CBT-6P Circuit Breaker Timer Users Manual

TELDAR INSTRUMENTS CO.

CBT-6P Circuit Breaker Timer Users Manual

1. DESCRIPTION A circuit breaker is designed to operate reliability when the need arises. Circuit breaker contact timing is a proven method in checking the synchronism of breaker operation. Operation time tests conducted at the factory, during commissioning and regular intervals are studied and compared to ensure proper breaker performance. Breaker manufacturers usually supply acceptable limits in their manuals, deviations from such should prompt immediate investigation, repair or replacement of the apparatus. The CBT-6P is a stand-alone, microprocessor-based instrument for the time testing of distribution and transmission level circuit breakers. This instrument offers an economical alternative where applications do not require complicated velocity and motion measurements, thus involving cumbersome assembly of motion transducers. The unit has 6 timing channels capable of measuring the operation times of 2 interruptors per phase; each interruptor can consist of a main and a resistor contact in parallel. Five breaker test operations can be performed: Open, Close, Open-Close, Close-Open, Open-CloseOpen. The CBT-6P allows programming of power supply initiate pulse times, while multiple operation can be initiated by programmable time delay or by sensing breakers contact condition. The CBT-6P has a built-in adjustable DC power supply. This allows the user to run a test without having to use station batteries. External triggering is also possible. Minimum voltage coil trip test can also be performed. The panel screen displays the timing trace and the numerical values consisting of open, close, bounce times, delta time and maximum coil current (only for internal DC power supply). Main contact and resistor dead time is displayed for open-close operation, while main contact and resistor live time is displayed for close-open operation. The user can perform point analysis and zoom-in on the trace from the panel controls. The built-in thermal printer allows on-site print-out of both trace and numerical values. Results of test can be saved into the units internal memory and re-called later on.

CBT-6P Circuit Breaker Timer Users Manual

2. SPECIFICATIONS 2.1 Power: 220VAC, 60Hz, 1-phase 2.2 Timing Channels: 6 Inputs 3 Inputs with added insertion resistor measurements

2.3 Timing Window: 1 ~ 1000ms Accuracy: (0.1% of reading 2 digits) Resolution: 0.1ms

2.4 DC Power Supply Output range: 30 ~ 265V, 10A max. Resolution: 1V Accuracy: < 1% Stability: < 1%

2.5 Printer: Thermal printer 2.6 Internal Memory: 40 records 2.7 Dimension & Weight: Unit in box: 43cm L x 38cm W x 30cm H, 14kg. Cables in box: 43cm L x 35cm W x 21cm H, 8kg.

3. FRONT PANEL DESCRIPTION 3.1. Main Power Switch Turns ON / OFF the machine. 3.2. Mains outlet jack fuse protected, connects to a 220 Vac, 60 Hz power supply. 3.3. USB port for software upgrade and diagnostic use only. 3.4. Contrast contrast adjustment for the LCD screen. 3.5. Large Backlit LCD screen displays results and timing trace. 3.6. Printer On-board thermal printer permits on-site printouts of both tabulated results and trace.

CBT-6P Circuit Breaker Timer Users Manual

3.7. Ext. Trigger External voltage trigger inputs from the breaker under test, RED wires connects across the CLOSE coil, GREEN wires connects across the OPEN coil. 3.8. DC power supply: 3.8.1. On-board DC supply provides the necessary voltage trigger to activate the OPEN and CLOSE coils of the breaker, make sure the breaker is primed before each test. 3.8.2. DC power supply is fully adjustable from 30 to 265 Vdc, it outputs a voltage pulse (duration adjustable) to trigger the coils of the breaker, it is NOT a circuit breaker power source. 3.8.3. Set the DC adjust knob at its minimum counterclockwise position after every internal DC supply initiated test. 3.9. DC supply output terminals: 3.9.1. BLACK - connected to one side of both the OPEN and CLOSE coils. 3.9.2. RED - connected to the CLOSE coil. 3.9.3. GREEN - connected to the OPEN coil. 3.10. Timing Input Ports: 6 Channels: o A1 Yellow - Black terminal o B1 Green - Black terminal o C1 Red - Black terminal o A2 Yellow - Black terminal o B2 Green - Black terminal o C2 Red - Black terminal 3 Channels: With insertion resistor measurements o A1 Yellow - Black terminal o B1 Green - Black terminal o C1 Red - Black terminal

* Connect the channels to a set of circuit breaker contacts under test, take note the initial condition of the breaker whether it is in OPEN or CLOSE state, make sure that the breaker is primed properly. 3.11. Printer - Built-in on-board thermal printer, press OPEN button to lift hatch and change thermal paper.

