You are on page 1of 4

900 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 12, NO.

1, MARCH 2002

Application Studies of Superconducting Fault Current


Limiters in Electric Power Systems
Lin Ye, LiangZhen Lin, and Klaus-Peter Juengst

Abstract—In power systems, superconducting fault current lim- in electric power systems is expected not only to suppress the
iters (SFCLs) can limit the prospective short-circuit currents to amplitudes of the short circuits but also to enhance the power
lower levels, so that the underrated switchgears can be operated system stability.
safely. This paper presents a detailed theoretical analysis of im-
proving power system stability by using of SFCLs. Electromag- In this paper, we mainly give a theoretical analysis of
netic Transient Program (EMTP) simulation results based on a improving power system transient stability by using an SFCL
model system also show that SFCLs are effective for enhancing the which is capable of consuming the excessive accelerating
transient stability of electric power systems by restraining the gen- generator power, increasing the stability-limit of the system
erator rotors from accelerating after faults and improving power and then enlarging the stability-region after the short circuit.
quality. This paper outlines the basic application guidelines for
using superconducting fault current limiters in different voltage- In addition, some application guidelines for using SFCLs in
level power systems. In order to insure the safe and proper usage power grids are also presented.
of SFCLs, some future considerations on the interaction between
SFCLs and power systems are presented as well. II. A BRIEF ANALYSIS OF THE SHORT CIRCUIT CURRENT
Index Terms—Power quality, SFCL, short circuit, supercon-
A brief review of short circuits is given prior to discussing
ducting fault current limiter, transient stability.
the application of superconducting fault current limiters. The
general formula of short circuit current [7] is described by (1)
I. INTRODUCTION

A S ELECTRIC power systems grow and become more


interconnected, at some points, the available fault currents
levels may exceed the maximum short-circuit ratings of the
(1)

switchgear. Traditionally, to alleviate the cost of switchgear and where is the peak value of the symmetrical current deter-
bus replacements, the most common ways to limit high-level mined by the magnitude of the system voltage and the equiv-
fault currents are: uprating of switchgear and other equipment, alent short-circuit impedance. is the peak value of the cur-
splitting the power grid and introducing higher voltage con- rent during normal operation. is the initial voltage angle.
nections (AC or DC), using current-limiting fuses or series is the impedance angle prior to the short circuit. is given by
reactors or high-impedance transformers, and using complex , where is the equivalent short circuit ratio.
strategies like sequential network tripping. Nevertheless, these From (1), the short circuit current is composed of the symmet-
alternatives may create other problems such as loss of power rical short circuit and the dc offset, in which the dc component
system safety and reliability, high cost and increasing power is exponentially decaying. The combination of these two cre-
losses [1]. ates an asymmetrical short circuit current which depends on the
In the past few years, many kinds of fault current limiting system ratio and the voltage angle when a fault occurs. It
devices have been moved forward in accordance with the devel- is noted that the maximum asymmetrical current appears within
opment of power electronics, magnet technology and supercon- the first half cycle if the fault occurs at the zero voltage crossing
ducting materials [2]–[5]. point. So the onset of SFCLs must be available to limit the max-
Due to superconducting fault current limiters’ low-loss nature imum fault currents within milliseconds.
in superconducting state during normal operation, SFCLs could
offer a solution to controlling fault current levels in utility dis- III. ANALYSIS OF IMPROVING THE POWER SYSTEM TRANSIENT
tribution and transmission networks [6]. In the event of a fault, STABILITY USING SFCL
SFCLs will produce impedances due to losing superconduc- Stable operation of the power system network is dependent
tivity, and insert them into the circuits. Application of SFCLs on the balance of mechanical and electromagnetic forces
keeping the generators in synchronism. When a power system
Manuscript received September 24, 2001. This work was supported by is in normal conditions, there is an equilibrium between the
the National Center for R & D on Superconductivity of China (Contract consumed and produced power in this power system. When a
863-CD040000).
L. Ye and K.-P. Juengst are with Forschungszentrum Karlsruhe (FZK), Insti- large disturbance such as a short circuit or line tripping appears,
tute for Technical Physics (ITP), 3640, D-76021 Karlsruhe, Germany (e-mail: this situation of synchronous equilibrium may momentarily
lin.ye@itp.fzk.de). damp oscillations or definitively be lost, depending on the case.
L. Z. Lin is with the Institute of Electrical Engineering (IEE), Chinese
Academy of Sciences (CAS), Beijing 100080, P. R. China. So the power system transient stability problem is then defined
Publisher Item Identifier S 1051-8223(02)03850-2. as that of assessing whether or not the power angle of the
1051-8223/02$17.00 © 2002 IEEE
YE et al.: APPLICATION STUDIES OF SFCLs IN ELECTRIC POWER SYSTEMS 901

