HF-REGULATOR II Touch and DALI for PL-L lamps

Product Description

Flat, lightweight high-frequency electronic regulating ballast, using DALI (Digital Addressable Lighting Interface) or Touch and Dim pushbutton protocol for PL-L fluorescent lamps

Features and Benefits


Lamp power can be regulated from 1 to 100% Flat ballast design, 22 mm high Digital control input according to the industry-standard DALI (Digital Addressable Lighting Interface) combined with the Touch and Dim pushbutton protocol Protected against excessive mains voltages, incorrect connections and incorrect lamp use Striation-free operation, no stroboscopic effects Lamp starts at 10% (DALI 1..100% in 250 ms, from 100..1% in 100ms) Automatic stop circuit is activated within 5 s in case of lamp failure (safety stop) Ballast resets automatically after lamp replacement Equipped with WAGO 251 connectors suitable for automatic wiring Up to 75% reduction in energy consumption by using automatic lighting control systems (e.g. Philips ActiLume) Quick warm start: 0.5 s, flicker-free warm start by preheating the lamp electrodes enables lamps to be switched on/off without reducing useful life. Ideal for areas with a high switching frequency Low energy consumption in standby 0.35 W Smart power ensures constant light, independent of mains fluctuations Philips HF-REGULATOR II gear is equipped with Extended Cable Flexibility (ECF) Technology. ECF Technology is based on a dedicated integrated circuit that ensures independent control of lamps, and in doing so takes care that:

HF-R PL-L/PL-T/TL5/TL5/PL-L/TL-D

In case of long or asymmetrical wiring (e.g. with emergency units or bundled wiring) deep and stable dimming is guaranteed (possible consequences for electromagnetic interference and compatibility EMI/EMC to be checked) Systems always remain operational in extreme conditions (e.g. low temperatures, lamp impurities at burning-in) in combination with the integrated anti extinguish control Lamp life is unaffected by dimming position whilst energy savings are maximized

Applications

Offices requiring simple, easy-to-install dimming or personal light level adjustment, e.g. with ActiLume DALI installations with daylight linking and/or movement detection DALI installations with remote control systems Installations with emergency back-up, according to IEC 60598-2-22

Quality Philips Quality applies optimum quality with respect to:

3.2

OEM Catalogue 2008/2009

HF-REGULATOR II Touch and DALI for PL-L lamps

ENEC VDE-EMV EN 61347-1

Compliances and approvals RFI < 30 MHz RFI > 30 MHz Harmonics Immunity Safety Performance EN 55015 EN 55022 limit B EN 61000-3-2 EN 61547 EN 61347-2-3 EN 60929

Temperature declared thermally protected CE marking Recommended ballast page 2.4

www.philips.com/OEM

Type

HF-Regulator TD 124 TL5/PL-L EII 220-240V HF-Regulator TD 136 PL-L EII 220-240V 50/60Hz

A1Nom
359 425 360

A2Nom
350 415 350

C1Nom
22 22 22

D1Nom
4.2 4.2 4.2

HF-Regulator TD 280 TL5/PL-L EII 220-240V

HF-R PL-L/PL-T/TL5/TL5/PL-L/TL-D

Inrush current
Type Maximum ballast number on MCB (x) HF-Regulator TD 124 TL5/PL-L EII 220-240V HF-Regulator TD 136 PL-L EII 220-240V 50/60Hz HF-Regulator TD 236 PL-L EII 220-240V 50/60Hz HF-Regulator TD 240 PL-L EII 220-240V 50/60Hz HF-Regulator TD 280 TL5/PL-L EII 220-240V 28 28 12 28 9 Inrush current Peak (A) 27 27 45 45 40 Inrush current Width (ms) 0.25 0.30 0.40 0.40 0.15

Electrical data
Type Number of Lamps (x) HF-Regulator TD 124 TL5/PL-L EII 220-240V HF-Regulator TD 136 PL-L EII 220-240V 50/60Hz HF-Regulator TD 140 PL-L EII 220-240V 50/60Hz HF-Regulator TD 155 PL-L EII 220-240V 50/60Hz HF-Regulator TD 180 TL5/PL-L EII 220-240V HF-Regulator TD 224 TL5/PL-L EII 220-240V HF-Regulator TD 236 PL-L EII 220-240V 50/60Hz HF-Regulator TD 240 PL-L EII 220-240V 50/60Hz HF-Regulator TD 255 PL-L EII 220-240V 50/60Hz HF-Regulator TD 280 TL5/PL-L EII 220-240V 1 1 1 1 1 2 2 2 2 2 Rated BallastLamp Power 24 36 40 55 80 24 36 40 55 80 Power losses gear (W) 4.5 5.2 5.6 7 7 7.3 8.7 6.9 11.7 13.2 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 Energy Efficiency Index Cable-Cap outputwires to earth (pF) 75 75 75 75 150 75 75 75 75 150 Cable-Cap outputwires mutual (pF) 100 100 100 100 100 100 100 100 100 100

OEM Catalogue 2008/2009

3.3

CFL-Non Integrated Gear

Vibration & bump tests System supplier: As manufacturer of lamps, electronic control gear and lighting control equipment, Philips ensures that, from the earliest Quality standard development stage, optimum performance is maintained. Environmental standard International standards: Philips HF electronic regulating ballasts Approval marks comply with all relevant international rules and regulations.