CBT-6P Circuit Breaker Timer Users Manual

4.

MAIN MENU 4.1 TEST Selects the various breaker operation for test: OPEN, CLOSE , CLOSE OPEN, OPEN CLOSE, OPEN CLOSE OPEN. 4.2. SETTINGS Selects the trigger mode, initiate and display options. 4.3. VminTrip- Minimum voltage trip test for OPEN and CLOSE operation. 4.4. TRACE View the contact trace graph of breaker operation. 4.5. PRINT Print the on-screen results. 4.6. SAVE Save record to memory. 4.7. LOAD Retrieve file from memory. 4.8. ChState Checks the state of the 6 timing channels O-for OPEN contact C-for CLOSE contact * At Main Menu, use the left and right arrows to scroll thru the selections, press ENTER to select.

5. SUBMENU 5.1. Settings menu: 5.1.1. Trigger: Int or Ext trigger Internal or External voltage trigger (standard setting) Channel trigger Trigger from a channels change of state. * At trigger submenu press ENTER, use left and right keys to scroll thru selections, press ENTER to confirm, select CANCEL to exit. 5.1.2. Initiate: Internal Power supply initiate settings Open 300ms - Standard voltage trigger pulse duration at 300ms - Adjustable from 1ms to 999ms

CBT-6P Circuit Breaker Timer Users Manual

Close 300ms - Standard voltage trigger pulse duration at 300ms - Adjustable from 1ms to 999ms Close Open A1 - Standard setting of CLOSE operation first then OPEN after channel A1 changes state. - Select from A1 and I (current) Open Close A1 - Standard setting of OPEN operation first then CLOSE after channel A1 changes state. - Select from A1 and I (current) Open 300ms Close-Open A1 - Standard setting of OPEN operation first, then CLOSE operation and finally OPEN after A1 changes state. - Voltage trigger pulse duration adjustable from 1ms to 999ms. - Select from A1 and I (current).

* To change power supply initiate settings, use left and right keys to scroll thru the selections, then press ENTER to highlight parameter, use left and right keys to change values, ENTER to confirm and use left and right keys to scroll thru the other selections, go to OK to return to the submenu. 5.1.3. Display: Additional data on tabulated results display. Imax: Maximum coil current - displays the maximum coil current from internal DC power supply. Resistor Time - displays the insertion resistor time * To select these additional data, use left and right keys to select press ENTER to confirm, go to OK to return to the submenu. 5.1.4. Clock: Date and time stamp * To change values, press ENTER to scroll thru the parameters, use left and right keys to change values, press ENTER to highlight the whole selection, go to OK to return to the submenu.

CBT-6P Circuit Breaker Timer Users Manual

5.2. SAVE menu: 5.2.1. CBT-6Ps onboard memory can store up to 40 Tabulated and trace results. 5.2.2. After a test, press ENTER to go to SAVE submenu, there are 4 pages for 10 tests per page for a total of 40 records. 5.2.3. Users have to decide on which of the memory location to place the saved data. 5.2.4. Use the left and right keys to scroll thru the memory locations, press ENTER to confirm location, the record number will be highlighted, press ENTER again to input the 5 character file name, each character will be highlighted, use left and right keys to scroll thru the letters and numbers, press ENTER for next character, when finished, press ENTER until the whole row is highlighted, use left and right keys to scroll thru the commands. 5.2.5. The SAVE submenu commands are as follows: UP - use to scroll UP the record page. DOWN - use to scroll DOWN the record page. DEL - use to delete a particular record, when highlighted. SAVE - use to save the record plus its filename to the highlighted record number. CANCEL - return to main menu When a particular record number location is highlighted, scroll down to SAVE, press ENTER to save the on-screen tabulated results, trace, time and date stamp. To delete a file, choose the record number, press ENTER to highlight then scroll to DEL command, press ENTER to delete record. Select CANCEL to return to Main Menu.

