Description a. b. c. d. e. f. Type of cable Conductor cross section Conductor diameter, mm Conductor material No. of wires, pcs. / cross section of wire, mm2 Longitudinal water sealing system for the conductor 1. Required (Yes, No) 2. Type / description
Annealed copper
Yes
Yes Compacted conductor / compacted factor: more than 95% Compacted conductor / compacted factor: more than 95%
3. Material
g.
Conductor screen 1. Material 2. Nominal thickness, mm 3. Minimum thickness, mm Semi conductive compound Semi conductive compound 0.6 0.5
h.
Insulation 1. Material 2. Nominal thickness, mm 3. Minimum thickness, mm Cross linked polyethylene (XLPE) Cross linked polyethylene (XLPE) 4.5 3.95
i.
Insulation screen
1. Material 2. Nominal thickness, mm 3. Minimum thickness, mm j. Screen bedding 1. Type and material 2. Thickness, mm k. Metallic screen 1. Material
Strippable extruded
Annealed copper tape Remark: the technical data offered is greater than the technical data required 7 Thickness of copper tape: 0.1 mm
Owners Requirements
Offered
Extruded black PE
Extruded black PVC with 90 temperature carrying capability Remark: the technical data offered is greater than the technical data required. 1.41 for PVC with 90 temperature carrying capability 2.6 2.4
2. Density, kg/dm3
0.92~0.93
3. Nominal thickness, mm 4. Min. thickness at any point, mm 5. Termite protection required 6. Type / material of fire protection m. n. Overall diameter of completed cable (nominal), mm Maximum pulling tension, N Yes
When laid inside the cable trench it shall be flame protected in accordance with IEC 60332 3 22
B.1.1.2
Electrical and thermal data for the 15kV power cable a. Rated voltage, kV b. Maximum voltage, kV c. Lightning impulse voltage withstand level, kV 13.8 20 95 34 60 13.8 20 95 34 60
f.
g. Maximum operating temperature, h. Max. continuous current carrying capacity per conductor @ 90 temperature i. Max. conductor short circuit current permissible when short circuit occurs at a conductor temperature of 90
j.
Max. continuous current carrying capacity per conductor when laid in air at an ambient temperature of 40 and conductor temperature of 90 1. One circuit laid in trefoil formation, A 2. Two circuit laid in trefoil formation, A 136 117 90 90 250 160 Not less than 2 hrs. Not less than 2 hrs.
k. i. m. n. o.
Continuous conductor temperature at max. continuous current carrying capacity stated above, Maximum allowable conductor temperature at maximum continuous rating (100% load factor), Maximum conductor temperature under emergency condition, Maximum metallic screen short circuit temperature, Duration at which the cable can be sustained at maximum conductor temperature under emergency situation, hr.