Professional Documents
Culture Documents
278558 Rev. A1
Use this publication as a source for complete and accurate information that helps you better operate or service Metso Automation equipment. Your comments and suggestions are welcome. Metso Automation, Inc. 1180 Church Road Lansdale, PA 19446 Attention: Manager, Technical Publications
Copyright 2004 by Metso Automation MAX Controls Inc. Printed in the United States of America All rights reserved
Contents
Preface ...............................................................................................................................................1 Chapter 1 ........................................................................................................................................1-1 Introduction ....................................................................................................................................1-1 maxDNA System Alarm Classes .......................................................................................................... 1-1
Process Alarms......................................................................................................................1-1 System Alarms ......................................................................................................................1-1 Alarm Configuration ..............................................................................................................................1-2 Configuring Alarm Priorities ................................................................................................1-2 Viewing Alarm Messages ......................................................................................................................1-2 Alarm Summary Display........................................................................................................................1-3 Alarm Summary Menu Buttons ............................................................................................1-3 Alarm List Display................................................................................................................1-4 Acknowledging and Silencing Alarms...................................................................................................1-5 Using Keyboard Buttons........................................................................................................................1-5 Acknowledge and Silence.....................................................................................................1-5 Defeat....................................................................................................................................1-5 Restore ..................................................................................................................................1-6 Defeating and Restoring Alarms ............................................................................................................1-6 Using maxVUE Runtime Display Buttons............................................................................................1-6
Chapter 3 ........................................................................................................................................3-1 How to Interpret .............................................................................................................................3-1 System Alarms ...............................................................................................................................3-1 System and Network Alarms ................................................................................................................ 3-1
Logged System Alarms Format ............................................................................................3-2 Troubleshooting System Problems .......................................................................................3-2
maxSTATION Installation
Reference Guide ...........................................................................................................................II -1 Process Alarms .................................................................................................................................... II -1
DPU4E/DPU4F Process Alarms ..........................................................................................................II -2 DPU4E/DPU4F System Alarms...........................................................................................................II -3 WorkStation Alarms.............................................................................................................................II -4 Controller/Datapoint Alarms................................................................................................................II -8
Part III .............................................................................................................................................III-1 Alarm Message.............................................................................................................................III -1 Reference Guide ..........................................................................................................................III -1 System Alarms....................................................................................................................................III -1
Preface
The Alarm Reference Message Guide contains listings of all the process and system related alarm messages you are likely to encounter in the operation of a maxDNA system. Part I of this publication introduces you to all the maxDNA alarm types, alarm-related displays and alarm message formats appearing on displays and on hard copy reports. Part II provides a complete alphabetized listing of all the maxDNA process alarm messages along with text explaining what they mean. Part III provides a similar listing for system alarms. This publication assumes you are familiar with the maxSTATION and the various display environments. For more information about related topics, refer to the following publications: Book Title maxSTATION Operator's Guide 278557 Book Number
Chapter 1
Introduction
maxDNA System Alarm Classes
maxDNA System lets you view two classes of alarms: Process Alarms System Alarms
Process Alarms
Process alarms consist of alarm messages associated with the process itself. These consist of two types: Process Limit Alarms Process limit alarms are caused by values exceeding their assigned limits. Alarm information consists of time, point tagname and its long description, alarm text associated with the alarm, current value of the point, alarm limit value, and the units of measure for the point in alarm. Process Status Alarms Process status alarms are generated by points and programs at DPUs. Alarm information consists of time, point tagname and its long description, alarm type text and the alarm value.
System Alarms
System Alarms consist of alarm messages associated with the system hardware. These consist of two types: Station Diagnostic Alarms Station diagnostic alarms are caused by maxSTATION or Remote Processing Unit (DPU, I/O boards) faults, such as weak batteries, card failures, etc. Alarm information consists of time,
maxSTATION Installation
tagname of the station reporting the alarm, the device reporting the fault, and the alarm text. DPU Bus Network Diagnostic Alarms This relates to two classes of alarms, DPU Bus related and maxNET network related. DPU Bus network diagnostic alarms are caused by cable breaks, token passing errors, failure of stations to respond, etc. maxNET Network alarms are caused by Frame Switch or hub failures, Ethernet card failures, Ethernet cable breaks, or a failed target maxSTATION. Alarm information consists of time, tagname for the DPU Bus reporting the alarm (e.g. DPUBUS1), name of the maxSTATION involved in the fault, and the alarm text.
Alarm Configuration
You may set up alarms and events to be detected when you create configurations using maxTOOLS. The system then automatically detects the alarms and events, processes them, and identifies them for display and acknowledgment, logging, analysis, and optional archiving.
Introduction
Custom graphic displays
maxSTATION Installation
Process diagnostic Process control Display only process diagnostic alarms. Display only process control alarms.
Refer to the following Alarm Filtering Quick Reference Table for a listing of each filtering category that you may select, and the corresponding alarm classes and types that come under this category. These correspond to choices available under the Alarm Type field from the Temporary Filter Settings dialog window in maxVUE Runtime. Table 1-1. Alarm Filtering Quick Reference Table
Filtering Category (from Alarm Type field) Process Diagnostic/Control Process/System Diagnostic System Diagnostic Process Diagnostic Process Control All Alarm Class Alarm Types
Process Limit, Process Status System Diagnostic, Process Limit Alarm, Process Status Alarm Station Diagnostic, Highway Network Diagnostic Process Limit Alarm, Process Status Alarm Process Limit, Process Status Process Limit, Process Status, Station Diagnostic Highway Network
Introduction
Defeat
Defeats all alarms on the currently selected block. When implemented, the block will not alarm until it has been restored. Use of this key may be restricted. On the PC keyboard, the equivalent key is <Ctrl-F4>.
maxSTATION Installation
Restore
Restores all alarms on the currently selected block so that it can alarm again. On the PC keyboard, the equivalent key is <Ctrl-F5>. See next section.
*Ack Top
Introduction
the Alarm List window and the Alarm Summary display. **Silence Vertical Toolbar Silence an audible signal originating in a maxSTATION equipped with a sound board and speakers. The audible signal indicates that an alarm has occurred for a point assigned to a predefined hierarchical group.
* If an audible alarm is equipped, this action will silence the audible alarm.
** The Silence key only silences an audible alarm; the Acknowledge key both silences and acknowledges the top most alarm on the list. maxSTATIONs not equipped with sound boards and speakers may be configured to silence alarms occurring at a maxSTATION playing the sound.
Note: Because <Acknowledge> and <Silence> buttons, and the Alarm List window appear on the standard Vertical and Horizontal Toolbars, you may place these elements on every screen view in the system, if desired. You may select individual alarms on the Alarm Summary display by pointing to an alarm and clicking the left mouse button. In response, the system displays the point tag name at the bottom of the display. Once selected, the point can be acknowledged via the Ack point button. Additionally, the Point Data, Control and Detail buttons will apply to the selected point.
Chapter 2
How to Interpret Process Alarms
A process alarm indicates that some portion of the process has gone beyond its specified limits. When a point goes into alarm, the system adds its tagname to the Alarm List and Alarm Summary displays, and indicates the alarm condition on appropriate point-related pop-up displays. Each of the standard maxDNA functional blocks stored in the DPU database has many alarm states and control conditions built into them, which are set during the configuration process. This permits alarming capability and an interlocking capability with other user-ready and userdefined blocks.
(Refer to online help to reference Alarm/Mode Words associated with each Control Block type.)
maxSTATION Installation
The PID Control Block will display an alarm if any of the input alarm conditions occur. (Refer to the next section.) This control block will also set triggers for individual interlocks upon the following other conditions: Output HI. Output LO. Emergency down state induced by either operator or interlock to other conditions. Receipt of a cascaded forceback signal. Receipt of an external override signal. Placed into manual through a hand station. Placed into manual by operator. Placed into manual by interlock from other control blocks. Placed in automatic by either interlock or operator. Placed into cascade by either interlock or operator. Placed into computer mode by either interlock or operator.