5.3. LOAD menu: 5.3.1. Press ENTER to go to LOAD submenu, there are 4 pages with locations for 10 tests for each page for a total of 40 records. 5.3.2. Users have to decide on which of the memory location to retrieve the test record.

CBT-6P Circuit Breaker Timer Users Manual

5.3.3. Use the left and right keys to scroll thru the memory locations, press ENTER to confirm location, the record number will be highlighted, use left and right keys to scroll thru the commands. 5.3.4. The LOAD submenu commands are as follows: UP - use to scroll UP the record page. 5.4 PRINT: 5.4.1. Press PRINT to printout the on-screen tabulated results. DOWN - use to scroll DOWN the record page. DEL - use to delete a particular record, when highlighted. LOAD - use to retrieve the record CANCEL - return to main menu When a particular record number location is highlighted, scroll down to LOAD, press ENTER to retrieve the record and post it on-screen. To delete a file, choose the record number, press ENTER to highlight then scroll to DEL command, press ENTER to delete record. Select CANCEL to return to Main Menu.

5.5. TRACE: 5.5.1. With the tabulated results on-screen, select TRACE to view its timing graphs. 5.5.2. The TRACE submenu commands are as follows: Zoom In press ENTER under this selection to zoom in on the graph. Zoom Out press ENTER under this selection to zoom out on the graph. Cursor 1 press ENTER under this selection to bring up the 1st cursor line, use left and right keys to move the line, time t indicates the time line in ms, press ENTER to return to submenu. Cursor 2 press ENTER under this selection to bring up the 2nd cursor line, use left and right keys to move the line, time t indicates the time line in ms, delta t

CBT-6P Circuit Breaker Timer Users Manual

indicates the time difference between cursor line 2 and cursor line 1, press ENTER to return to submenu. PRINT press ENTER to printout on-screen trace results. BACK press ENTER to return to Main Menu.

5.6. VminTrip: 5.6.1. Under VminTrip, the CBT-6P lets users continuously adjust the DC output voltage to the OPEN and CLOSE coils to determine the minimum amount of level for operation. 5.6.2. Adjust for the initial DC voltage value, select Ok, the CBT-6P will output the set voltage to either the OPEN or CLOSE coil. 5.6.3. If the breaker did not operate, set the DC voltage to a higher value, then try again. 5.6.4. If it did operate, the value registered on the LED screen is the minimum voltage trip.

6. CONNECTIONS: 6.1. 6 Timing channels are available for contacts without insertion resistors: A1 Yellow Black terminal B1 Green Black terminal C1 Red Black terminal A2 Yellow Black terminal B2 Green Black terminal C2 Red Black terminal

6.2. 3 Timing channels are available for contacts with insertion resistors: A1 Yellow Black terminal B1 Green Black terminal C1 Red Black terminal

6.3. Connect them across the deenergized breaker contacts. 6.4. Take note of the initial breaker contact state, if it is OPEN or CLOSE, for those without a power supply, hand primed the breaker first.
8

CBT-6P Circuit Breaker Timer Users Manual

6.5. Connections using CBT-6P DC power supply: 6.5.1. Make sure that the coil control section of the breaker is deenergized. 6.5.2. Set the DC adjust knob to the minimum start position. 6.5.3. Connect one side of the RED, GREEN and BLACK wires to the DC Output Int. Trigger Terminals. 6.5.4. Connect the RED and BLACK wires to the CLOSE coil of the breaker. 6.5.5. Connect the GREEN and BLACK wires to the OPEN coil of the breaker. 6.6. Connections using External Trigger Supply: 6.6.1. The CBT-6P uses the coil trigger voltage from the circuit breakers power supply. 6.6.2. Connect the Ext. Trigger plug to the Ext. Trigger terminals. 6.6.3. Connect the two RED wires to the CLOSE coil of the breaker. 6.6.4. Connect the two GREEN wires to the OPEN coil of the breaker.