generator will be kept or reach a new acceptable steady-state


operating point following the fault [8]. If SFCLs are used in
the power system during a fault, theory and simulation results
show that the transient stability of system can be enhanced.
Fig. 1. Diagram of a model power system.
A. Electromagnetic Power Characteristic
Power systems are made up of many power plants, transmis-
sion lines and various kinds of loads. Given a system of gen-
erators, so the electromagnetic power of the generator can be
formulated as (3)

(3) Fig. 2. Equivalent circuit of a model power system with SFCL.

Without SFCL, the generator’s power characteristic is de-


where:
duced from (4) and described by (5).
the complex generator voltage source (emf).
the complex generator voltage source (emf).
the complex current of the generator . (5)
the conjugate complex function.
the complex network transfer admittance matrix. where:
The electromagnetic power of the generator can be also ex- system voltage
pressed as a function of the power angle generator voltage (emf)
total reactances of the system during normal operation

(4)

transfer reactance between generator and system.


where: It can be expressed by (6)
angle between and .
modulus of the complex input impedance. (6)
modulus of complex transfer impedance.
,
Based on the positive sequence equivalent criterion, while a
. short circuit occurs, the use of symmetrical components allows
the complex input conductance. any type of faults to be represented in the positive sequence
the complex transfer conductance. network by a fault shunt reactance connected between the
the complex input susceptance. point of the fault and the neutral [7]. The value of the shunt
the complex transfer susceptance. reactance depends on the type of faults.
From (4), the power angle characteristic of a generator can be Supposed the network has SFCL installed (Fig. 2), let the final
expressed by the electric potentials and the relative angles of resistance of the SFCL be given by . So the generator’s power
other generators. characteristic is expressed by (7)

B. Theoretical Analysis of Improving Power System Stability (7)


Using SFCL
The simple power system of Fig. 1 which consists of a gen- where:
erator supplying power to a network via transformers and two rotor angle of synchronous generator
parallel transmission lines was used to investigate how well the complementary angle of the system impedance angle
SFCL can enhance the stability of the power system following final resistance of SFCL
a three-phase short circuit at the beginning of one of the trans- modulus of the complex input impedance
mission lines. In theoretical analysis, the synchronous machine
can be modeled as a constant voltage source (emf) behind
a transient reactance . The damping and field excitation by
AVR (Automatic Voltage Regulator) and PSS (Power System modulus of complex transfer impedance, see (8)
stabilizer) are neglected. The mechanical power is assumed to
be constant. The equivalent circuits of the model power system
with resistive SFCL are shown in Fig. 2. (8)
902 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 12, NO. 1, MARCH 2002

Fig. 3. Diagram of the power angle of the generator with and without SFCL.
Fig. 4. Two radial networks connected via a SFCL.