Note: Since AIBs cannot be independently alarmed, they do not appear on any alarm displays. AIBs may be read by Control and Data Blocks; should an AIB reach an alarm state, the Control and Data Block used to monitor the AIB will actually go into an alarm state. To actually look at the AIB alarm condition, you may have to look at the associated Control and Data Block detail display.
maxSTATION Installation
HI alarms, rising/falling, or all alarms. Cutout can be due to process value changes or system hardware conditions. For example, during known disruptive operations (start up or shut down), selective alarms can be temporarily disabled to avoid masking more important real alarms. Yet you will be kept aware of other conditions of that same bypassed point, such as an open thermocouple. These alarm cutouts are independent of the Alarm Defeat/Restore mechanism, and can be triggered either by operator command, by a discrete signal, or induced by a program. Any event, threshold of analog value, lapse of time, condition, state, sequence step (or completion) or command either within or outside of maxDNA can be used to trigger an alarm cutout. A single event or logic result of several conditions or events (boolean expression) can impact the alarm of a single Data Block, or any combination of Blocks. Each Data Block can have its own independent triggering circumstance.
Variable Character Lengths Note: The Limits field does not apply to status alarms.
Displayed process limit alarms and process status alarms are also somewhat different from each other. Process limit alarms report: Time the alarm occurred. Tagname of associated point. Name of point and alarm message text under the Description field. Alarm type. Current value of the point. Alarm limit value. Units of measure for the point. The process status alarms format is similar to the process limit alarms format as outlined above; however, because status alarms are associated with digital type points, the Summary Display Limits field does not apply and is not used. Process alarm messages also appear in a hardcopy version that uses a format somewhat different from the Alarm Summary Display format. Because the printed format can accommodate 133 characters per line, printed text may contain additional information. Refer to the following figure to learn how to recognize logged process alarms:
18
16
16
Process limit alarms report: Date/time Time the process alarm occurred.
maxSTATION Installation
Severity Alarm severity ranging from 0 to 5; the severity number appears in a three-character field surrounded by asterisks: *5* Type When a process alarm is logged, the characters pa appear in this twocharacter wide field. Note: The format for process alarms and edit actions is the same. An Edit Action occurs when an operator takes some action involving a point, such as a mode change or a configuration. When a Edit Action is logged, the characters ea appear. Tagname Tagname of associated point; the tagname is created when you configure a point using maxTOOLS.
Alm/clr When an unacknowledged process alarm is logged, the characters alm appear in this three-character wide field. If the alarm is acknowledged or otherwise clears, the characters clr appear. If the line applies to an edit action, the field is blank. Description Process Alarm message text, such as HiHi LoLo; Range High; and so forth. When this field applies to an edit action, the message text describes an attribute that was edited. Value Limit When this field applies to a process alarm, it reports the current value of the point and the alarm limit value. When this field applies to an edit action, it reports that the limit was changed; the new limit value along with the previous value limit appear in this field. Long Title Long name of point. To troubleshoot process alarms, you may access Point Data, Control, and Detail pop-up displays to learn more about points in alarm and to make quick adjustments to your process. When a process alarm occurs, the alarm message will also appear on these displays.
Chapter 3
How to Interpret System Alarms
System and Network Alarms
System diagnostic status alarms inform you of maxDNA system hardware and software problems. Problems detected within a specific module or station are classified as diagnostic failures. Problems with communications are referred to as highway network alarms. DPU Bus network alarms are further divided between DPU Bus network and maxNET network communications problems. maxVUE Runtime System Status displays show both alarm types. System alarms appear along with process alarms on the Alarm Summary Display and on the Alarm List. The format of displayed system alarms is somewhat different from the format for process alarms; refer to the previous chapter for a description of process alarm formats. System alarms have the following format:
Time HH:MM:SS Date MM:DD:YY Tagname Up to 16 characters Text Subsystem Name Message Text
On the display, the subsystem reporting the fault and the message text appear together under the Description field. The three fields to the right of this field Type, Value, Limit apply to Process alarms. System alarm messages also appear in a hardcopy version that uses a format somewhat different from the Alarm Summary display format. Because the printed format can accommodate 133 characters per line, printed text may contain additional information. Refer to the following figure to learn how to recognize logged system alarms:
maxSTATION Installation
Logged System Alarms Format
date/time Size of field 18 severity 3 type 2 alm/clr 3 tagname 16 description 54
System alarm fields report: Date/time Time the system alarm occurred. Severity Alarm severity ranging from 0 to 5; the severity number appears in a three-character field surrounded by asterisks: *5* Type When a system alarm is logged, the characters sy appear in this twocharacter wide field. Tagname Tagname of associated point; the tagname is created when you configure a point using maxTOOLS. Alm/clr When an unacknowledged system alarm is logged, the characters alm appear in this three-character wide field. If the alarm is acknowledged or otherwise clears, the characters clr appear. Description Alarm message text.
Part II
Alarm Message Reference Guide
Process Alarms
Part II consists of an alphabetic listing of all maxDNA Process Alarm messages. The following pages contain the actual message text (appearing here in all upper case characters), the point or points which can generate the alarm, and a description of what each process alarm message means. Process alarm message text for any given point appears in three versions: 16-character text used in alarm log 12-character text used in Alarm Summary displays 12-character text used in Detail pop-ups All three versions are listed for each process alarm message entry. Note: Points for which an alarm message is applicable include some Control Blocks, which are no longer supported by maxDNA, but were supported by the Models 582 and 585 Operator Stations. Those points are identified using ** in the table.
maxSTATION Installation
DTAG
TMSG is set to TRTXT or FLSTXT based on the value of OUT in the DTAG. A clear alarm occurs when the DTAG output value changes to the non-alarm state.
Alarm Digital Value = (TMSG attribute value)
DTAG
TMSG is set to TRTXT or FLSTXT based on the value of OUT in the DTAG.
Return to Normal
DTAG, ATAG
Return to Normal behavior must be selected in the ALMBEHAVE attribute. A return to normal alarm occurs when the alarm condition of an acknowledged alarm clears.
AlarmRising =ACTUALRATE Lim=LIMRATE ATAG
The DPUTEMP atomic block in a DPU4F can generate a Low, High, LoLo, or HiHi alarm if the DPU temperature exceeds one of the specified limit values.
RangeLoAlarm Lim=LIMRANGELO Value=OUT RangeHiAlarm Lim=LIMRANGEHI Value=OUT ATAG ATAG
Workstation Alarms
Input# is the TC input referenced by the ATAG. nnn is the address of the TC card. This alarm is generated by ATAG but actually occurs due to a break in the wiring for a TC input. Standby DPU has Failed BACKUP
This occurs in DPU4E only and is somewhat misleading. This alarm is generated in the active DPU that has just taken over due to a takeover request or failure of the (previously) active DPU. Primary/Secondary DPU Takeover BACKUP
DPU4F only. This alarm is generated when the inactive DPU changes it state to active due to a takeover or a failure of the (previously) active DPU. Normal Queue Overrun QUEOVRN
The normal time class typically executes every 500 ms in a DPU. If it cannot complete execution of all of the normal time class atomic blocks in the configured time period, this alarm is generated. While this alarm should be very rare, it indicates a fairly serious condition. The DPU is overloaded to the point where it cannot perform control and monitoring functions in a timely manner. Prompt attention should be given to the size of the configuration and to the allocation of atomic blocks to the critical, high and normal time classes. For example, too many critical atomic blocks could impact the performance of the normal time class. NetErr: DPU NetA: CommOk || NetB: CommLost NETALARM
Generated when the A or B network is not usable by the DPU. Usually indicates some physical problem with the network. Can also be a configuration problem. A
maxSTATION Installation
DPU4F set to 10 MB operation when connected to a 100 MB port will generate a NetErr alarm. DPU Battery Problem BATALARM
DPU4E only. Generated when the battery voltage is determined to be too low to sustain DPU operation long enough to write the configuration to flash memory. DPU CPU Fan Problem FANALARM
DPU4E only. The CPU fan has stopped or slowed to the point where it is no longer effective. The fan should be replaced.
