DUCTING AND DIFFUSER SIZE COMPUTATION SHEET Project: College of Hotel and Restaurant Management Hasmin Building Third

Floor
THE MAIN DUCT Zone 1

Zone 2

AHU

TOTAL cfm ON THIRD FLOOR = 20,543 VELOCITY for SCHOOLS based on ASHRAE = FRICTION LOSS based on FRICTION LOSS CHART TOTAL cfm on ZONE 1 = 7,171 cfm TOTAL cfm on ZONE 2 = 13,372 cfm Main Duct total CFM per floor velocity for school equivalent diameter duct size (in) longest width cfm of based duct 49 20,543 based DUCT width - X = Y x= y= 17 32 = = = = 20,543 1300 53.8 49 x in by

cfm 1,300 =

fpm 0.04

in WC/100 ft

144in sq ft. sq

2276

ft sq.

49

X cfm on next duct x 7,171

SIZING for ZONE 1 from MAIN DUCT total cfm for the next rooms = 7,171 friction loss based on the friction loss chart = 0.04 equivalent diameter = 36 in duct size (in) = 33 by

in.WC/100ft 33

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 33 17 ) ( 7 ) L= 112 in

ZONE 1

TO NEXT ROOMS

longest width cfm of based duct 33 7,171

X cfm on next duct X 4831

ND LABORATORY

based DUCT width - X = Y x= y= 22 11

sizing for next rooms ducts total cfm for the next rooms = 4,831 friction loss based on the friction loss chart= equivalent diameter = 31 duct size (in) = 29

(eccentric) cfm 0.04 in by

in.WC/100ft 28

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 29 22 L= 49 in sizing for ROOM total cfm for the rooms = 2340 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 23.6 duct size (in) = 22

)(7)

(concentric) cfm 0.04 770.5 in by

in.WC/100ft fpm 21

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 22 11 ) 2 / (4) L= 22 in DIFFUSER Size Computation cfm of the room = 2340 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = 1170 cfm 0.04 in. WC / 100 ft 770.5 / = 649.4 1.8 ft2

fpm

diffuser size = cfm/ fpm

= = = = =

1.80 x in2 / % compensation ans. = 13 by 22 in 2

144 = 19.3

= 370.6 in

259.4 in2

in2

diffuser size (rectangle) no. of diffuser

TO NEXT ROOMS

longest width cfm of based duct 29 4,831

X cfm on next duct X 2693

BEVERAGE AND CATERING ROOM

based DUCT width - X = Y x= y= 16 13

sizing for next rooms ducts total cfm for the next rooms = 2,693 friction loss based on the friction loss chart= equivalent diameter = 24.9 duct size (in) = 23

(eccentric) cfm 0.04 in by

in.WC/100ft 23

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 23 16 L= 49 in sizing for ROOM total cfm for the rooms = 2138 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.8 duct size (in) = 21

)(7)

(concentric) cfm 0.04 753.6 in by

in.WC/100ft fpm 21

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 13 ) 2 / (4) L= 18 in DIFFUSER Size Computation cfm of the room = 2138 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = 1069 0.04 753.6 1.7 cfm in. WC / 100 ft / = 635 ft2

fpm

diffuser size = cfm/ fpm

= = = = =

1.68 x in / % compensation ans. =


2

144 = 18.6

= 346.3 in

242.4 in2

in2

diffuser size (rectangle) no. of diffuser

13 by 20 in 2

QUALITY AND CONTROL ROOM sizing for room total cfm of the room = 2693 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 24.9 duct size (in) = 23 (concentric) cfm 0.04 797.5 in by

in.WC/100ft fpm 23

DIFFUSER Size Computation cfm of the room = 2693 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = diffuser size = cfm/ fpm = = = = = 1347 0.04 797.5 2.0 cfm in. WC / 100 ft / = 672.4 ft2 144 = 20.3 = 412.1 in 288.5 in2 in2

fpm

2.00 x in / % compensation ans. =


2

diffuser size (rectangle) no. of diffuser

15 by 21 in 2

SIZING for ZONE 2 from MAIN DUCT total cfm for the next rooms = 13,372 cfm friction loss based on the friction loss chart = 0.04 equivalent diameter = 45.7 in duct size (in) = 42 by L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) (( 42 32 L= 20 in

in.WC/100ft 42

) 2 / (4)

ZONE 2

TO NEXT ROOMS

longest width cfm of based duct 42 13,372

X cfm on next duct X 11398

FOOD PREPARATION

based DUCT width - X = Y x= y= 36 6

sizing for next rooms ducts total cfm for the next rooms = 11,398 friction loss based on the friction loss chart= equivalent diameter = 43 duct size (in) = 40

(eccentric)

0.04 in by

in.WC/100ft 39

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 40 36 L= 28 in sizing for ROOM total cfm for the rooms = 1975 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.1 duct size (in) = 20

)(7)

(concentric) cfm 0.04 739 in by

in.WC/100ft fpm 20

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 20 6 L= 28 in DIFFUSER Size Computation cfm of the room = 1975 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

