Sl.no Formula DESCRIPTION VALUE


Leaflet SFC (gms/bhp-hr) 147 147 147 153 147 147
conversion SFC (gms/kw-hr) 197.05 197.05 197.05 205.1 197.1 197.1
A 197.05 197.05 197.05 205.1 197.1 197.1
B Required Rating ALTERNATOR RATING (KVA) 180 200 250 320 380 500
C C = B x 0.8 ALTERNATOR RATING (KW) 144 160 200 256 304 400
D From leaflet EFFICIENCY(%) OF KEC ALT 92.6 92.6 92.6 92.9 92.9 94.8
E E=C/D I/P POWER REQUIRED in kW 155.51 172.79 215.98 275.57 327.23 421.94

F From ARAI form POWER(KW) OF ENGINE 187 187 236 300 339 454
G G = ( F / E ) x 100 ENGINE UTILISATION(%) 83.18 92.43 91.42 91.77 96.44 92.92

H Assumed DENSITY OF DEISEL 825 825 825 825 825 825


I I=A/H SFC AT FULL LOAD(ltrs/kw-hr) 0.24 0.24 0.24 0.25 0.24 0.24
J J=ExI FUEL CONSUMPTION per Hour 37.14 41.27 51.59 68.51 78.16 100.78
K K= C/ J Units Generated Per Liter 3.88 3.88 3.88 3.74 3.89 3.97
L L Per Liter Diesel 42 42 42 42 42 42
M M = L/K Per Unit in Rs 10.83 10.83 10.83 11.24 10.80 10.58

@ 75 % load 27.86 30.95 38.69 51.38 58.62 75.59

Note: The figures are as per the test conducted at STD NTP condition