7. INITIAL SETTINGS: 7.1 At SETTINGS, select TRIGGER, confirm Int or Ext Trigger selection. 7.2 At SETTINGS, select INITIATE, confirm these parameters: Open 300ms Close 300ms Close-Open A1 Open-Close A1 Open 300ms Close-Open A1

7.3. At SETTINGS, select DISPLAY, select additional measurements: Imax: Maximum Coil Current (when using internal DC power supply) Resistor Time (when measuring contacts with insertion resistors, otherwise do not activate)

7.4. Check for the correct time and date.

CBT-6P Circuit Breaker Timer Users Manual

8. TIMING OPERATIONS: 8.1. OPEN Operation (Using On-board DC power supply): 8.1.1. Check the breaker contact connections to the CBT-6P, make sure the breaker is primed and contacts at initial CLOSE position. 8.1.2. Make sure the control section of the breaker coil is deenergized. 8.1.3. Check the connections for DC Output Int. trigger, GREEN and BLACK wires to OPEN coil of breaker. 8.1.4. Turn ON the CBT-6P. 8.1.5. Use the potentiometer to adjust the correct DC coil voltage (always zero start the power supply before each test). 8.1.6. Select TEST, then select OPEN, press OK to start breaker test. 8.1.7. The CBT-6P will automatically outputs the necessary coil voltage to activate the breaker and register its operating times and contact traces. 8.1.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.1.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.1.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory. 8.2. OPEN Operation (Using Ext- trigger): 8.2.1. Check the breaker contact connections to the CBT-6P, make sure the breaker is primed and contacts at initial CLOSE position. 8.2.2. The CBT-6P will use the signal from the breakers OPEN coil to start count. 8.2.3. Check the connections at Ext. trigger terminals, connect the two GREEN wires to the OPEN coil of breaker. 8.2.4. Turn ON the CBT-6P. 8.2.5. Select TEST, then select OPEN, press OK to start breaker test. 8.2.6. The CBT-6P will display the message OPERATE BREAKER NOW !.

10

CBT-6P Circuit Breaker Timer Users Manual

8.2.7. Operate the breaker, the signal from the OPEN coil will trigger the CBT-6Ps timing circuits and register the operating times and contact traces. 8.2.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.2.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.2.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory.

OPEN WAVEFORM

To To: CONTACT OPEN TIME Bo: BOUNCE Ro: RESISTOR OPEN TIME
Bo

Ro

RESULTS: To - Contact OPEN time (ms) Bo - Contact OPEN BOUNCE time (ms) Ro - Insertion Resistor OPEN time (ms), if breaker has insertion resistor contacts. DELTA Time - maximum deviation between OPEN time (ms) Imax - Maximum coil current (A)

11

CBT-6P Circuit Breaker Timer Users Manual

12

CBT-6P Circuit Breaker Timer Users Manual

8.3. CLOSE Operation (Using On-board DC power supply): 8.3.1. Check the breaker contact connections to the CBT-6P, make sure the breaker is primed and contacts at initial OPEN position. Make sure the control section of the breaker coil is deenergized. Check the connections for DC Output Int. trigger, RED and BLACK wires to CLOSE coil of breaker. Turn ON the CBT-6P. Use the potentiometer to adjust the correct DC coil voltage (always zero start the power supply before each test). Select TEST, then select CLOSE, press OK to start breaker test. The CBT-6P will automatically outputs the necessary coil voltage to activate the breaker and registers its operating time and contact trace. Select PRINT to printout the tabulated results via the on-board thermal printer. Select TRACE to view the contact graph, select PRINT to printout the trace.

8.3.2. 8.3.3.

8.3.4. 8.3.5.

8.3.6. 8.3.7.

8.3.8. 8.3.9.

8.3.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory. 8.4. CLOSE Operation (Using Ext- trigger) 8.4.1. Check the breaker contact connections to the CBT-6P, make sure the breaker is primed and contacts at initial OPEN position. 8.4.2. The CBT-6P will use the signal from the breakers CLOSE coil to start count. 8.4.3. Check the connections at Ext. trigger terminals , connect the two RED wires to the CLOSE coil of breaker. 8.4.4. Turn ON the CBT-6P. 8.4.5. Select TEST, then select CLOSE, press OK to start breaker test. 8.4.6. The CBT-6P will display the message OPERATE BREAKER NOW !.

