Professional Documents
Culture Documents
Joseph's Chennai
NEUTRAL EARTHING
ARCING GROUND
If a capacitive fault current of around 4 to 5 mA flows into the earth which is sufficient to maintain a arc in the ionized path of the fault , even though the medium causing the fault has cleared itself. Charging and discharging of system due to capacitive currents gives rise to persistency of arc. Very high voltages build up which can cause insulation break down.
Below 3.3 kV and above 33 kV Between 3.3 kV and 33 kV Between 3.3 kV and 33 kV
EFFECTIVELY GROUNDED
Ratio of zero sequence reactance to positive sequence reactance must not be greater than 3 Ratio of zero sequence resistance to positive sequence resistance must not be greater than 1 for any condition of operation
FAVOR
PROBLEM
Arcing grounds and over voltages are eliminated. Ground fault relaying is simple and satisfactory. Voltage of the healthy phases does not exceed 80% of the normal voltage Less cost of insulation
Heavy flow of fault current. Danger to personnel. Transient fault may also be converted in to short circuit fault. Interference with communication circuit. Current handling by circuit breakers are difficult.
RESISTANCE GROUNDING
Grounding of system through low value of resistance allows the use of discriminative relaying. Limits the fault current. Less interference with communication circuits. Transient ground faults are converted to controlled current faults. Enormous energy loss in the resistor. Extra investment and shift of system neutral.
RESONANT GROUNDING
Iron core tapped reactor tuned to system capacitance. Arcing grounds are self extinguished and to reduce ground fault currents. Medium voltage overhead lines and radial lines employ resonant grounding. During normal operation losses are minimal. Less interference with communication circuits. Continuity of supply can be maintained until fault is cleared