WorkStation Alarms
A number of programs in the workstation can produce alarms. The name of the originating program is shown on the right. The text on the left will appear in the Text field on the alarm summary display. All workstation alarms are of type System. [IP address] DPU is Not Responding Healthlog
Healthlog cannot establish communication with the DPU. [IP address] Status: SBP_E_TIMEOUT Healthlog
Healthlog has lost communication with a DPU. ALM DLL COULD NOT READ name RealTimeGateway
The RealTimeGateway alarm dll could not establish communication with a DBM (name). Alarms from this DBM will not be displayed. ALM Primary and Secondary Printer Error LSS
The primary and secondary network printers are not available. Some possibilities are that they could be disconnected, powered down or out of paper. ALM Primary Printer Error LSS
Workstation Alarms
The primary network printer is not available. Data (loggers, reports) should be re-directed to the secondary printer. ALM Secondary Printer Error LSS
The secondary network printer is not available. If the primary printer should fail, the secondary will not be there to takeover. ALM Reports size n MB exceeds limit of m MB LSS
The size of generated report files on the hard disk has exceeded the amount specified in the MCS registry (Max Generated Rpts MB). Generated reports are saved in the c:\Custom\Reports\Generated folder. ALM Archive size n MB exceeds limit of m MB LSS
The size of archived report files on the hard disk has exceeded the amount specified in the MCS registry (Max Archive Megabytes). Archived reports are saved in the c:\Custom\Reports\Archive folder. ALM Event size n MB exceeds limit of m MB LSS
The size of event databases on the hard disk has exceeded the amount specified in the MCS registry (Max Event Megabytes). Event MDBs are saved in the c:\Custom\Database\System\Events folder. ALM Spool size n MB exceeds limit of m MB LSS
The size of the files in the spool folder the hard disk has exceeded the amount specified in the MCS registry (Max Spooling Megabytes). Spool files are saved in the c:\WinNT\System32\Spool\Printers folder. ALM Total size n MB exceeds limit of m MB LSS
The size of the report, event and spool files on the hard disk has exceeded the amount specified in the MCS registry (Max Total Megabytes). COMM: SBP_E_TIMEOUT Operation Timeout The maxMERGEDPUALM program will issue the alarm above if communication is lost with one of its alarm providers (maxDPU). The tagname of this alarm will have the malm suffix.
maxSTATION Installation
Dead Man Timer Timed Out LSS
Only applies to a program that starts up an LSS dead man timer service. That program is responsible for updating the dead man timer. If it does not do so in a timely fashion, the above alarm is generated. Disable Time Sync To DBM RealTimeGateway
maxSTORIAN
This alarm will occur if the disk is full and has not yet been trimmed. Dongle will expire in n days LSS
The parallel port dongle will expire shortly and maxVUE will no longer run. This alarm is associated with test dongles. ILLEGAL ALARM SORT FOR DBM RealTimeGateway
The DBM does not support the Sev/Time sort order. An alarm request for this sort order will cause the RealTimeGateway to issue an alarm. Alarms from the DBM will not be displayed. The maxLINKS program can also generated alarms if it has been configured to do so. It will issue analog and digital alarms as shown below where name is the tagname of a maxLINKS service/point. Name = Val => LimitH = LimVal Name = Val => LimitHH = LimVal Name = Val <= LimitL = LimVal Name = Val <= LimitLL = LimVal Name -> TRUE Name -> FALSE Maximum disk usage level reached ! maxLINKS maxLINKS maxLINKS maxLINKS maxLINKS maxLINKS maxSTORIAN
Old data will be deleted by maxSTORIAN when this alarm is generated. MERGE COULD NOT READ Provider maxMERGEALM
Workstation Alarms
An alarm provider such as maxMERGEDPUALM, LSS, or RealTimeGateway could not be read. Alarms from this provider will not appear on the alarm summary display. MERGE RCV BAD ALARM FROM provider maxMERGEALM
Indicates that unknown data was received from an alarm provider. This is not a serious problem since the alarm data will be retrieved on the next read. However, repeated occurrences of this alarm indicate some workstation problem (possibly low memory?). Net Err: Station Lost Comm with DBM on Net A/B Realtimegateway Generated by the DBMcomm plugin in the RealTimeGateway when communication is lost with a DBM on the A or B network. NetErr: name NetA status maxTransport
Text for this alarm could also indicate net B. name is the workstation name. Status can display: CommLost, CommRegained, CommOk. If the status sticks at CommLost, no communication is occurring on the failed network. POINTS WITH LOWERED PRIORITY maxSTORIAN
maxSTORIAN cannot keep up with all of the data that it is receiving and will shed load. Station: Log In: [IP] RemoteServe
A user has logged in remotely from the listed IP address. Station: Log Out [IP] A remote user has logged out. UNCONNECTED POINTS maxSTORIAN RemoteServe
MaxSTORIAN cannot access one or more points that it was asked to collect. Warning disk usage level reached ! maxSTORIAN
The amount of disk space used by the maxSTORIAN has reached the warning level.
maxSTATION Installation
Controller/Datapoint Alarms
ALM INT'LOCK ALM INRLOCK ALARM INLK
Point(s) which generate this alarm: Reversing Motor Controller (Cntrl Block) Meaning: One of the Interlock inputs configured as an Alarm Interlock has become true. The motor will be turned off. This alarm may cause the algorithm to go to the 'stopping' state.
ALARM INTERLOC ALM INTERLOC ALM INTERLOC
this
alarm:
Binary
Backup
Meaning: Control has been transferred to the secondary DPU of a backup pair.
BACKUP BACKUP BACKUP
this
alarm:
Meaning: This block is now receiving data from the backup DPU of a backup pair,because of a transfer of control in that pair.
BOTH LIMITS BOTH LIMITS BOTH LIMIT
Point(s) which generate this alarm: Valve/Breaker Controller (Control Block) Meaning:
CLOSED
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL. in Binary
Binary Control
Workstation Alarms
COMM FAILED COMM FAILED COMM FAIL
this
alarm:
Point(s) which generate this alarm: Blocks Meaning: into one Block.
DEV HIHI
All Data
Point(s) which generate this alarm: Alarm (Control Block) Meaning: The deviation configured HIHI limit.
DEV LIMIT DEV LIMIT
**Real the
has
DV
exceeded
generate
this
alarm:
PID
Meaning: 'Generic' alarm raised if the PID algorithm has raised a deviation limit alarm but the condition cleared before it was logged.
DEV LOLO DEV LOLO DV HL
Point(s) which generate this alarm: Alarm (Control Block) Meaning: The deviation configured LOLO limit.
DEVIATION DEVIATION
**Real the
has
exceeded
DV
**Data
DEVIATION HI
DEV HIGH
DV
generate
this
alarm:
PID
maxSTATION Installation
Meaning: Deviation between process variable and set point has exceeded the configured high alarm limit.
DEVIATION LO DEV LOW DV
generate
this
alarm:
PID
Meaning: Deviation between process variable and set point has exceeded the configured low alarm limit.
DEV HIGH DEV HIGH DV
**Event
Meaning: Output minus the specified deviation value has exceeded the configured deviation high alarm limit.
DEV LOW DEV LOW DV
this
alarm:
**Event
Meaning: Output minus the specified deviation value has exceeded the configured deviation low alarm limit.
DIGITAL ALRM DIGITAL ALRM ALARM
this
alarm:
All
Digital
Meaning: The output bit of the point has become true and the algorithm is configured to alarm.
