STRUCTURAL CALCULATIONS

PROJECT SUBJECT DESIGNER DATE

ISOLATED FOOTING DESIGN 6/29/2011 18:53

The design loads considered in the sizing of the footing are unfactored or service loads as stated in the National Structural Code of the Philippines 5th Edition Section 415.3.2 Footing Name Allowable Soil Bearing Capacity Design Service load F1 2000 psf 595 kip

The weight of the foundation to be added to the service load shall be at a maximum of 10% of the load Foundation Weight Total Load 59.5 kip 654.5 kip

The required area of footing shall be determined by dividing the total load by the allowable soil bearing pressure Required Area Adopted Dimensions of Footing WIDTH LENGTH Actual Footing Area Actual Soil Pressure 327.25 sqft

13.12 ft 13.12 ft 172.13 sqft 3802.26 psf

4 meter 4 meter

For the design of footing reinforcement, ultimate loads (1.4DL+1.7LL) or 1.55xActual Soil Pressure shall be considered Reinforcement Along Ftg Width Column Dim. 28 Cant. Length 5.39 Moment 85.72 Des. Mu 85.72 r F'c Fy Rn Ftg. Thk. Adopt Ftg. Thk. As_bot Rebar dia Rebar area No. Rebar 0.0030 3000 60000 173.65 26.42 Reinforcement Along Ftg Length Column Dim. 28 in Cant. Length 5.39 ft Moment 85.72 kip-ft/ft

in ft kip-ft/ft kip-ft/ft

psi psi psi in Trial Ftg. Thk. As_bot Rebar dia Rebar area No. Rebar 28 in 11.81 sqin 20 mm 0.487 sqin 25 pcs.

28 in 11.81 sqin 20 mm 0.487 sqin 25 pcs. END