EN 60068-2-6-FC EN 60068-2-29-Eb ISO 9001 ISO 14001

HF-REGULATOR II Touch and DALI for PL-L lamps


Electrical data
Type Number of Lamps (x) HF-Regulator TD 324 TL5/PL-L EII 220-240V HF-Regulator TD 424 TL5/PL-L EII 220-240V 3 4 Rated BallastLamp Power 24 24 Power losses gear (W) 11.2 16.4 A1 A1 Energy Efficiency Index Cable-Cap outputwires to earth (pF) 75 75 Cable-Cap outputwires mutual (pF) 100 100

Ordering and packing data


Type HF-Regulator TD 124 TL5/PL-L EII 220-240V HF-Regulator TD 136 PL-L EII 220-240V 50/60Hz HF-Regulator TD 140 PL-L EII 220-240V 50/60Hz HF-Regulator TD 155 PL-L EII 220-240V 50/60Hz HF-Regulator TD 180 TL5/PL-L EII 220-240V HF-Regulator TD 224 TL5/PL-L EII 220-240V HF-Regulator TD 236 PL-L EII 220-240V 50/60Hz HF-Regulator TD 240 PL-L EII 220-240V 50/60Hz HF-Regulator TD 255 PL-L EII 220-240V 50/60Hz HF-Regulator TD 280 TL5/PL-L EII 220-240V HF-Regulator TD 324 TL5/PL-L EII 220-240V HF-Regulator TD 424 TL5/PL-L EII 220-240V 8711500911704 8711500910677 8711500913609 8711500913623 8711500911667 EAN code 1 piece 8711500914460 8711500911643 8711500914507 8711500911681 8711500909657 Weight 0.26 kg 0.26 kg 0.26 kg 0.265 kg 0.285 kg 0.295 kg 0.305 kg 0.295 kg 0.32 kg 0.417 kg 0.37 kg 0.385 kg Qty bulk packing 12 12 12 12 12 12 12 12 12 12 10 10 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 40.8 cm x 20.8 cm x 7.6 cm 47.6 cm x 20.6 cm x 7.6 cm 41.1 cm x 20.6 cm x 7.6 cm 41.1 cm x 20.6 cm x 7.6 cm 8711500911711 8711500910691 8711500913616 8711500913630 8711500911674 Dimensions bulk packing EAN code bulk packing 8711500914477 8711500911650 8711500914514 8711500911698 8711500909664 EOC 8711500 914460 30 911643 30 914507 30 911681 30 909657 30 914521 30 911667 30 914583 30 911704 30 910677 30 913609 30 913623 30

Electrical installation notes Mains operation Rated mains voltage With tolerances for safety +/- 10% Performance tolerance +6%-8% Mains frequency Smart power: with AC mains voltage fluctuations, luminous flux varies by 2% max. Earth leakage current 220 - 240 V 198 - 264 V 202 - 254 V 50/60 Hz 202 - 254 V Ignition time Ignition aid

Note: Ensure that the Neutral is reconnected again after the above mentioned test is carried out and before the installation is put in operation. Typical 0.5 sec. quick warm start. For optimum ignition the PL-L lamps should be mounted at a maximum distance of 12 mm from a metal plate The metal plate should be electrically connected to the ballast housing Earthing of the HF ballast in a luminaire is necessary for EMC (electromagnetic compatibility)

< 0.5 mA per ballast

Maximum number of ballasts which 30 can be connected to one Residual Current Detector of 30 mA Overvoltage protection 48 hrs at 320 V AC 2 hrs at 350 V AC Yes Earthing

Automatic restart after lamp replacement or voltage dip Insulation resistance test

Protected against accidental mains Yes voltage connection DC/Emergency operation DC voltage operation (during emergency back-up) Required battery voltage for 198 - 254 V guaranteed ignition Required battery voltage for burning lamps 176 - 254 V

500 V DC from Line/Neutral to Earth (not between Line and Neutral)

3.4

OEM Catalogue 2008/2009

HF-REGULATOR II Touch and DALI for PL-L lamps

Nominal light output is obtained at 220 - 240 V a voltage of Notes:1. For continuous DC application, an external fuse should be used in the luminaire. 2. Continuous low DC voltages (< 198 V) can influence the lifetime of the ballast.3. For the HF-R TD 280 PL-L EII lamp power will be limited to 50% of the nominal lamp power when operating on DC. Control characteristics Control input Regulating level (lamp power) 1 to 100% The control input complies with EN 60929 (Annex E) and is compatible with Philips lighting control equipment < 350 mW 1500 V