DISCREPANCY DISCREPANCY DISCREPANCY
alarm:
Meaning: Either the first control block in a 'chain' of blocks (used to construct sequences with more than 8 steps) is not the same type as the others in the chain; or the control
Workstation Alarms
block attempted to access a step which is higher than allowed based on the number of slots in the chain; or the control block was trying to find the first 'off' step but either could not find it or its number was greater than 255.
DISCREP+TIM DISCREP+TIME DISC + TIME
alarm:
Meaning: A discrepancy alarm has occurred, and the time in a particular step has exceeded the allowed time.
DV HL DV HL DV
**Real
Meaning: 'Generic' alarm raised if the Real Alarm algorithm has raised a deviation limit alarm but the condition cleared before it was logged.
DV RATE DV RATE DV R
**Real
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL. in Binary
Binary Control
maxSTATION Installation
FAILED FAILED FAILED
Backup
Meaning: Control has been transferred to the backup DPU of a backup pair; this control block is no longer in control.
FALLING FALLING FALLING
Analog
Meaning: The output of the Data Block is decreasing at a rate faster than the configured Rate-of-Change limit.
HIGH ALARM HIGH ALARM ALARM HIGH
Point(s) which generate this alarm: Data Blocks, Analog Input Buffers
Analog
Meaning: Input value is greater than or equal to the configured high alarm limit.
HIHI ALARM HIHI ALARM HIHI ALARM
Analog
Meaning: Input value is greater than or equal to the configured high alarm limit.
INP 1 INP 1 INP
Analog
Meaning: Input 1 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 2 INP 2 INP
Analog
Meaning: Input 2 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 3 INP 3 INP
Workstation Alarms
Point(s) which generate this alarm: Control Blocks Analog
Meaning: Input 3 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 4 INP 4 INP
Analog
Meaning: Input 4 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 5 INP 5 INP
Analog
Meaning: Input 5 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 6 INP 6 INP
Analog
Meaning: Input 6 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 7 INP 7 INP
Analog
Meaning: Input 7 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INP 8 INP 8 INP
Analog
Meaning: Input 8 of this block is in alarm; see the input's Detail Popup to observe the exact alarm condition.
INPUT ALARM INPUT ALARM INP
Analog
maxSTATION Installation
Meaning: 'Generic' alarm raised if the control block has raised an input alarm but the condition cleared before it was logged.
I1 LIMIT I1 LIMIT INP
Point(s) which generate this alarm: and 8-Pos Switch Control Blocks
Select
Meaning: 'Generic' alarm indicating that the control block has raised an input alarm for input 1 but the condition cleared before it was logged.
I2 LIMIT I2 LIMIT INP
Point(s) which generate this alarm: and 8-Pos Switch Control Blocks
Select
Meaning: 'Generic' alarm indicating that the control block has raised an input alarm for input 2 but the condition cleared before it was logged.
INSTR HIGH INSTR HIGH INST HIGH
Point(s) which generate this alarm: Data Blocks, Analog Input Buffers
Analog
Meaning: Hardware failure alarm indicating that the input is greater than 5.5V on a 1V-5V input.
INSTR LOW INSTR LOW INST LOW
Point(s) which generate this alarm: Data Blocks, Analog Input Buffers
Analog
Meaning: Hardware failure alarm indicating that the input is less than 0.5V on a 1V-5V input. LEFT LIMIT LEFT LIMIT LEFT LIMIT this alarm:
Meaning: The left limit input has become true while the motor is running in the reverse direction.
LINK FAILED LINK FAILED LINK FAIL
Workstation Alarms
Point(s) Blocks which generate this alarm: Data
Meaning: The DPU has lost communication with the I/O device; for example, if a Receive Data Block can no longer communicate with the other DPU.
LOLO ALARM LOLO ALARM LOLO ALARM
Point(s) Blocks
which
generate
this
alarm:
Data
Meaning: Input value is less than or equal to the configured low low alarm limit.
LOW ALARM LOW ALARM ALARM LOW
Point(s) which generate this alarm: Data Blocks, Analog Input Buffers
Analog
Meaning: Input value is less than or equal to the configured low alarm limit.
NO MINIMUM SPEED NO MIN SPEED NO MIN SPEED
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NO MFWD/MREV NO MF/MR
Binary Control
in
Binary
NO MF/MR
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NON CONGR INPT NON CNG
Binary Control
in
Binary
INPT
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NORMAL NORMAL
Binary Control
in
Binary
NORMAL
which
generate
this
alarm:
Data
maxSTATION Installation
NOT CLOSED
NOT CLOSED
NOT CLOSED
Point(s) which generate this alarm: Valve/Breaker Controller (Control Block) Meaning: The 'closed' feedback input has not gone true within the specified time limit. Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NOT OPEN NOT OPEN
Binary Control
in
Binary
NOT OPEN
Point(s) which generate this alarm: Valve/Breaker Controller (Control Block) Meaning: The 'open' feedback input has not gone true within the specified time limit.
NOT OFF NOT OFF NOT OFF
Reversing
Meaning: Within 2 seconds of the start/stop input going false the motor forward (or motor reverse) input has not gone false; or the run feedback input has not gone false within the configured time limit during the stop sequence. Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NOT OPEN/CLOSED NOT OP/CL
Binary Control
in
Binary
NOT OP/CL
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NOT OPN+CLSD NO OP+CLOSED
Binary Control
in
Binary
NOT OP + CL
Workstation Alarms
Meaning: Both 'open' and 'closed' feedback inputs are false.
NOT READY NOT READY NOT READY
Reversing
Meaning: The 'motor ready' input goes false while the motor is running, or during startup. Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
NOT START NOT START
Binary Control
in
Binary
NOT START
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
OPEN T/C OPEN T/C
Binary Control
in
Binary
OPEN TC
Analog
**Demand
Meaning: Generic alarm indicating that the point has generated either an output > input alarm or an output < input alarm, but the condition cleared before it was logged.
OUTPUT<INPUT OUTPUT < INP DV
**Demand
Meaning: Difference between the input to and the output of the algorithm has exceeded the configured limit value.
OUTPUT>INPUT OUTPUT > INP DV
**Demand
maxSTATION Installation
Meaning: Difference between the input to and the output of the algorithm has exceeded the configured limit value.
POS'N TIMOUT POS'N TMOUT POS TIME
this
alarm:
Meaning: The motor has been started and the maximum positioning time has been exceeded.
POS+BOTH LIM POS+BOTH LMS POS BOTH
this has
alarm: been
Meaning: Maximum position time exceeded and both limits are true.
POS+L LIMIT POS+LEFT LM POS LEFT
this
alarm: been
Meaning: Maximum position time has exceeded and the left limit is true.
POS+R LIMIT
POS+RIGHT LM
POS RIGHT
this
alarm: been
Meaning: Maximum position time has exceeded and the right limit is true.
PV HIGH HIGH PV HIHI PV HL
**Real
Meaning: The process input value has exceeded the configured HIHI limit.
PV LOW LOW PV LOLO PV HL
**Real
Meaning: The process input value has exceeded the configured LOLO limit.
PV HIGH PV HIGH PV
Workstation Alarms
Point(s) which generate this alarm: Control Blocks Analog
Meaning: The process variable input (or input 1) has exceeded the configured PV high limit.
PV HL PV HL PV
**Real
Meaning: Generic alarm indicating that the point has generated a PV high or low alarm, but the condition cleared before it was logged.
PV LOW PV LOW PV
Analog
Meaning: The process variable input (or input 1) is less than the configured PV lo limit.
PV RATE PV RATE PV R
**Real of
Meaning: The process input value rate change has exceeded the configured limit.
PV I1 HIGH PV I1 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I1 is greater than the configured HI alarm value.
PV I1 LOW PV I1 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I1 is less than the configured LO alarm value.
PV I2 HIGH PV I2 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks)
maxSTATION Installation
Meaning: Analog input I2 is greater than the configured HI alarm value.
PV I2 LOW PV I2 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I2 is less than the configured LO alarm value.
PV I3 HIGH PV I3 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I3 is greater than the configured HI alarm value.