The power limit of the generator is obtained by . electrical torque is quasi zero. Therefore, the generator is accel-
So the power limits without SFCL and with SFCL are given by erated due to the excessive mechanical input torque. As a re-
(9) and (10), respectively sult, the power angle of the generator increased. The change of
the internal angle will go to infinity with no SFCL used. This
(9) means that the generator starts to accelerate uncontrollably and
the system becomes unstable.
(10)
On the other hand, in the case of the SFCL, the resistance
appears in the superconducting element of the SFCL due to the
In case of the worst fault in a network, i.e., a three-phase quench phenomenon. This inserted resistance ( ) into
short circuit, , the electrical power from the generator the power system could not only limit the short circuit currents
to the system drops, without SFCL, from its prefault value to but also increase the electrical power. So the SFCL could reduce
zero . The driving mechanical power becomes the excess power of the generator, damp the power swing and
much greater than the opposing electrical power and the suppress the generator shaft torque oscillations. Fig. 3 shows
rotor begins to accelerate, and may lose synchronism. With that the power angle of the generator was damped with oscilla-
SFCL, it will produce a resistance to increase electrical power tions and could return to a new stable state.
, and consume the kinetic acceler- It is pointed out that SFCL could improve the power charac-
ating power. The decelerating torque will force the generator teristic and enhance the transient stability of the power system.
rotor back toward the equilibrium point or reach an acceptable
steady-state operating point following the fault.
B. Power Quality
In general, for HV transmission networks, the equiv-
alent resistance is much smaller than that of the equiva- In fact, during a short circuit, the voltage drop causes a cor-
lent reactance. With SFCL, the power characteristic will responding drop of the power transmission to the networks. In
move upwards and power angle shifts left degrees. So order to limit the short circuit level of the system below the com-
. This means that SFCLs can ponents’ withstand level, radial supply networks could be inter-
enhance the transient stability by increasing the power limit connected via SFCL which can keep the voltage level of the
and enlarging the stability region. busbar during the fault (Fig. 4).
In case of a short circuit at 0.2 second on system 2, the bus tie
IV. DIGITAL SIMULATION becomes the main routeway of the fault currents, in which the
SFCL could perform most effectively. Without SFCL, the bus
A. Transient Stability A voltage will drop to 30% of the nominal value ( KV)
In order to investigate how well the SFCL can influence the which causes problems to sensitive loads. If SFCL is used on
power system transient stability, we used the simple power the bus-tie, it can not only decrease the magnitude of the fault
system described in Fig. 2 and Section III to simulate two cases: currents but also give lower voltage dips. Fig. 5 shows that the
with and without SFCL. System simulation parameters are in bus A voltage can be kept on 90% of the nominal level during a
per unit. ( , , , ). fault, although it could incur somewhat overvoltage. The voltage
The evolution of the power angle of the generator with and dips can be mitigated and the bus voltage can be kept on an
without SFCL is shown in Fig. 3. acceptable level during a fault by using the SFCL, thus improve
A three phase short circuit occurred on the line at 1.2 sec- the power quality.
onds at the beginning point of the transmission lines connected As it can be seen, parallel connection of radial systems via the
to transformer 1, the electrical output power of the generator SFCL can improve both the voltage stability, i.e., makes voltage
is mainly reactive, i.e., the effective power output and related dips less severe, and the reliability of supply.
YE et al.: APPLICATION STUDIES OF SFCLs IN ELECTRIC POWER SYSTEMS 903

into the power grid. If SFCLs are used at the strategic points
such as bus-tie positions, the voltage dips can be mitigated and
the bus voltage can be kept on an acceptable level during a fault,
thus improving the power quality as well.
Benefits of SFCLs in this application include the following:
separate buses can be tied together without a large increase in
the fault duty on either bus, a large transformer can be used
to meet increasing demands on a bus without circuit breaker
upgrades, a low impedance transformer can be used to maintain
voltage regulation at the new power level and damage to the
transformer is limited.