Inrush current
CFL-Non Integrated Gear
3.5

Conversion table for max. quantities of ballasts on other types of Miniature Circuit Breaker MCB type B B C C L, I L, I G, U, II G, U, II K, III K, III Rating 16 A 10 A 16 A 10 A 16 A 10 A 16 A 10 A 16 A 10 A Relative number of ballasts 100% (see table) 63% 170% 104% 108% 65% 212% 127% 254% 154%

Standby power consumption Control input insulation, basic insulation

Notes: 1. Data is based on a mains supply with an impedance of 400 m (equal to 15 m cable of 2.5 mm2and other 20 m to the middle of the power distribution), under worst case conditions. With an impedance of 800 m the number of ballasts can be increased by 10%. 2. Measurements will be verified in real installations; therefore data are subject to change. 3. In some cases the maximum number of ballasts is not determined by the MCB but by the maximum electrical load of the installation. 4. Note that the maximum number of ballasts is given when these are all switched on at the same moment, i.e. by a wall switch. 5. Measurements were carried out on single-pole MCBs. For multipole MCBs it is advisable to reduce the number of ballasts by 20%. 6. The maximum number of ballasts which can be connected to one Residual Current Detector of 30 mA is 30. Mechanical installation notes

Option 1) DALIDigital coded input signal according to Digital Addressable Lighting Interface protocol, including 16 presets and 64 addresses possibility. Option 2) Touch and DimA short push on the button represents the On/Off command.Personal light levels can be stored in the internal memory by a firm longer push on the push button.Failure proof (non volatile) memory ensures that the ballast always remembers your setting when next time switched on or in case of power failure. 32 Pcs Maximum number of ballasts connected in one circuit (switched on by one or multiple switches) Mains input signal Ignore status, < 0.04 sec. Retractive push-to-make switch To avoid reaction on mains

spikes! Short push, between 0.04 sec. and Switch On/Off 0.5 sec. Long push, between 0.5 sec. and 10 sec. Reset push, >10 sec. Dim Up/Down Set light to mid value (35% output) Notes: 1.The dim function will toggle after each individual push. Except when the value is lower than 10% it will always dim up, and when the light output is higher than 70% it will always dim down to perform according human perception. 2. First digital regulating steps (DALI) are fixed at 1% light output (dimming specification).

Technical data for design and mounting in fixtures TemperaturesTemperature range to ignite lamp With ignition aid 1..100% 0 C to +50 C at a 70..100% dim input -20 C to +50 C Storage temperature range -25 C to +80 C Stable lamp operation assured > 15 C* Striation possible < 10 C Max Tcase 75 C * >20 C for HF-R TD 280 TL5/PL-L EII The lifetime of a ballast depends on the temperature of the ballast. This means there is a relation between the Tc point on the ballast and its lifetime. The HF-REGULATORII ballast for PL-L applications has a specified lifetime of 50,000 hrs with a maximum of 10% failuresguaranteed at a measured Tcase of 75 C.For more information regarding this subject consult the Philips Application guide for fluorescent lamp control gear.

OEM Catalogue 2008/2009

HF-REGULATOR II Touch and DALI for PL-L lamps

Class II luminaires

This application is not advisable; only with extensive tests on luminaires can the correct operation be verified EMI precautions have to be taken IP=20 In outdoor the luminaire has to be sufficiently IP rated Permitted humidity is tested according to EN 61347-1 par 11 Note that no moisture or condensation may enter the ballast.

(ALF and ADS) and manual wiring. Wire cross-section: ADS manual connection IDC connection (*) Stranded wire Strip length

0.5..1.0 mm2 0.5..0.75 mm2(*)

Outdoor application

8.0 - 9.0 mm

Hum and noise level

Inaudible

Connector type:Connection wiring is greatly simplified through use of WAGO 251 universal connector. Suitable for both automatic wiring

Wiring tips: Earth connection to be made via housing or mains connector. Wiring inside fixture should be straight and as short as possible. Lamp wires should not run parallel to mains or control wires to avoid EMC problems. For optimal performance, note that: 1. For one lamp ballasts wires 4 and 5 as short as possible, equal in length and a minimum of 50 mm from mains and dim wires. Keep lamp wires 6 and 7, equal in length. 2. For two lamp ballasts wires 3, 4 and 5 as short as possible, equal in length and a minimum of 50 mm from mains and dim wires. Keep lamp wires 6 and 7 and 1 and 2 equal in length.

Digital steps according DALI

250 200

Mains power

System power

150

Total lamp power


100

50 0

Ballast power losses Relative light level Dimming level

Relationship between lamp power and digital regulation

Input power vs dimlevel HF-REGULATOR II (Touch and DALI)

HF-R 1 PL-L/TL5/PL-L

HF-R 2 PL-L/TL5/PL-L

3.6

OEM Catalogue 2008/2009

HF-REGULATOR II Touch and DALI for PL-L lamps

HF-R 424

HF-R 324

OEM Catalogue 2008/2009

3.7

CFL-Non Integrated Gear