13

CBT-6P Circuit Breaker Timer Users Manual

8.4.7. Operate the breaker, the signal from the CLOSE coil will trigger the CBT-6Ps timing circuits and register the breakers operating times and contact traces. 8.4.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.4.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.4.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory.

CLOSE WAVEFORM

Tc Tc: CONTACT CLOSE TIME Bc: BOUNCE Rc: RESISTOR CLOSE TIME

Bc

Rc

RESULTS: Tc - Contact CLOSE time (ms) Bc - Contact CLOSE BOUNCE time (ms) Rc - Insertion Resistor CLOSE time (ms), if breaker has insertion resistor contacts DELTA Time - maximum deviation between CLOSE time (ms). Imax - Maximum coil current (A)

14

CBT-6P Circuit Breaker Timer Users Manual

15

CBT-6P Circuit Breaker Timer Users Manual

8.5. CLOSE-OPEN Operation (Using On-board DC Power Supply): 8.5.1. Check the breaker contact connections to the CBT-6P, make sure the breaker contacts are at initial OPEN position, primed and can be configured for this CLOSE-OPEN test. 8.5.2. Make sure the control section of the breaker coils are deenergized. 8.5.3. Check the connections for DC Output Int. trigger, RED and BLACK wires to CLOSE coil of breaker, GREEN and BLACK wires to the OPEN coil of breaker. 8.5.4. Turn ON the CBT-6P. 8.5.5. Use the potentiometer to adjust the correct DC coil voltage (always zero start the power supply before each test). 8.5.6. Select TEST, then select CLOSE-OPEN, press OK to start breaker test. 8.5.7. The CBT-6P will automatically outputs the necessary coil voltage to activate the breaker test sequence and register its operating times and contact traces. 8.5.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.5.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.5.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory.

16

CBT-6P Circuit Breaker Timer Users Manual

CLOSE-OPEN WAVEFORM

To Tc TL Tc: CONTACT CLOSE TIME Bc: CONTACT CLOSE BOUNCE Rc: RESISTOR CLOSE TIME To: CONTACT OPEN TIME Bo: CONTACT OPEN BOUNCE Ro: RESISTOR OPEN TIME TL: CONTACT LIVE TIME RL: RESISTOR LIVE TIME

Bc

Bo

Rc Ro

RL

RESULTS: Tc - Contact CLOSE time (ms) Bc - Contact CLOSE BOUNCE time (ms) Rc - Insertion Resistor CLOSE time (ms), if breaker has insertion resistor contacts To - Contact OPEN time (ms) Bo - Contact OPEN BOUNCE time (ms) Ro - Insertion Resistor OPEN time (ms), if breaker has insertion resistor contacts TL- Contact LIVE time (ms) RL - Resistor LIVE time (ms) Delta CLOSE time - maximum deviation between CLOSE time (ms) Delta OPEN time - maximum deviation between OPEN time (ms). Imax - Maximum coil current

17

CBT-6P Circuit Breaker Timer Users Manual

18

CBT-6P Circuit Breaker Timer Users Manual

8.6. OPEN-CLOSE Operation (Using On-board DC Power Supply): 8.6.1. Check the breaker contact connections to the CBT-6P, make sure the breaker contacts are at initial CLOSE position, primed and can be configured for this OPEN-CLOSE test. 8.6.2. Make sure the control section of the breaker coils are deenergized. 8.6.3. Check the connections for DC Output Int. trigger, RED and BLACK wires to CLOSE coil of breaker, GREEN and BLACK wires to the OPEN coil of breaker. 8.6.4. Turn ON the CBT-6P. 8.6.5. Use the potentiometer to adjust the correct DC coil voltage (always zero start the power supply before each test). 8.6.6. Select TEST, then select OPEN-CLOSE , press OK to start breaker test. 8.6.7. The CBT-6P will automatically outputs the necessary coil voltage to activate the breaker test sequence and register its operating times and contact traces. 8.6.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.6.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.6.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory.

