250V CABLES

LKSM-HF
DESIGN: 1. Conductor - stranded copper conductor 2. Insulation - XLPE plastic 3. Bedding - separator tape

Armoured control and instrumentation cable 250 V

STANDARDS: IEC 60092-376, design IEC 60228, class 2 IEC 60092-351 Flameretardant Fireresistant Halogenfree Low smoke emission

4. Armour - copper wire braid, coverage > 90%


2/2010

IEC 60092-350

5. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series

Halogen-free Smoke emission

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Core identification: black numbers on white base Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

27
250V CABLES

LKSM-HF 250V
Part number 26 402 26 403 26 404 26 405 26 407 26 410 26 412 26 414 26 416 26 419 26 424 26 427 26 432 26 437

Number of conductors & cross-section n x mm2 2x0,75 3x0,75 4x0,75 5x0,75 7x0,75 10x0,75 12x0,75 14x0,75 16x0,75 19x0,75 24x0,75 27x0,75 32x0,75 37x0,75

Crosssection of screen mm2 3,6 3,6 3,6 4,1 4,1 5,1 5,3 5,6 11,4 8,7 11,7 11,7 11,8 11,9

Nominal outer diameter mm 7,5 8,0 9,0 9,5 10,0 12,5 12,5 13,0 14,5 15,0 17,0 17,5 18,0 20,0

Approximate weight kg/km 90 105 125 145 165 220 245 270 330 360 460 490 545 620

Current rating A 11,3 9,8 8,9 8,3 7,4 6,6 6,2 5,9 5,6 5,3 4,9 4,7 4,5 4,3

Min. bending radius fixed installation mm 45 50 55 60 60 75 75 80 90 90 105 105 110 120

2/2010

28
250V CABLES

RFE-HF
DESIGN:

Armoured instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design IEC 60228, class 2 IEC 60092-351 Flameretardant Fireresistant Halogenfree Low smoke emission

1. Conductor - stranded copper conductor 2. Insulation - XLPE plastic 3. Bedding - filler tape 4. Armour - drain wire copper (in all sizes) - copper wire braid, coverage > 94%

2/2010

IEC 60092-350

5. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant Halogen-free Smoke emission 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series 0,5mm2 0,75mm2 80 52 55 50 0,6 0,6 1500 1500 1,5mm2 24,4 60 0,7 1500 Unit ohm/km nF/km mH/km Mohm*km.

Electrical data: Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

29
250V CABLES

RFE-HF 250V
Part number 20 362 20 364 20 366 20 368 20 369 20 370 20 371 20 372 20 374 20 376 20 378 20 382 20 384 20 386 20 388 20 389 20 390 20 391 20 392 20 394 20 396 20 490 20 491 20 493 20 494 20 495 20 496 20 497 20 498 20 499 Twisted two pair cable on request: 20 363 20 383 20 492

Number of conductors & cross-section n x mm2 1x2x0,5 2x2x0,5 Quad 4x2x0,5 7x2x0,5 8x2x0,5 10x2x0,5 12x2x0,5 14x2x0,5 19x2x0,5 24x2x0,5 37x2x0,5 1x2x0,75 2x2x0,75 Quad 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 1x2x1,5 2x2x1,5 Quad 4x2x1,5 7x2x1,5 8x2x1,5 10x2x1,5 12x2x1,5 14x2x1,5 19x2x1,5 2x2x0,5 2x2x0,75 2x2x1,5

Nominal outer diameter mm 7,5 8,0 11,5 14,0 14,5 17,0 17,5 18,5 21,0 23,5 28,0 7,5 9,0 12,5 15,5 16,0 18,5 19,0 20,5 23,5 26,0 10,0 11,0 17,0 20,0 21,5 24,5 25,5 27,0 31,0 10,5 11,0 14,5

Approximate weight kg/km 85 100 170 245 270 350 390 440 545 665 930 95 125 215 330 375 440 490 565 715 860 140 190 375 545 625 760 855 960 1230 130 155 235

