Functional Description
LineTroll110E continuously monitors the line voltage and phase current, the sources of information it needs to operate. The unit is fully self-contained, no external transformers or connections is required. During normal line conditions, LineTroll110E remains extinguished. The indicator is looking for a specific sequence of line conditions to happen before it starts flashing. The general sequence is as follows: A. The line should be energised (voltage or current present) for a minimum of 5 seconds. B. Di/Dt: The line current should increase rapidly by the amount of a user set value (the step level). Threshold: The line current exceeding a preset current level C. The line should be de-energised. (voltage or current not present) The user may program the criteria for operation to suit his local requirement by manipulating a bank of micro-switches inside the indicator.
LineTroll110E
Fault Passage Indicator for Overhead lines (6-66kV)
Technical Specifications
Application: Fault-detection: Innrush-blocking: Reset: Short circuit and Earth fault indication for overhead lines. System Voltage: MV voltage network (6-66kV) Grounding system: Isolated, resistor and solidly grounded Sensitivity Di/Dt: 6, 12, 25, or 60* Sensitivity treshold: 250, 500, 750 or 1000A* Duration: >25ms* 5 sec Automatic: Re- energized line (Voltage or current, programmable) Timer: 2, 6, 12, or 32 hours Manual: By magnet/Mounting-reset tool
Note *: All treshold, timers etc. are selectable and programmable by microswitches. Indication: Intensity: Power supply: Mounting: Temp: Housing: Dimension: Weight: Degree of protection: Battery change: Hot-stick Conductor size: 1 Green LED for transient fault 4 Red LEDs for permanent fault 1 Orange Led for low battery indication > 10 lumens 1 Lithium Cell (D size 16,5 Ah) Every 1200 hous flashing, normally every 7-8 years Live-line mounting with KBN-3 mounting tool 5-24mm -40 to +70 deg Polycarbonate, UV stablized 202 x 54mm (with box 235 x 65 x 85) 460g (including box and battery) IP54
Ordering Information
Product nr: Product nr: Product nr: Product nr: 1200 1066 1068 1056 LineTroll110E KBN-3 Reset/mounting tool with bolt hot-stick adaptor KBN-3 Reset/mounting tool with eye-plate hot-stick adaptor KBB-11 replacement battery
Since the foundation in 1976, Nortroll AS has devoted its activities to the development of equipment aiming to reduce electric utilities outage times. We offers a wide range of products for fault detection and remote operation in the MV Distribution Network.
About Nortroll AS
Your Representative