THE MAIN DUCT Zone 1
Zone 2
AHU
TOTAL cfm ON THIRD FLOOR = 20,543 VELOCITY for SCHOOLS based on ASHRAE = FRICTION LOSS based on FRICTION LOSS CHART TOTAL cfm on ZONE 1 = 7,171 cfm TOTAL cfm on ZONE 2 = 13,372 cfm Main Duct total CFM per floor velocity for school equivalent diameter duct size (in) longest width cfm of based duct 49 20,543 based DUCT width - X = Y x= y= 17 32 = = = = 20,543 1300 53.8 49 x in by
cfm 1,300 =
fpm 0.04
in WC/100 ft
144in sq ft. sq
2276
ft sq.
49
SIZING for ZONE 1 from MAIN DUCT total cfm for the next rooms = 7,171 friction loss based on the friction loss chart = 0.04 equivalent diameter = 36 in duct size (in) = 33 by
in.WC/100ft 33
ZONE 1
TO NEXT ROOMS
ND LABORATORY
sizing for next rooms ducts total cfm for the next rooms = 4,831 friction loss based on the friction loss chart= equivalent diameter = 31 duct size (in) = 29
in.WC/100ft 28
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 29 22 L= 49 in sizing for ROOM total cfm for the rooms = 2340 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 23.6 duct size (in) = 22
)(7)
in.WC/100ft fpm 21
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 22 11 ) 2 / (4) L= 22 in DIFFUSER Size Computation cfm of the room = 2340 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = 1170 cfm 0.04 in. WC / 100 ft 770.5 / = 649.4 1.8 ft2
fpm
= = = = =
144 = 19.3
= 370.6 in
259.4 in2
in2
TO NEXT ROOMS
sizing for next rooms ducts total cfm for the next rooms = 2,693 friction loss based on the friction loss chart= equivalent diameter = 24.9 duct size (in) = 23
in.WC/100ft 23
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 23 16 L= 49 in sizing for ROOM total cfm for the rooms = 2138 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.8 duct size (in) = 21
)(7)
in.WC/100ft fpm 21
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 13 ) 2 / (4) L= 18 in DIFFUSER Size Computation cfm of the room = 2138 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = 1069 0.04 753.6 1.7 cfm in. WC / 100 ft / = 635 ft2
fpm
= = = = =
144 = 18.6
= 346.3 in
242.4 in2
in2
13 by 20 in 2
QUALITY AND CONTROL ROOM sizing for room total cfm of the room = 2693 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 24.9 duct size (in) = 23 (concentric) cfm 0.04 797.5 in by
in.WC/100ft fpm 23
DIFFUSER Size Computation cfm of the room = 2693 / 2 = friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM = diffuser size = cfm/ fpm = = = = = 1347 0.04 797.5 2.0 cfm in. WC / 100 ft / = 672.4 ft2 144 = 20.3 = 412.1 in 288.5 in2 in2
fpm
15 by 21 in 2
SIZING for ZONE 2 from MAIN DUCT total cfm for the next rooms = 13,372 cfm friction loss based on the friction loss chart = 0.04 equivalent diameter = 45.7 in duct size (in) = 42 by L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) (( 42 32 L= 20 in
in.WC/100ft 42
) 2 / (4)
ZONE 2
TO NEXT ROOMS
FOOD PREPARATION
sizing for next rooms ducts total cfm for the next rooms = 11,398 friction loss based on the friction loss chart= equivalent diameter = 43 duct size (in) = 40
(eccentric)
0.04 in by
in.WC/100ft 39
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 40 36 L= 28 in sizing for ROOM total cfm for the rooms = 1975 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.1 duct size (in) = 20
)(7)
in.WC/100ft fpm 20
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 20 6 L= 28 in DIFFUSER Size Computation cfm of the room = 1975 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
) 2 / (4)
= = =
144 = 23.4
= 549.7 in
384.8 in2
in2
= =
17 by 24 in 1
TO NEXT ROOMS
CENTRALIZED STORAGE
sizing for next rooms ducts total cfm for the next rooms = 10,323 friction loss based on the friction loss chart= equivalent diameter = 41.4 duct size (in) = 38
(eccentric)
0.04 in by
in.WC/100ft 38
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 38 36 L= 14 in sizing for ROOM total cfm for the rooms = 1,075 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 17.6 duct size (in) = 16
)(7)
in.WC/100ft fpm 16
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 16 4 L= 24 in DIFFUSER Size Computation cfm of the room = 1075 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
) 2 / (4)
= = = = =
144 = 18.6
= 347.8 in
243.4 in2
in2
13 by 20 in 1
TO NEXT ROOMS
sizing for next rooms ducts total cfm for the next rooms = 8,255 friction loss based on the friction loss chart= equivalent diameter = 38 duct size (in) = 35
(eccentric)
0.04 in by
in.WC/100ft 35
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 35 30 L= 35 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21
)(7)
in.WC/100ft fpm 20
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 8 L= 26 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
) 2 / (4)
2.77
144
398.4
in2
= 23.9
569.2 in
in2
TO NEXT ROOMS
CLASSROOM 304
sizing for next rooms ducts total cfm for the next rooms = 6,187 friction loss based on the friction loss chart= equivalent diameter = 34.1 duct size (in) = 31
(eccentric)
0.04 in by
in.WC/100ft 31
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 31 26 L= 35 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21
)(7)
in.WC/100ft fpm 20
) 2 / (4)
DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
= =
2.77 x in / % compensation
2
144 =
= 569.2
398.4 in2
in2
ans. 18 by 24 in 1
23.9
in
TO NEXT ROOMS
CLASSROOM 303
sizing for next rooms ducts total cfm for the next rooms = 4,119 friction loss based on the friction loss chart= equivalent diameter = 29.2 duct size (in) = 27
(eccentric)
0.04 in by
in.WC/100ft 26
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 27 21 L= 42 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21
)(7)
in.WC/100ft fpm 20
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 10 L= 22 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
) 2 / (4)
2.77
144
398.4
in2
= = = =
= 23.9
569.2 in
in2
TO NEXT ROOMS
CLASSROOM 302
sizing for next rooms ducts total cfm for the next rooms = 2,052 friction loss based on the friction loss chart= equivalent diameter = 22.5 duct size (in) = 21
(eccentric)
0.04 in by
in.WC/100ft 20
L (length of eccentric) = (width of the next duct - x) ( 7 ) ( 21 13 L= 56 in sizing for ROOM total cfm for the rooms = 2,068 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21
)(7)
in.WC/100ft fpm 20
L (length ofconcentric) (=(width of next duct - y) / 2 ) ( 4 ) ( 21 14 L= 14 in DIFFUSER Size Computation cfm of the room = 2068 cfm friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
) 2 / (4)
= = = = =
144 = 23.9
= 569.2 in
398.4 in2
in2
18 by 24 in 1
CLASSROOM 301
sizing for room total cfm of the room = 2052 friction loss based on the friction loss chart= fpm based on the friction loss chart = equivalent diameter = 22.5 duct size (in) = 21 DIFFUSER Size Computation cfm of the room = 2052 friction loss based on the friction loss chart = fpm based on the friction loss chart = percent compensation = 0.7 cfm per room / fpm of ROOM =
in.WC/100ft fpm 20
= = = = =
144 = 23.8
= 565.9 in
396.1 in2
in2