VI. FUTURE CONSIDERATIONS ON THE INTERACTION BETWEEN


SFCLS AND POWER SYSTEMS
An SFCL can be effectively used to increase the transient sta-
Fig. 5. Bus A voltage curves with and without SFCL. bility and the power quality without upgrading the power grids.
However, to employ an SFCL properly, other factors need to be
V. SELECTION PRINCIPLE OF DIFFERENT TYPES OF SFCLs considered.
• Coordination between SFCLs and the protective devices.
In order to enhance the transient stability of power systems,
• Recovery characteristic and Open–Close–Open duty.
one of the most important measures is to reduce the equivalent
• Inrush currents of large transformers.
reactance of the network.
• Operation with other FACTS devices.
For high voltage power systems, the reactances of lines and
transformers are much larger than their resistances. During fault
conditions, if using reactance-type of SFCLs such as inductive ACKNOWLEDGMENT
shielded core SFCL, reactances will be magnetically coupling
to the network to limit the fault current. Short circuit current de- The authors would like to acknowledge the discussions with
cays slowly due to the increased time constant of the system. Prof. S. S. Chen of Tsinghua University, Prof. C. Y. Li of Peking
So it is noted that the value of the inductance must be chosen University and Prof. Z. X. Han of ZheJiang University, P. R.
carefully cooperating with the current protective devices. In ad- China. Thanks are also expressed to Prof. Dr. P. Komarek of
dition, it needs no current leads, which is especially attractive Institute for Technical Physics (ITP), Forschungszentrum Karl-
for high current applications, since losses of the leads are pro- sruhe (FZK) of Germany.
portional to their current carrying capability [9]. Compared with
the resistive SFCL, the shielded core SFCL shows the disadvan-
tage of being only applicable for AC-currents and having much REFERENCES
larger size and weight. [1] A. J. Power, “An overview of transmission fault currents,” in Colloquium
On the other hand, resistive type SFCLs like braking resistors, on Fault Current Limiters—A Look at Tomorrow: IEE London, 1995,
can not only restrain the fault current but also consume electrical Digest 1995/026.
[2] R. F. Giese et al., “Assessment study of superconducting fault current
power of the generators during the fault condition. The resistive limiters operation at 77K,” IEEE Trans. Power Delivery, vol. 8, no. 3,
type SFCL can enhance transient stability of the power systems pp. 1138–1147, July 1993.
by suppressing the excessive kinetic energy. [3] R. K. Smith et al., “Solid state distribution current limiter and circuit
breaker application requirements and control strategies,” IEEE Trans.
For low voltage power systems, especially the distribution PWRD, vol. 8, no. 3, pp. 1155–1164, July 1993.
system, the resistances of the feeder cables are larger than their [4] E. Thuries et al., “Toward the superconducting fault current limiter,”
reactances. If the faults occur at the end of the feeder cable, the IEEE Trans. Power Delivery, vol. 6, pp. 801–808, Apr. 1991.
[5] M. Chen et al., “Fabrication and characterization of superconducting
fault current levels may rise to exceed the available switchgear rings for fault current limiter application,”, vol. 282–287, 1997.
interruption ratings due to the distributed capacitances of the [6] R. Schwall, “WTEC Panel Report—Superconducting fault current lim-
feeder cables. In order to use the light circuit breakers and avoid iter,” WTEC-Hyper-Librarian, Sept. 1997.
[7] H. Z. Xiang, Electric Power System Analysis: ZheJiang University Press,
increasing the cross-sectional areas of the feeder cables, reac- 1997.
tance or resistive type SFCLs can be assembled at the end of the [8] J. Machowski, Power System Dynamic and Stability: John Wiley & Sons
feeder positions to limit the fault currents. Press, 1997.
[9] W. Paul and M. Chen et al., “Superconducting fault current limiter appli-
Theoretical analysis and digital simulations show that the cations, technical & economical benefits and simulations & test results,”
power system stability can be enhanced by introducing SFCLs in CIGRE, Paris, Session-2000, 13-201, pp. 1–8.

You might also like