Cooling Coils for Chilled Water for Connection to Circular Ducts

For cooling air with chilled water

Design
Coils with enclosed headers and circular duct connections: QJCD. Available in 7 sizes. Normal air velocity 23.0 m/s. Easy to size using our computerized product selection program called Coils that youll find under the heading: Heating and Cooling Coils, or using the appropriate sizing page in this catalogue.

Features
Conform to AMA Code QFC.1. Designed for air flows up to 780 l/s. Conform to Tightness Class B to Swedish Standard VVS AMA 98 Enclosed headers Adapted to meet Standards for Circular Ducts Simple to install Removable cover panel for cleaning Stainless drip tray with drain. Insulated to prevent condensation.

Coiltech

4644 GB 05.01

We reserve the right to alter specifications.

Ventilation Coils for Ducts

CATALOGUE

Cooling Coils for Chilled Water for Connection to Circular Ducts


Design
The arrangement of the tubes mounted in the coil is staggered for the effective transfer of cooling energy from the circulating medium to the air. The coil casing conforms to the provisions of Tightness Class B to VVS AMA 98 Standard. The casing is equipped with a circular connection that fits against ducts that conform to Swedish Circular Duct Standard SIS 82 72 06.The connection spigot is fitted with a gasket. A removable cover panel is secured to the connection side of the coil for cleaning and inspection. The casing is fitted with condensation insulation with 9 mm thick INSUL cellular rubber and equipped with an interior tray with R1/2 drain connection.

Installation
Clamp ring couplings (not included) are used for connecting the pipes on the liquid side to the pipework. The lower pipe is normally the inlet to facilitate venting. On the air side, the cooler is to be mounted horizontally in the direction of air flow indicated by the arrow label fitted.

Materials and Surface Treatment


The coil consists of copper tubes and aluminium fins. The casing is made of hot galvanized sheet steel with a tray made of stainless steel, 304L. The pipe connections on the water side are made of copper.

Sizing
Use our product selection program called Coils for sizing, or the appropriate sizing page in this catalogue. The program specifies the following data: Air side: Outlet air temperature Output, kW Air velocity Pressure dropl Return temperature Liquid flow Liquid velocity Liquid pressure drop C kW m/s Pa C l/s m/s kPa

Maintenance
Operating and maintenance instructions can be downloaded from our product selection program called Coils or via our website on the Internet.

Water side:

Environment
An Environmental and Building Product Declaration can be downloaded from our product selection program called Coils or via our website on the Internet.

And other material codes, coil data and product code.

Technical data
Sizes: Number of tube rows: Fin pitch: Max. liquid velocity: 100, 125, 160, 200, 250, 315, 400 3 2,5 mm 2,0 m/s

Coiltech

4644 GB 05.01

We reserve the right to alter specifications.

Ventilation Coils for Ducts

CATALOGUE

Cooling Coils for Chilled Water for Connection to Circular Ducts


Design Data
Max. operating temperature: 150 C All coils are pressure tested with dry air under water. They are designed and produced in accordance with the Pressure Equipment Directive 9723 EG (PED).

Dimensions and Weights


Backside

Product Code
Coil Size (aaa) (Circular duct, mm) QJCD-aaa

Drain R1/2

100, 125, 160, 200, 250, 315, 400

Outlet side

Size QJCD -100 -125 -160 -200 -250 -315 -400

D 100 125 160 200 250 315 400

d 10 10 10 22 22 22 22

G 40 40 40 40 40 70 70

Weight kg 4,4 6,8 6,7 9,7 13 16

225 186 140 305 261 215 305 261 215 385 336 290 460 411 365 540 486 420 690 536 425

380 300 380 300 380 300 380 300 380 300 440 300 475 335

27 97 27 97 27 97 27 97 27 97 27 97

39 114 21,4

Coiltech

4644 GB 05.01

We reserve the right to alter specifications.

Ventilation Coils for Ducts

CATALOGUE

Cooling Coils for Chilled Water for Connection to Circular Ducts


Sizing
Use the tables below, which enable the appropriate size of coil to be determined quickly with sufficient accuracy for practical purposes. If your application calls for air volumes other than those specified in the tables, you can interpolate. Get in touch with your nearest Coiltech sales office if you need further assistance. pt pr q qr P ti tu tri tru rh

Symbols
= total pressure drop on the air side . . . . . .Pa = pressure drop on the water side . . . . . .kPa = air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .l/s = water flow . . . . . . . . . . . . . . . . . . . . . . . . . . .l/s = output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .kW = inlet air temperature . . . . . . . . . . . . . . . . . .C = outlet air temperature . . . . . . . . . . . . . . . . .C = inlet water temperature . . . . . . . . . . . . . . .C = outlet water temperature . . . . . . . . . . . . . .C = relative humidity of the air . . . . . . . . . . . . .%
Output P kW 0,28 0,36 0,38 0,49 0,44 0,56 0,53 0,68 0,96 1,29 1,26 1,69 0,82 1,14 1,33 1,79 1,7 2,2 1,19 1,3 2,1 2,9 2,8 3,7 1,87 2,9 3,4 4,6 4,4 5,9 3,4 4,6 5,4 7,3 6,9 9,3 5,2 7,1 8,3 11,1 10,5 13,9 Water flow qr l/s 0,01 0,01 0,02 0,02 0,02 0,02 0,02 0,03 0,04 0,05 0,05 0,07 0,03 0,05 0,05 0,07 0,07 0,09 0,05 0,05 0,09 0,11 0,11 0,15 0,07 0,12 0,14 0,18 0,18 0,23 0,13 0,18 0,22 0,29 0,28 0,37 0,21 0,28 0,33 0,44 0,42 0,55 Pressure drop, water pr kPa 0,4 0,6 0,7 1,2 1 1,6 1,7 2,7 8 13 13 22 6 10 14 24 22 37 2,3 2,8 8 14 13 21 2,3 6 8 14 13 22 5 9 13 22 20 34 5 9 12 20 18 30

Water temperature: 6/12 C Humidity: 50% Size

Airflow ,q l/s 16

Pressure drop, air pt Pa 8 9 27 29 55 59 3,6 3,9 14 15 29 32 9 11 34 38 70 78 7 7 25 28 52 58 7 8 24 27 50 56 8 9 28 31 59 65 10 11 35 39 72 81

QJCD-100

31 47 24

QJCD-125

49 74 40

QJCD-160

81 121 63

QJCD-200

126 189 98

QJCD-250

196 294 156

QJCD-315

312 468 251

QJCD-400

503 754

Inlet air temperature ti C 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28 25 28

Outlet air temperature tu C 13,7 14,8 16,4 17,9 17,9 19,7 11,6 12,3 12,8 13,2 14,1 14,9 12,2 12,3 14,4 15,2 15,8 16,9 13 13,8 14,1 14,8 15,4 16,4 12,9 11,9 13,9 14,5 15,2 16,1 11,7 11,9 14 14,7 15,3 16,4 12,2 12,3 14,5 15,3 15,8 16,9

Coiltech

4644 GB 05.01

We reserve the right to alter specifications.