Min. bending radius fixed installation mm 45 50 70 85 90 105 105 115 130 145 170 45 55 75 95 100 115 115 125 145 160 60 70 105 120 130 150 155 165 190 65 70 90

2/2010

Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... (Quad)cable is built up as a star quad with the following identification 1 core white 2 core blue 3 core white 4 core blue

30
250V CABLES

RFE-HF (i)
DESIGN:

Armoured and pair screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design

1. Conductor - stranded copper conductor IEC 60228, class 2 2. Insulation - XLPE plastic IEC 60092-351 3. Pair screen - plastic coated aluminium tape and a tinned copper drain wire 4. Bedding - filler tape 5. Armour - drain wire copper (in all sizes) - copper wire braid, coverage > 94% IEC 60092-350 6. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour grey, other colours on request

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant Halogen-free Smoke emission 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series 0,75mm2 1,5mm2 52 24,4 70 90 0,6 0,7 1500 1500 Unit ohm/km nF/km mH/km Mohm*km.

Electrical data: Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

31
250V CABLES RFE-HF(i) 250V
Part number 22 006 22 010 22 012 22 014 22 016 22 018 22 020 22 022 22 024 22 026 22 050 22 054 22 056 22 058 22 060 22 062 22 064 22 066 22 068 Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)
2/2010

Number of conductors & cross-section n x mm2 1x2x0,75 2x2x0,75 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 1x2x1,5 2x2x1,5 4x2x1,5 7x2x1,5 8x2x1,5 10x2x1,5 12x2x1,5 14x2x1,5 19x2x1,5

Nominal outer diameter mm 8,0 11,5 13,0 15,5 16,5 19,0 20,0 21,0 24,0 27,0 10,0 14,5 17,0 20,0 22,0 25,0 26,0 28,0 32,0

Approximate weight kg/km 95 170 240 375 420 520 585 650 835 1035 150 255 415 610 700 855 965 1105 1440

Min. bending radius fixed installation mm 50 70 75 100 105 115 120 130 145 160 60 85 105 125 130 150 155 165 190

32
250V CABLES

RFA-HF
DESIGN:

Screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design IEC 60228, class 2 IEC 60092-351 Flameretardant Fireresistant Halogenfree Low smoke emission

1. Conductor - stranded copper conductor 2. Insulation - XLPE plastic 3. Separator - separator tape 4. Screen - drain wire tinned copper - aluminium polyestercopper tape coverage 100%

IEC 60092-350

2/2010

5. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships, especially when lightweight cables are needed. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series 0,5mm2 80 55 0,6 1500 0,75mm2 52 50 0,6 1500 Unit ohm/km nF/km mH/km Mohm*km.

Halogen-free Smoke emission

Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath
Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

33
250V CABLES

RFA-HF 250V
Part number 20 910 20 912 20 916 20 918 20 920 20 922 20 924 20 926 20 930 20 932 20 936 20 970 20 972 20 976 20 978 20 980 20 982 20 984 20 986 20 990 20 992 Twisted pair cables on request. 20 914 20 974 Core identification

Number of conductors & cross-section n x mm2 1x2x0,5 2x2x0,5 Quad 4x2x0,5 7x2x0,5 8x2x0,5 10x2x0,5 12x2x0,5 14x2x0,5 19x2x0,5 24x2x0,5 37x2x0,5 1x2x0,75 2x2x0,75 Quad 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 2x2x0,5 2x2x0,75

Nominal outer diameter mm 6,0 7,0 10,5 12,5 13,5 15,5 16,0 17,5 20,0 22,0 27,0 6,5 7,5 11,5 14,0 15,0 17,0 18,0 19,0 22,0 24,5 9,0 10,0

Approximate weight kg/km 45 65 120 175 200 245 280 315 410 515 745 55 80 150 225 260 320 365 415 555 680 75 100