PV I3 LOW PV I3 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I3 is less than the configured LO alarm value.
PV I4 HIGH PV I4 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I4 is greater than the configured HI alarm value.
PV I4 LOW PV I4 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I4 is less than the configured LO alarm value.
PV I5 HIGH PV I5 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I5 is greater than the configured HI alarm value.
PV I5 LOW PV I5 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks)
Workstation Alarms
Meaning: Analog input I5 is less than the configured LO alarm value.
PV I6 HIGH PV I6 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I6 is greater than the configured HI alarm value.
PV I6 LOW PV I6 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I6 is less than the configured LO alarm value.
PV I7 HIGH PV I7 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I7 is greater than the configured HI alarm value.
PV I7 LOW PV I7 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I7 is less than the configured LO alarm value.
PV I8 HIGH PV I8 HIGH PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I8 is greater than the configured HI alarm value.
PV I8 LOW PV I8 LOW PV
Point(s) which generate this alarm: Overrides, 8 Pos Switch (Control Blocks) Meaning: Analog input I8 is less than the configured LO alarm value.
PV LIMIT PV LIMIT PV
Analog
maxSTATION Installation
Meaning: 'Generic' alarm indicating that the point has generated a PV limit alarm but the condition cleared before it was logged.
RANGE HIGH RANGE HIGH OVERRANGE
alarm:
Data
Meaning: The input to the data block is greater than the configured range high limit.
RANGE LOW RANGE LOW UNDERRANGE
alarm:
Data
Meaning: The input to the data block is less than the configured range low limit.
RIGHT LIMIT RIGHT LIMIT RIGHT LIMIT
this
alarm:
Meaning: The right limit input has become true while the motor is running in the reverse direction.
RISING RISING RISING
Analog
Meaning: The output of the data block is increasing at a rate faster than the configured Rate-of-Change limit.
RUNBACK RUNBACK DV
this
alarm:
Hard
Meaning: The logic input calling for a runback has become true and the output of the block is being decreased; or the limit associated with the logic input calling for the runback has been exceeded.
RUNDOWN RUNDOWN DV
Demand
Meaning: The logic input calling for a rundown has become true and the output of the
Workstation Alarms
block is being decreased to the limit associated with the logic input calling for the rundown.
RUN'G NO F/R RUN NO MF/MR RUN NO FF
Reversing
Meaning: Either the motor forward input or the motor reverse input goes false while motor is running.
RUNN'G NO RF RUNN NO RF RUN NO RF
Reversing
Meaning: The motor running feedback input goes false while the motor is running.
RUNUP RUNUP DV
Demand
Meaning: The logic input calling for a runup has become true and the output of the block is being increased to the limit associated with the logic input calling for the runup.
SEC'Y FAIL SEC FAIL SEC FAIL
this
alarm:
Meaning: No data being received from the other station; the last value that was received came from the secondary DPU of a backup pair.
SEC'Y NO RDY SEC NOT RDY NOT READY
Backup
Meaning: There is a problem with the secondary DPU of a backup pair, or the backup link is not working; the secondary will not be able to assume control.
SEQ INT'LOCK SEQ INRLOCK SEQ INLK
Reversing
maxSTATION Installation
Meaning: One of the Interlock inputs configured as a Sequence Interlock has become true. The motor will be turned off only if it is not already in the Running Forward or Running Reverse states. This alarm may cause the algorithm to go to the stopping state.
SEQUENC INTERLOC
SEQ INTERLOC
SEQ INTERLOC
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
SETPT CLAMP SETPT CLAMP
Binary Control
in
Binary
SP
generate
this
alarm:
PID
Meaning: 'Generic' alarm indicating that the point has generated a setpoint clamp alarm but the condition cleared before it was logged.
SETPT HI SETPT HI SP
generate
this
alarm:
PID
generate
this
alarm:
PID
this
alarm:
Binary
Point(s) which generate this alarm: Reversing Motor Controller (Cntrl Block)
Workstation Alarms
Meaning: The run feedback input has not gone true within the configured time limit during the starting sequence of the motor.
START NO F/R
ST NO MF/MR
START NO FF
Reversing
Meaning: The motor forward (or motor reverse) input has not gone true within 2 seconds of the start sequence of the motor.
TIME EXCEED TIME EXCEED TIME XCD
alarm:
Meaning: The configured time to move to the next step of the ramp or sequence has been exceeded.
TRIP TRIP TRIP
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL.
UNAVAIL FLD DEV UA FIELD DEV UA
Binary Control
in
Binary
FIELD DEV
Point(s) which generate this alarm: Control (Control Block) Meaning: User-defined Module ExCEL. in Binary
Binary Control
Part III
Alarm Message Reference Guide
System Alarms
Part III consists of an alphabetic listing of all maxDNA System Alarm messages. The following pages contain the actual message text (appearing here in all upper case characters), how the alarm impacts the DPU, the reporting device and a description of what each system alarm message means.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
24-BIT BUS PATH ERROR IN 1ST DATA BASE A CABLE IS BROKEN A STATION WENT DOWN OR CAME UP
DHW HWYn
A test value written to the common database by background diagnostics was found to have been corrupted. At one or more locations on the named highway, there is a cable break; see the System Status display for that highway to see which stations are reporting the break. One of the highway stations has stopped passing token, or has just started passing token again. (name) is the name of the station which could not pass the token to the station which left the highway. Linearization range calculation error. There are more process alarms present than the database is sized to handle. An attempt at subsequent reconstruction is performed, assuming that this might be a transitory problem. A session was allocated, but now the DBM is not responding with alarm list data. This alarm occurs when trying to allocate an alarm session with a DBM. The Real-Time Processor annunciates that the attached Applications Processor has become active.
HWYn (name)
YES
NO
39
IOP RTP
ALM DLL COULD NOT Read DBMName (such vas "DBM1 or "DBM2") ALM DLL COULD NOT START DBMName (such as "DBM1 or "DBM2") SESSION AP BECAME ACTIVE
System Alarms
APPL
APPL
APPL
An Applications Processor has lost communications with a Real-Time Processor on Network A. Real-Time Processors regularly broadcast their status on both control room networks. All Graphics Processors will receive all Real-Time Processor broadcasts, even if the Graphics Processor and Real-Time Processor are in different domains. When a Graphics Processor ceases to receive a broadcasts from a Real-Time Processor on this network, it generates this alarm. This situation may be caused by any number of failures, such as a bad Ethernet card A in the Applications Processor, a bad cable, a bad Ethernet card A in the Real-Time Processor, or a failed Real-Time Processor. The Applications Processor has either lost Control Room Network communications with its current Real-Time Processor or has determined that a different Real-Time Processor in the same domain has a better data highway status. This is a one shot alarm and does not persist. An Applications Processor has lost communications with a Real-Time Processor on Network B. Real-Time Processors regularly broadcast their status on both control room networks. All Graphics Processors will receive all Real-Time Processor broadcasts, even if the Graphics Processor and Real-Time Processor are in different domains. When a Graphics Processor ceases to receive a broadcast from a Real-Time Processor on this network, it generates this alarm. This situation may be caused by any number of failures, such as a bad Ethernet card B in the Applications Processor, a bad cable, a bad Ethernet card B in the Real-Time Processor, or a failed Real-Time Processor.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
QUE
NO NO
NO NO
13 04
QUE QUE
BATTERY #1 WEAK
NO
NO
02
IOP
BATTERY #2 WEAK
NO
NO
03
IOP
BUFFER OVERFLOW
DHWn
BUFFER OVERFLOW
YES
NO
37
DHW
There was a communications error (either a cyclic redundancy check failed, or there was a frame error) in the high-speed backup link between a backup pair of DPUs. The inactive DPU of a backup pair is not keeping up with information coming over the backup link. The active DPU of a pair of backup DPUs is reporting that the inactive DPU didnt respond to a query within the timeout period. Battery #1 weak on DPU motherboard (model 555-2) or battery weak for CMOS on the CPU board (models PSF and PDP). Battery #2 weak on DPU motherboard. (model 555-2) or battery pack weak on motherboard (models PSF and PDP). One of the highway processor's communications buffers is not being emptied by the DBRT in the RTP. Will probably require that the Real-Time Processor be reset. The DPUs highway processors communications buffers are not being emptied by the CP. Will require that the DPU be reset.