) 2 / (4)

0.04 739 2.7

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

= = =

2.67 x in2 / % compensation ans. =

144 = 23.4

= 549.7 in

384.8 in2

in2

diffuser size (rectangle) no. of diffuser

= =

17 by 24 in 1

TO NEXT ROOMS

longest width cfm of based duct 40 11,398

X cfm on next duct X 10,323

CENTRALIZED STORAGE

based DUCT width - X = Y x= y= 36 4

sizing for next rooms ducts total cfm for the next rooms = 10,323 friction loss based on the friction loss chart= equivalent diameter = 41.4 duct size (in) = 38

(eccentric)

0.04 in by

in.WC/100ft 38

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 38 36 L= 14 in sizing for ROOM total cfm for the rooms = 1,075 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 17.6 duct size (in) = 16

)(7)

(concentric) cfm 0.04 635.9 in by

in.WC/100ft fpm 16

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 16 4 L= 24 in DIFFUSER Size Computation cfm of the room = 1075 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

) 2 / (4)

0.04 635.9 1.7

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

= = = = =

1.69 x in / % compensation ans. =


2

144 = 18.6

= 347.8 in

243.4 in2

in2

diffuser size (rectangle) no. of diffuser

13 by 20 in 1

TO NEXT ROOMS

longest width cfm of based duct 38 10,323

X cfm on next duct X 8,255

CLASSROOM 305 based DUCT width - X = Y x= y= 30 8

sizing for next rooms ducts total cfm for the next rooms = 8,255 friction loss based on the friction loss chart= equivalent diameter = 38 duct size (in) = 35

(eccentric)

0.04 in by

in.WC/100ft 35

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 35 30 L= 35 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21

)(7)

(concentric) cfm 0.04 747.4 in by

in.WC/100ft fpm 20

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 8 L= 26 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

) 2 / (4)

0.04 747.4 2.8

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

2.77

144

398.4

in2

= = diffuser size (rectangle) no. of diffuser = =

in2 / % compensation ans. = 18 by 24 in 1

= 23.9

569.2 in

in2

TO NEXT ROOMS

longest width cfm of based duct 35 8,255

X cfm on next duct X 6,187

CLASSROOM 304

based DUCT width - X = Y x= y= 26 9

sizing for next rooms ducts total cfm for the next rooms = 6,187 friction loss based on the friction loss chart= equivalent diameter = 34.1 duct size (in) = 31

(eccentric)

0.04 in by

in.WC/100ft 31

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 31 26 L= 35 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21

)(7)

(concentric) cfm 0.04 747.4 in by

in.WC/100ft fpm 20

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 9 L= 24 in

) 2 / (4)

DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

0.04 747.4 2.8

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

= =

2.77 x in / % compensation
2

144 =

= 569.2

398.4 in2

in2

= diffuser size (rectangle) no. of diffuser = =

ans. 18 by 24 in 1

23.9

in

TO NEXT ROOMS

longest width cfm of based duct 31 6,187

X cfm on next duct X 4,119

CLASSROOM 303

based DUCT width - X = Y x= y= 21 10

sizing for next rooms ducts total cfm for the next rooms = 4,119 friction loss based on the friction loss chart= equivalent diameter = 29.2 duct size (in) = 27

(eccentric)

0.04 in by

in.WC/100ft 26

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 27 21 L= 42 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21

)(7)

(concentric) cfm 0.04 747.4 in by

in.WC/100ft fpm 20

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 10 L= 22 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

) 2 / (4)

0.04 747.4 2.8

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

2.77

144

398.4

in2

diffuser size (rectangle) no. of diffuser

= = = =

in2 / % compensation ans. = 18 by 24 in 1

= 23.9

569.2 in

in2

TO NEXT ROOMS

longest width cfm of based duct 27 4,119

X cfm on next duct X 2,052

CLASSROOM 302

based DUCT width - X = Y x= y= 13 14

sizing for next rooms ducts total cfm for the next rooms = 2,052 friction loss based on the friction loss chart= equivalent diameter = 22.5 duct size (in) = 21

(eccentric)

0.04 in by

in.WC/100ft 20

L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 21 13 L= 56 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21

)(7)

(concentric) cfm 0.04 747.4 in by

in.WC/100ft fpm 20

L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 14 L= 14 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

) 2 / (4)

0.04 747.4 2.8

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

= = = = =

2.77 x in / % compensation ans. =


2

144 = 23.9

= 569.2 in

398.4 in2

in2

diffuser size (rectangle) no. of diffuser

18 by 24 in 1

CLASSROOM 301

sizing for room total cfm of the room = 2052 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21 DIFFUSER Size Computation cfm of the room = 2052 friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =

(concentric) cfm 0.04 746 in by

in.WC/100ft fpm 20

0.04 746 2.8

in. WC / 100 ft fpm ft2

diffuser size = cfm/ fpm

= = = = =

2.75 x in2 / % compensation ans. = 18 by 24 in 1

144 = 23.8

= 565.9 in

396.1 in2

in2

diffuser size (rectangle) no. of diffuser