Min. bending radius fixed installation mm 40 45 65 75 85 95 100 105 120 135 165 40 45 70 85 90 105 110 115 135 150 55 60

2/2010

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... (Quad)cable is built up as a star quad with the following identification 1 core white 2 core blue 3 core white 4 core blue

34
250V CABLES

RFA-HF (i)
DESIGN:

Collectively and pair screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design

1. Conductor - stranded copper conductor IEC 60228, class 2 2. Insulation - XLPE plastic IEC 60092-351 3. Pair screen - plastic coated aluminium tape and a tinned copper drain wire 4. Bedding - separator tape 5. Collective screen - drain wire tinned copper IEC 60092-350 - aluminium polyester tape, coverage 100% 6. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour grey, other colours on request

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas and on open deck in ships, especially when lightweight cables are needed. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant Halogen-free Smoke emission 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series

Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. Loop inductance, nom. Insulation resistance / +20C

0,5mm2 80 55 0,6 1500

0,75mm2 52 70 0,6 1500

Unit ohm/km nF/km mH/km Mohm*km

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath
Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

35
250V CABLES

RFA-HF(i) 250V
Part number 20 940 20 942 20 944 20 946 20 948 20 950 20 952 20 956 20 958 21 059 21 061 21 063 21 065 21 067 21 069 21 071 21 075 21 077 Other sizes on request.

Number of conductors & cross-section n x mm2 2x2x0,5 4x2x0,5 7x2x0,5 8x2x0,5 10x2x0,5 12x2x0,5 14x2x0,5 19x2x0,5 24x2x0,5 2x2x0,75 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75

Nominal outer diameter mm 9,5 11,0 13,0 14,0 16,0 16,5 17,5 20,0 22,5 10,0 12,0 14,5 15,0 17,5 18,0 19,5 22,5 25,0

Approximate weight kg/km 95 145 220 245 305 350 395 520 655 115 180 275 310 380 440 520 680 840

Min. bending radius fixed installation mm 60 65 80 85 95 100 110 125 140 65 75 90 95 105 110 120 135 155

2/2010

Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... The pairs are covered by a numbered tape (1, 2, 3, 4, 5....)

36
250V CABLES

RFE-FRHF
DESIGN: 1. Conductor - stranded copper conductor 2. Insulation - Mica tape - XLPE plastic 3. Bedding - filler tape

Fire-resistant armoured instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design IEC 60228, class 2 Flameretardant Fireresistant Halogenfree Low smoke emission

IEC 60092-351

2/2010

4. Armour - drain wire (in all sizes) - copper wire braid, coverage > 94%

IEC 60092-350

5. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant Fire-resistant Halogen-free Smoke emission Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C 150/250V (300V) + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60331-21 IEC 60754 series IEC 61034 series

0,75mm2 1,5mm2 52 24,4 45 55 0,6 0,7 1500 1500

Unit ohm/km nF/km mH/km Mohm*km.

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

37
250V CABLES

RFE-FRHF 250V
Part number 20 520 20 522 20 526 20 528 20 530 20 532 20 534 20 536 20 538 20 540 20 575 20 577 20 581 20 583 20 585 20 587 20 589 20 591 Twisted two pair cable on request 20 524 20 579

Number of conductors & cross-section n x mm2 1x2x0,75 2x2x0,75 Quad 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 1x2x1,5 2x2x1,5 Quad 4x2x1,5 7x2x1,5 8x2x1,5 10x2x1,5 12x2x1,5 14x2x1,5 2x2x0,75 2x2x1,5

Nominal outer diameter mm 9,5 11,0 16,5 20,0 21,0 24,5 25,5 27,0 31,0 34,5 10,5 12,0 18,5 22,5 24,0 27,5 29,0 30,5 14,0 16,0

Approximate weight kg/km 115 160 325 465 510 630 705 800 1015 1245 155 220 430 650 715 875 1000 1125 210 315