19

CBT-6P Circuit Breaker Timer Users Manual

OPEN-CLOSE WAVEFORM

Tc To TD To: CONTACT OPEN TIME Bo: CONTACT OPEN BOUNCE Ro: RESISTOR OPEN TIME Tc: CONTACT CLOSE TIME Bc: CONTACT CLOSE BOUNCE Rc: RESISTOR CLOSE TIME TD: CONTACT DEAD TIME RD: RESISTOR DEAD TIME

Bo

Bc

Ro Rc

RD

RESULTS: To - Contact OPEN time (ms) Bo - Contact OPEN BOUNCE time (ms) Ro - Insertion Resistor OPEN time (ms), if breaker has insertion resistor contacts Tc - Contact CLOSE time (ms) Bc - Contact CLOSE BOUNCE time (ms) Rc - Insertion Resistor CLOSE time (ms), if breaker has insertion resistor contacts TD - Contact DEAD time (ms) RD-Resistor DEAD time (ms) Delta OPEN time - maximum deviation between OPEN time (ms) Delta CLOSE time - maximum deviation between CLOSE time (ms). Imax - Maximum coil current

20

CBT-6P Circuit Breaker Timer Users Manual

21

CBT-6P Circuit Breaker Timer Users Manual

8.7. OPEN-CLOSE-OPEN Operation (Using On-board DC Power Supply): 8.7.1. Check the breaker contact connections to the CBT-6P, make sure the breaker contacts are at initial CLOSE position, primed and can be configured for this OPENCLOSE-OPEN test. 8.7.2. Make sure the control section of the breaker coils are deenergized. 8.7.3. Check the connections for DC Output Int. trigger, RED and BLACK wires to CLOSE coil of breaker, GREEN and BLACK wires to the OPEN coil of breaker. 8.7.4. Turn ON the CBT-6P. 8.7.5. Use the potentiometer to adjust the correct DC coil voltage (always zero start the power supply before each test). 8.7.6. Select TEST, then select OPEN-CLOSE-OPEN , press OK to start breaker test. 8.7.7. The CBT-6P will automatically outputs the necessary coil voltage to activate the breaker test sequence and register its operating times and contact traces. 8.7.8. Select PRINT to printout the tabulated results via the on-board thermal printer. 8.7.9. Select TRACE to view the contact graph, select PRINT to printout the trace. 8.7.10. Select SAVE to download record to memory, select the specific memory cell for which to store the record, select LOAD to upload the record from memory.

22

CBT-6P Circuit Breaker Timer Users Manual

OPEN-CLOSE-OPEN WAVEFORM

To2 Tc To1

Bo1

Bc

Bo2

Ro1 Rc Ro2

To1: CONTACT OPEN#1 TIME Bo1: CONTACT OPEN#1 BOUNCE Ro1: RESISTOR OPEN #1 TIME Tc: CONTACT CLOSE TIME Bc: CONTACT CLOSE BOUNCE Rc: RESISTOR CLOSE TIME To2: CONTACT OPEN#2 TIME Bo2: CONTACT OPEN#2 BOUNCE Ro2: RESISTOR OPEN #2 TIME

23

CBT-6P Circuit Breaker Timer Users Manual

RESULTS: To1 - Contact OPEN #1 time (ms). Bo1 - Contact OPEN #1 BOUNCE time (ms). Ro1 - Insertion Resistor OPEN #1 time (ms). Tc-Contact CLOSE time (ms). Bc - Contact CLOSE BOUNCE time (ms). Rc - Insertion Resistor CLOSE time (ms). To2 - Contact OPEN #2 time (ms). Bo2 - Contact OPEN #2 BOUNCE time (ms). Ro2 - Insertion Resistor OPEN #2 time (ms). Delta OPEN #1 time - maximum deviation between OPEN #1 time (ms). Delta CLOSE time - maximum deviation between CLOSE time (ms). Delta OPEN #2 time - maximum deviation between OPEN #2 time (ms). Imax - Maximum coil current

24

CBT-6P Circuit Breaker Timer Users Manual

25

CBT-6P Circuit Breaker Timer Users Manual

PARTS LIST

Transport case for CBT-6P Transport case for cables DC output supply cable External trigger sense cable 2 sets Red, Yellow, Green sense cables 5 pcs. Black cables 1 pc. Interconnect cable 6 pcs. Shorting cable Mains cable Manuals

26