System Alarms
GP
GP
A Graphics Processor has lost communication with a Real-Time Processor on Network A. Real-Time Processors regularly broadcast their status on both control room networks. All Graphics Processors will receive all Real-Time Processor broadcasts, even if the Graphics Processor and Real-Time Processor are in different domains. When a Graphics Processor ceases to receive a broadcast from a Real-Time Processor on this network, it generates this alarm.This situation may be caused by any number of failures, such as a bad Ethernet card A in the Graphics Processor, a bad cable, a bad Ethernet card A in the Real-Time Processor, or a failed Real-Time Processor. This alarm will persist until either the problem is resolved or the network database of the failed RTPs domain is purged. Refer to the Graphics Processor Operators Guide, Using the Real-Time Processor Selection Display, Clear Button. A Graphics Processor has lost communication with a Real-Time Processor on Network B. Real-Time Processors regularly broadcast their status on both control room networks. All Graphics Processors will receive all Real-Time Processor broadcasts, even if the Graphics Processor and Real-Time Processor are in different domains. When a Graphics Processor ceases to receive a broadcast from a Real-Time Processor on this network, it generates this alarm. This situation may be caused by any number of failures, such as a bad Ethernet card B in the Graphics Processor, a bad cable, a bad Ethernet card B in the Real-Time Processor, or a failed Real-Time Processor. (continued on next page)
System Alarms
CAN'T COMMUNICATE WITH RTP VIA NETWORK B (continued from prior page)
RTP
RTP
YES
NO
46
DHW
RTP
CONFIGURATION ROLLBACK
RTP
RTP
CONTROLLER OR DPU RELOADING CONTROLLER PROCESS ALARM LOG SUSPENDED COULD NOT OPEN THE EVENT DISK
NO
NO
09
This alarm will persist until either the problem is resolved or the network database of the failed RTPs domain is purged. Refer to the Graphics Processor Operators Guide, Using the Real-Time Processor Selection Display, Clear Button The Real-Time Processor cannot request the use of the SCSI bus in order to communicate with its clients (Applications or Graphics Processors). This is most likely to be a hardware fault such as a lose SCSI connector, a defective cable, etc. One of the Real-Time Processor's clients initiated a SCSI transaction; when the response was ready, the client would not respond. This can be caused by either hardware, software, or a processor which is temporarily 'too busy'. During DPU startup, either the CMOS clock is not running, or the value of the year stored in the clock is before 1995. An overflow occurred in the memory buffer which stores status broadcast messages; thus, some messages have been lost. There was an error during the database installation phase of Install; thus, this Real-Time Processor has rolled back to its previous configuration. The specific problem(s) which caused the rollback are detailed in a log file which is built by the Configuration Builder during Install. During startup, this Real-Time Processor's database called for highway card(s) to be present which are not responding to a startup request. A reload of this DPU is currently underway. Controller process alarm logging has been suspended because of the overflow of the buffer containing the status broadcast messages. There has been a failure of the hard disk partition in
RTP
Metso Automation, Inc. 278558 III-6
System Alarms
PARTITION CPU FAILURE CPU FAILURE CURRENT RTP IS NOT A PREFERRED SELECTION YES NO 48
RTP
DAQD OR IOP DEADMAN TIMER TIMED OUT DATA POINT RECEIVES IN LINKFAIL DEADMAN TIMER NOT REFRESHED DH NEVER RECEIVED CP RESPONSE
YES YES
YES NO
18 25
YES
NO
F0
DHW
RTP
which the events are stored. The highway processor's periodic diagnostic test of its CPU detected a fault. The highway processors periodic diagnostic test of its CPU detected a fault. A Graphics or Applications Processor is currently using a Real-Time Processor as a data server and that Real-Time Processor is not on its preferred server list. This alarm will persist until the station starts using a preferred Real-Time Processor as its current server. The switch to non-preferred server can happen either as a result of failure of all preferred servers, or manual switch via the RTP Selection Display. The time configuration file which has been produced and installed by the Configuration Builder is not correct; thus, this Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder. IOP timed out (periodic tasks not being scheduled). Millisecond interrupts have stopped. Data block receive in Linkfail condition; data is not being received by Data Block. This highway processor is reporting that its own deadman timeout circuitry has not been refreshed. The highway CPU requested data from the CP in order to respond to a highway request; but, after a timeout period, the CP had not responded. There is a fault in the SCSI bus of this WorkStation: a DMA operation was not completed within the required timeout period. The most likely reason for this error is that some Graphics Processors in this WorkStation have the same SCSI ID (look at CONFIG.INI in the \VUE subdirectory to see). There may also be a hardware fault such as a lose SCSI connector, a defective SCSI cable, etc.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
SLOT
RTP RTP
DPU FAILURE: ILLEGAL RETURN THRU 0 DPU FAILURE: SRAM CHECKSUM ERROR
YES YES
YES YES
FE FF
SLOT SLOT
DPU IS OFFLINE
NO
NO
07
IOP
In a DPU backup pair, the Secondary is currently active. After you determine that the Primary DPU is able to take control, you can transfer control back via the pushbutton on that DPU. The event queue of a DPU has been emptied; this event was received from that DPU. The event queue of a DPU has not been emptied fast enough by one or more Real-Time Processors; thus some older events in the queue have been overwritten by newer events, and the older ones will not be collected by those Real-Time Processors. An internal failure has occurred in the DPU; this is a fatal error. There is a checksum error in the static RAM (the RAM which contains the operating system) of this DPU. This is a fatal error (reported by model 555-2 only). The DPU is presently offline, so it is no longer updating any process/control outputs. Check the state of the DPU keylock and Interaction Page 9 to get the DPU back online.
Alarm Text
Type
Reporting Device
Description
SLOT
YES
YES
FD
SLOT
The cooling fan mounted on the CP of the PDP DPU has failed. Replace or repair the fan immediately to avoid overheating. The CP background diagnostics has detected an incorrect checksum in the program logic stored in dynamic RAM (DRAM); the DPU will have to be reset.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
DUPLICATE HIGHWAY STATION NUMBERS DUPLICATE HIGHWAY STATION NUMBERS ECC CORRECTED A ONE-BIT ERROR EVENT BARREL OVERFLOW
DHW DHWn
NO
NO
11
DHW RTP
RTP
EVENT QUEUE DATA LOSS EVENT QUEUE HAS BEEN RESET EVENTS BUFFER NEARLY FULL
YES
NO
E2
APPL
The highway processor received a message in which the highway address of the sender was the same as its address. The highway processor received a message in which the highway address of the sender was the same as its address. ECC logic detected and corrected a single-bit DRAM error (reported by model 555-2 only). The event barrel of a Real-Time Processor has not been emptied fast enough by its client Applications Processor; thus, some older events which had been stored in the barrel will be lost. This alarm indicates a problem occurred when the events subsystem tried to access the hard drive of the Real-Time Processor. If this alarm persists, then there might be a problem with the hard drive. Event Queue overflow; dequeue rate is insufficient. Event Queue reset. The CURRENT volume is not mounted on the optical drive, or the CURRENT volume is full and needs to be closed out and replaced. The Event History buffer has been storing data and is nearly full. Same as above message, but this is a second-level warning for the Event History buffer.