Min. bending radius fixed installation mm 60 70 100 120 130 150 155 165 190 210 65 75 115 140 150 165 175 185 85 100

2/2010

Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... (Quad)cable is built up as a star quad with the following identification 1 core white 2 core blue 3 core white 4 core blue

38
250V CABLES

RFE-FRHF (i)
DESIGN:

Fire-resistant armoured and pair screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design

1. Conductor - stranded copper conductor IEC 60228, class 2 2. Insulation - Mica tape - XLPE plastic IEC 60092-351 3. Pair screen - plastic coated aluminium tape and a tinned copper drain wire 4. Bedding - filler tape 5. Armour - drain wire copper - copper wire braid, coverage > 94% IEC 60092-350 6. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour orange, other colours on request

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant Fire-resistant Halogen-free Smoke emission 150/250V (300V) + 90 C IEC 60332-1-2 IEC 60332-3-22 IEC 60331-21 IEC 60754 series IEC 61034 series 0,75mm2 1,5mm2 52 24,4 55 75 0,6 0,7 1500 1500 Unit ohm/km nF/km mH/km Mohm*km.

-test for single insulated wire and cable -test for bunched wires and cables, category A

Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

39
250V CABLES

RFE-FRHF(i) 250V
Part number 20 546 20 550 20 552 20 554 20 556 20 558 20 560 20 562 20 564 20 566 20 603 20 605 20 607 20 609 20 611 20 613 20 615 20 617 Core identification

Number of conductors & cross-section n x mm2 1x2x0,75 2x2x0,75 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 1x2x1,5 2x2x1,5 4x2x1,5 7x2x1,5 8x2x1,5 10x2x1,5 12x2x1,5 14x2x1,5

Nominal outer diameter mm 9,5 14,5 17,0 20,0 22,0 25,0 26,0 27,5 32,0 35,0 10,5 16,5 19,0 23,0 24,5 28,0 29,5 31,5

Approximate weight kg/km 125 225 355 515 585 710 800 910 1175 1425 165 320 475 720 810 985 1145 1295

Min. bending radius fixed installation mm 60 90 105 125 135 150 155 170 195 215 65 100 115 140 150 170 180 190

2/2010

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)

40
250V CABLES

RFA-FRHF
DESIGN:

Fire-resistant screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design

1. Conductor - stranded copper conductor IEC 60228, class 2 2. Insulation - Mica tape - XLPE plastic IEC 60092-351 3. Bedding - separator tape 4. Screen - drain wire tinned copper - aluminium polyester tape coverage 100% IEC 60092-350 5. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour orange, other colours on request

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant 150/250V (300V) + 90 C IEC 60332-1-2 IEC 60332-3-22

-test for single insulated wire and cable -test for bunched wires and cables, category A

Fire-resistant IEC 60331-21 Halogen-free IEC 60754 series Smoke emission IEC 61034 series For details see general information section Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C 0,75mm2 52 45 0,6 1500 Unit ohm/km nF/km mH/km Mohm*km.

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

41
250V CABLES

RFA-FRHF 250V
Part number 20 635 20 637 20 641 20 643 20 645 20 647 20 649 20 651 20 655 20 657 Twisted two pair cables on request 20 639

Number of conductors & cross-section n x mm2 1x2x0,75 2x2x0,75 Quad 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75 2x2x0,75

Nominal outer diameter mm 8,5 10,0 15,5 18,5 20,0 23,0 24,0 25,5 29,5 33,5 13,0

Approximate weight kg/km 75 120 215 330 380 480 545 620 805 1030 135

Min. bending radius fixed installation mm 55 60 95 115 120 140 145 155 180 205 80

Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... (Quad)cable is built up as a star quad with the following identification 1 core white 2 core blue 3 core white 4 core blue
2/2010

42
250V CABLES

RFA-FRHF (i)
DESIGN:

