operation, no golden or sliver accouterments like ring, watch wore.

15]
Copyright AST 2010 www.ast-global.com
A1 & A2 QUICK GUIDE

D. Do assume the safe operation procedure as a matter of course. If any doubt, consult with persons
being familiar with the instrument.
E. Keep eye on the hazardous voltage inside the UPS every moment. Using voltmeter to check if the input
power is completely cutoff and in safe status before maintenance and adjustability.
Please comply with the manual to use UPS. When UPS faults, please cut off the connection between battery
cabinet and UPS immediately then deliver it to professional maintainer or station. Self-deal is prohibited.

15]
Copyright AST 2010 www.ast-global.com