Alarm Text
Type
Reporting Device
Description
APPL PFI
Same as above, but Event History data has now been lost and cannot be recovered. As of the execution of a check command, the ExCEL processor's stack was not empty (the check command tests the state of the stack to permit debug of an ExCEL program which is causing the alarm "User Stack no empty
System Alarms
RTP
Highway Comm
RTP
NO
NO
04
DHW DHWn
at Restart" to be reported by PFI). There is a fault in the SCSI bus of this WorkStation. This can be caused by either hardware, software, or a processor which is temporarily too busy. An IGAP (Initialize Go-Ahead Pointers) was completed on this highway. The Real-Time Processor annunciates that the attached Graphics Processor has become active. The Graphics Processor has either lost Control Room Network communications with its current Real-Time Processor or has determined that a different Real-Time Processor in the same domain has a better data highway status. This is a one shot alarm and does not persist. An HDI card has failed during normal operation. This may be a temporary condition due to this station's being IGAP'd out; if not, then the Real-Time Processor will have to be reset. This highway processor is reporting that the periodic check of its highway address is failing. This highway processor is reporting that the periodic check of its highway address is failing.
Alarm Text
Type
Reporting Device
Description
RTP
This highway processor either stopped refreshing its deadman timer, or it failed to perform the periodic highway query issued by DBRT. Will probably require the Real-Time Processor to be reset.
System Alarms
Activates DPU Offline Contact
NO NO NO
Reporting Device
Description
I/O BUS ACCESS ERROR ILLEGAL ALGORITHM CODE ILLEGAL BUFFER POINTER VALUE
DHWn
YES
NO
17
PFI
YES
YES
E8
QUE
RTP
The DPUs programmed functions interpreter is unable to communicate with one or more modules on the I/O bus. A control block contains an algorithm code which is not part of the standard algorithm set. The highway processor does a periodic check of the buffer pointers of its communication buffers; this alarm indicates that one or more pointers were outside the allowed range. Will require that the DPU be reset. The highway processor does a periodic check of the buffer pointers of its communication buffers; this alarm indicates that one or more pointers were outside the allowed range. Will require the Real-Time Processor to be reset. The application program area of the DPU is either empty because the DPU needs to be reloaded, or there is illegal object code in that program area. The IOM is unable to complete its scheduled processing each millisecond. This condition occurs if either the IOM stops running or if it is configured with too many digital terminal boards (16 in model PSF SFP, 25 in model PDP). This Real-Time Processor could no longer communicate with one of its client Graphics Processors. The RTP's timesync function generates this alarm if each GP does not periodically issue time sync requests. This can be an Ethernet communications problem, or a failure of a Graphics Processor. This is a one-shot alarm and does not persist.
Alarm Text
Type
Reporting Device
Description
RTP
This Real-Time Processor could no longer communicate with its client Applications Processor. The RTP's time
System Alarms
maxSTATION <stationName> LOST COMM WITH DBM <dbm/name> ON NET A Or maxSTATION <stationName> LOST COMM WITH DBM <dbm/name> ON NET B
maxSTATION
MERGE COULD NOT READ Provider MERGE RCV BAD ALARM FROM Provider (_DBM_ALM) MERGE RCV BAD SBP STAT FROM Provider MODEM JABBERHALT RELAY ACTIVATED
YES
NO
31
sync function generates this alarm if the AP does not periodically issue time sync requests. This can be an Ethernet communications problem, or a failure of the Applications Processor. This is a one-shot alarm and does not persist. A maxSTATION has lost communications with a DBM on Network A or B. DBMs regularly broadcast their status on maxNET Networks A and B. All maxSTATIONs will receive all DBM broadcasts, even if the maxSTATION and DBM are in different subsystems. When a maxSTATION ceases to receive a broadcast from a DBM on this network, it generates this alarm. This situation may be caused by any number of failures, such as a bad Ethernet card A or B in the maxSTATION, a bad cable, a bad Ethernet card A or B in the DBM, a failed DBM, or a failed frame switch or network hub. This alarm occurs when trying to connect to an alarm provides (Alarm Summary or LSS). An error status was received from the provider, instead of alarm data. This alarm occurs when connected to a provider, but unable to read alarm data. The highway modem logic deactivated the relays which connect the modem's receiver/transmitter to the data highway. This action will be taken if the highway processor will not cease transmitting.
System Alarms
DHWn
NO CLEAR-TO-SEND AFTER REQUEST-TO-SEND NO CLEAR-TO-SEND AFTER REQUEST-TO-SEND NO TIME CONF DATA FOR CURRENT YEAR
NO
NO
12
Highway Comm
HWYn
APPL
APPL RTP
The highway modem logic deactivated the relays which connect the modem's receiver/transmitter to the data highway. This action will be taken if the highway processor will not cease transmitting. The highway processor wanted to transmit, but its modem would not activate CTS to permit transmission to begin. The highway processor wanted to transmit, but its modem would not activate CTS to permit transmission to begin. The time configuration file which has been produced and installed by the Configuration Builder is not correct; thus, this Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder. This system monitor detected that another station initiated a token pass which was out of sequence. This may be reported if there is a recovery from stallout. A request for either Process History data or Event History data has resulted in a request to mount an unmounted WORM volume. The optical disk which is currently being written to is either full or there are write errors. There is no space left in the outstanding transaction packet pool of memory. This alarm could be indicative of a software operational problem within the Real-Time Processor, but it could also occur as a side-effect of a SCSI communication problem. The Real-Time Processor will probably need to be rebooted.
System Alarms
Activates DPU Offline Contact
CONFIG. DEP.
Reporting Device
Description
IOP
RTP
PRINTER 1 NEEDS ATTENTION PRINTER 2 NEEDS ATTENTION PRINTER 3 NEEDS ATTENTION PRINTER 4 NEEDS ATTENTION PRINTER 5 NEEDS ATTENTION PRINTER 6 NEEDS ATTENTION PRINTER 7 NEEDS ATTENTION PRINTER 8 NEEDS ATTENTION PROCESS HISTORY BUFFER NEARLY FULL
APPL
There is a discrepancy between the parallel I/O module assignments called for in this DPU's configuration and the actual modules which are present. The module address is displayed on Interaction Page 10 with a red background. There is a problem with the point transfer database file which has been produced and installed by the Configuration Builder; thus, this Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder. A printer fault has been detected on the reported printer.
APPL
PROCESS HISTORY DATA LOSS EMINENT PROCESS HISTORY DATA LOST PROCESSOR BOARD LOCAL RAM ERROR PROCESSOR BOARD PROM CHECKSUM ERROR YES YES NO NO 44 45
The CURRENT volume is not mounted on the optical drive, or the CURRENT volume is full and needs to be closed out and replaced. The Process History buffer has been storing data and is nearly full. Same as above message, but this is a second-level warning for the Process History buffer. Same as above, but Process History data has now been lost and cannot be recovered. DPU highway CPU local RAM read/write error found by the on-line diagnostics. PROM checksum error found by on-line diagnostics.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
PROCESSOR EXECUTED ILLEGAL INSTRUCTION PROCESSOR EXECUTED ILLEGAL INSTRUCTION PROCESSOR RESTART - RESET OR RELOAD PROM CHECKSUM FAILURE REAL-TIME CLOCK CHIP ON 1ST DB FAILED RECOVERY FROM STALLOUT ATTEMPTED ON HWY RECOVERY FROM STALLOUT ATTEMPTED ON HWY RESET RTP CANNOT COMMUNICATE ON NETWORK A
DHW DHWn
NO
NO
10
The highway processor executed an instruction reserved for a fault condition. Will require that the DPU be reset. The highway processor executed an instruction reserved for a fault condition. Will probably require the Real-Time Processor be reset. DPU has been reset, or reload has been completed. The highway processor detected an error in its periodic on-line test of the checksum of its software PROM. Either a) the real-time clock hardware has failed; or b) there was an error in the reception of the IRIG-B time sync signal. A highway stallout (no highway activity for 500 microseconds) condition was detected; this station recovered by restarting the token. A highway stallout (no highway activity for 500 microseconds) condition was detected; this station recovered by restarting the token. This station has been reset. The Real-Time Processor failed to successfully initialize the NIC adapter card for Network A on start-up, or it cannot communicate with an Applications Processor on Network A. Communication failures can be caused by any number of failures, such as a bad Ethernet card A in the Real-Time Processor, a bad cable, a bad Ethernet card A in the Applications Processors or a failed Applications Processors.