Fire-resistant collectively and pair screened instrumentation and communication cable 250V

STANDARDS: IEC 60092-376, design

1. Conductor - stranded copper conductor IEC 60228, class 2 2. Insulation - Mica tape - XLPE plastic IEC 60092-351 3. Pair screen - plastic coated aluminium tape and a tinned copper drain wire 4. Bedding - separator tape 5. Collective screen - drain wire tinned copper - aluminium polyester tape coverage 100 % IEC 60092-350 6. Sheath - polyolefine plastic, SHF1 IEC 60092-359 - standard colour orange, other colours on request

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas and on open deck in ships. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant 150/250V (300V) + 90 C IEC 60332-1-2 IEC 60332-3-22

-test for single insulated wire and cable -test for bunched wires and cables, category A

Fire-resistant IEC 60331-21 Halogen-free IEC 60754 series Smoke emission IEC 61034 series For details see general information section Electrical data Loop resistance of pair, max. / +20C Pair capacitance, nom. / 800Hz Loop inductance, nom. Insulation resistance / +20C 0,75mm2 52 55 0,6 1500 Unit ohm/km nF/km mH/km Mohm*km.

Minimum recommended installation temperature -15 C Lowest operation temperature -40 C Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

43
250V CABLES

RFA-FRHF(i) 250V
Part number 20 667 20 669 20 671 20 673 20 675 20 677 20 679 20 683 20 685

Number of conductors & cross-section n x mm2 2x2x0,75 4x2x0,75 7x2x0,75 8x2x0,75 10x2x0,75 12x2x0,75 14x2x0,75 19x2x0,75 24x2x0,75

Nominal outer diameter mm 13,5 15,5 18,5 20,0 23,5 24,5 26,0 30,0 34,0

Approximate weight kg/km 155 245 380 430 545 625 725 945 1205

Min. bending radius fixed installation mm 85 95 115 120 145 150 160 180 205

Core identification Each pair white - blue. Cores numbered 1, 2, 3, 4, 5.... The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)
2/2010

44
60V CABLES

PBS

Field bus cable 60V

DESIGN: STANDARDS: Twisted pair cable EN 50170 1. Conductor - stranded copper conductor 2. Insulation - Polyethylene / foamed polyethylene plastic 3. Pair twisting 4. Bedding - separator tape 5. Screen - plastic coated aluminium tape and tinned copper braid, coverage 100% 6. Sheath - purple, polyolefine plastic 7. Outer sheath - grey polyolefine plastic, SHF1

Flameretardant Fireresistant Halogenfree Low smoke emission

2/2010

Application: For fixed installation in most areas. If the cable is exposed to direct sun light protective covering or cable with black outer sheath is recommended. Main characteristics Rated voltage Maximum conductor temperature Flame-retardant 60V + 90 C IEC 60332-1-2 -test for single insulated wire and cable IEC 60332-3-22 -test for bunched wires and cables, category A IEC 60754 series IEC 61034 series

Halogen-free Smoke emission

Identification: Lot number, cable type, cable size, voltage, temperature, standards, production month, manufacturer's name and meter marking printed on the sheath Core identification Each pair green - red.

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi

45
60V CABLES

PBS
Part number

Number of conductors & cross-section n x mm2 1 x 2 x 0,34

Nominal outer diameter mm 10,5

Approximate weight kg/km 145

Min.bending radius fixed installation mm 65

20 506

Cable for PROFIBUS DP. The cable has been tested according to the IEC 61158 specification and testing guidelines set by PROFIBUS Center Nederland. Cable is approved as type A cable. Compatible with the connector of Siemens (6ES7-972-0BA12 0XA0 or similar) after stripping the outer sheath.
2/2010

Type A bus cable. Maximum length of each bus segment. Data transfer rate in kbit/s Max. segment length in m 9.6 93.75 1200 187.5 1000 500 400 1500 200 3000 12000 100