YES
NO
28
YES
NO
27
DHW
DHWn
(any) RTP
System Alarms
RTP
RTP
RTP
RTP RTP
RTP
The Real-Time Processor failed to successfully initialize the NIC adapter card for Network B on start-up, or it cannot communicate with an Applications Processor on Network B. Communication failures can be caused by any number of failures, such as a bad Ethernet card B in the Real-Time Processor, a bad cable, a bad Ethernet card B in the Applications Processors or a failed Applications Processors. One or more configuration database files, which have been produced and installed by the Configuration Builder, are not correct; thus, this Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder. The trend database files, which have been produced and installed by the Configuration Builder, are not correct; thus, this Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder. Trend scanning was disrupted, usually because of severe highway communication problems. Trend scanning was not completed in its allotted time, usually because the highway token rate is momentarily below the level needed to permit timely completion of all tasks, or because of hardware problems which prevent highway communications. There was an error in the operation of the SCSI bus which runs among the Real-Time Processor and its clients (the Applications and Graphics processors).
System Alarms
RTP
SERIAL I/O COMMUNICATIONS ERROR SERIAL I/O COMMUNICATIONS ERROR SERIAL I/O DATA POINT ERROR SERIAL PORT 1 COMMUNICATION ERROR SERIAL PORT 2 COMMUNICATION ERROR
NO
NO
08
DHW DHWn
YES NO
NO NO
50 12 13
IOP PFI
SLOT #16 PARALLEL I/O MODULE TROUBLE SLOT #nn PARALLEL I/O MODULE TROUBLE SLOT #nn PARALLEL I/O MODULE TROUBLE SOE AND DIGITAL INPUT DATA LOSS
YES
NO
D1 B1-BF C1-D0
SLOT
The Real-Time Processor's database of hardware devices does not match the names and addresses of the SCSI client(s) which are currently connected to that device. The highway serial I/O chip is generating interrupts which, in the CPU's opinion, are garbage. The highway serial I/O chip is generating interrupts which, in the CPU's opinion, are garbage. Data has not been resent within the timeout period. An ExCEL program is communicating to an external device through a serial port. Either the ExCEL program cannot keep up with the incoming data stream, or the ExCEL program is transmitting too fast for the selected port and baud rate. You should check the RTS/CTS and XON/XOFF interlocks, as well as the ExCEL program running state. Any slot which is driving an Output Driver module will report this alarm if the Output Driver reports an output fault. D1 is used for slot 16; B1 to BF are used for slots 1 to 15; C1 to D0 are used for slots 17 to 32.
YES
NO
E0
IOP
YES
NO
38
DHW
Digital input barrel overflow caused by excessive input state change activity. The SOE barrel has 3000 entries, and is emptied at the rate of 5000 entries per second, so the excessive activity would have to continue for an extended period of time. Stack underflow detected in local RAM.
System Alarms
HWYn
HWYn (name)
RTP
STN BECAME ACTIVE FOR THE FIRST TIME STN DIDN'T USE CORRECT LOW LOOP ADDRESS STN IS MASTER WHILE THIS STN IS MASTER STN RCVR PROBLEM / MONITOR MISSED TOKEN
HWYn
The named highway station became inactive; normally reported after an IGAP caused the removal of that device from the system map. A data highway query was made of a station, and that station did not respond, perhaps because it failed. A Graphics or Applications Processor has switched to a new Real-Time Processor server either due to automatic failover or manual request via the RTP Selection Display. This is a one-shot alarm and does not persist. A station on this data highway is not IGAP'd, probably because it was reset after the last IGAP command (a station always comes up unIGAP'd). After an IGAP, a station did not correctly perform the IGAP operation (consisting of trying each address after its own until it finds a station, and then always giving the token to that station). The Real-Time Processor has detected the presence of a SCSI device which is not defined in the RTPs hardware database, or the SCSI device is not configured properly to match the database information. A station on HWYn became active for the first time; it will be added to the highway map maintained by each token monitor. The named station did not use the correct low-loop address when passing the token from the high-traffic loop to the low loop. This station has the token, and therefore is the master at the present moment. This station then detects that another station is attempting to transmit (illegally). A station appeared to have missed the token pass, maybe because this station had a receiver problem and did not hear the token being passed.
System Alarms
HWYn
IOP
NO
NO
13
DHW
DHWn
RTP
RTP
During an IGAP procedure, a station was searching for stations with addresses greater than its own; during that search, that station appeared to have skipped a station. Task overrun counters are non-zero: the CP couldnt keep up with scheduled periodic tasks (control blocks, data blocks, and analog input buffers). When this station had the token, it attempted to pass it on, but it got no response; so, it dropped the token to force a stallout, thus permitting a system monitor to restart token passing. When this station had the token, it attempted to pass it on, but it got no response; so, it dropped the token to force a stallout, thus permitting a system monitor to restart token passing. The time configuration file which describes timezone, standard or daylight savings, etc. was read correctly, but when the file was to be used by this Real-Time Processor, there was an error in the file. This Real-Time Processor will 'roll back' to its previous configuration. See the Install log file which is built by the Configuration Builder. The time configuration file which describes time zone, standard or daylight savings, etc. was not read correctly by this Real-Time Processor. This Real-Time Processor will roll back to its previous configuration. See the Install log file which is built by the Configuration Builder.
Alarm Text
Type
Reporting Device
Description
IOP
This station received a time sync message which was more than 10 seconds different from the current time being
System Alarms
TIME DIFFERS FROM TIME-SYNC-MSG BY 4 SEC TOKEN LOST ON RETURN FROM A LOW LOOP TOKEN NOT RECEIVED FROM HI LOOP Highway Comm YES NO 49
RTP
HWYn
IOP,DHW
TOKEN PASSING PROBLEMS TREND QUEUE HAS BEEN RESET TRH RAN OUT OF QUERY (INPUT) BUFFERS
RTP
RTP
maintained by this station. This station received a time sync message which was more than 4 seconds different from the current time being maintained by this station. When the token was returned from a low-traffic loop to the high-traffic loop, the low-loop station did not use the correct return address. The DPU did not receive the token from the high-traffic loop for more than 1.5 seconds (a DPU is supposed to get the token every 0.5 seconds). A generic message indicating that, on a particular data highway, token passing is not proceeding as it should. The trend queue (which is not currently used) has been reset. There is no space left in the input buffers of the transaction request handler pool of memory. This alarm could be indicative of a software operational problem within the Real-Time Processor, but it could also occur as a side-effect of a SCSI communication problem. The Real-Time Processor will probably need to be rebooted. There is no space left in the output buffers of the transaction request handler pool of memory. This alarm could be indicative of a software operational problem within the Real-Time Processor, but it could also occur as a side-effect of a SCSI communication problem. The Real-Time Processor will probably need to be rebooted. There is no space left in the transaction request packet pool of memory used by the transaction request handler. This alarm could be indicative of a software operational problem within the Real-Time Processor, but it could also occur as a side-effect of a SCSI communication problem. The Real-Time Processor will probably need to be rebooted.
System Alarms
Activates DPU Offline Contact
NO
Reporting Device
Description
UNEXPECTED OR SPURIOUS CTC INTERRUPT UNEXPECTED OR SPURIOUS CTC INTERRUPT UNKNOWN SERIAL I/O FAILURE
NO
NO
07
PFI
The highway processor received an unexpected interrupt from its counter-timer circuit. The highway processor received an unexpected interrupt from its counter-timer circuit. The highway processor has detected a fault in its serial I/O interface circuit; the root cause of the fault cannot be identified by the highway processor. At the restart command, the ExCEL processor's stack was not empty. Check the ExCEL program running in that DPU.
System Alarms