MODELS

FIRE PUMP ENGINES


JU4H-NL14 JU4H-NL24 JU4H-NL34 JU4H-NLK4 JU4H-NL54 JU6H-NL34 JU6H-NLM4 JU6H-NL54 JU6H-NL74 JU6H-NLR4 JU6H-NL84

NON-LISTED NFPA LIKE - HEAT EXCHANGER ENGINES *GROSS POWER RATINGS BHP/KW
JU4H MODEL NL14 NL24 NL34 NLK4 NL54 JU6H MODEL NL34 NLM4 NL54 NL74 NLR4 NL84 197 220 238 247 264 285 147 197 164 220 178 238 184 247 197 264 213 302 147 164 178 184 197 225 62 88 129 146 160 RATED SPEED 2800 46.5 64 66 91 96 129 109 146 119 160 3000 48 68 96 109 119

* Power rating: a 10% deduction in power must be made to determine the maximum allowable pump load.

SPECIFICATIONS
JU4H MODELS ITEM Number of Cylinders Aspiration Rotation* Weight - kg (lb) Compression Ratio Displacement - L (cu. in.) Engine Type Bore & Stroke - mm (in.) Installation Drawing Wiring Diagram Engine Series D - 525 John Deere 4045 Series 413 (910) 17.6:1 12.5 (766) 4 Stroke Cycle - Inline Construction 127 x 165 (5.00 x 6.50) D - 526 John Deere 6068 Series C07575 (DC Electrical Wiring) CO7651 (AC Heater Wiring) 424 (935) N NL14 NL24 NL34 4 T CounterClockwise (CCW) 750 (1657) 17.0:1 766 (1693) NLK4 NL54 NL34 NLM4 JU6H MODELS NL54 6 TRWA NL74 NLR4 NL84

Abbreviations: CW Clockwise TJWA Turbocharged & Aftercooled TRWA Turbocharged with Raw Water Aftercooling *Rotation viewed from Heat Exchanger / Front of engine CCW Rotation is not available Engine intended for Indoor use or inside weatherproof enclosure only

ENGINE RATINGS BASELINES


Engines are rated at standard SAE conditions of 29.61 in. (7521 mm) Hg barometer and 77F (25C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the testing laboratory (see SAE Standard J 1349). A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m). A deduction of 1 percent from engine horsepower rating as corrected to standard SAE conditions shall be made for diesel engines for every 10F (5.6C) above 77F (25C) ambient temperature.

Note: Engines are not to be used for continuous duty. Engines are to be used only for stationary emergency standby fire pump service. According to NFPA 25 engines are to be tested 30 minutes per week at no pump flow and full pump flow once per year.

GUARANTEED POWER AT ANY SPEED


Although BHP ratings are shown at specific speeds, Clarke engines can be applied at any intermediate speed. To determine the intermediate certified power, make a linear interpolation from the Clarke certified power curve. Contact Clarke or your Pump OEM representative to obtain details. Note: JU6H-NL34/M4/74/R4/84 Engines cannot be used between 2650 and 2750 RPM.

MODELS
FIRE PUMP ENGINES
JU4H-NL14 JU4H-NL24 JU4H-NL34 JU4H-NLK4 JU4H-NL54 JU6H-NL34 JU6H-NLM4 JU6H-NL54 JU6H-NL74 JU6H-NLR4 JU6H-NL84

ENGINE EQUIPMENT
EQUIPMENT Air Cleaner Alternator Exhaust Protection* Coupling STANDARD
Direct Mounted, Washable, Indoor Service 12V-DC, 42 Amps; w/Belt Guard

OPTIONAL
Direct Mounted, Washable, Indoor Service with drip guard 24V-DC, 40 Amps; w/Belt Guard Blankets on JU4H-NL14/24, Metal Guards on Manifolds & Turbo on JU4H-NL34/K4/54; JU6H-NL34/M4/54/74/R4/84 Falk Coupling, Engine Half on JU4H-NL14/24/34/K4/54, JU6H-NL34 - 1070T10; JU6H-NLM4/54/74/R4/84 - 1080T10 Drive Shaft & Guard JU4H-NL14/24 - SC41A; JU4H-NL34/K4/54 - SC55A; JU6H-NL34/M4/54 - SC55L; JU6H-NL74/R4/84 - SC61L SS Flex, NPT

Bare Flywheel

Exhaust Flex Connection Flywheel Housing Flywheel Power Take Off Fuel Connections* Fuel Filter Fuel Injection System Engine Heater* Governor, Speed Heat Exchanger Instrument Panel Junction Box Lube Oil Cooler Lube Oil Filter Lube Oil Pump Manual Start Controls Overspeed Control Raw Water Solenoid Operation Run-Stop Control Run Solenoid Silencer Starters Throttle Control Water Pump
*Required to Meet NFPA-20

SS Flex, Clamped S.A.E. #3 11.5 S.A.E. Industrial Flywheel Connection Primary Filter w/Priming Pump Stanadyne Direct Injection

Fire Resistant Flexible Supply & Return Lines

240V-AC, 1500 Watt, 120V-AC, 1500 Watt Constant Speed, Mechanical Tube & Shell Type, 14 Bar (206 psi) w/BSP Connections English & Metric, Tachometer, Hourmeter, Water Temperature, Oil Pressure & Two (2) Voltmeters Integral with Instrument Panel; For DC Wiring Interconnection to Engine Controller Engine Water Cooled, Plate Type Full Flow w/By-Pass Valve Gear Driven, Gear Type On Instrument Panel Electronic w/Reset & Test on Instrument Panel Automatic from Engine Con-troller & from Emergency Local Control On Instrument Panel With Control Position Warning Light Manual Stop Lever 12V-DC Energized to Run 24V-DC Energized to Run, 12V-DC Energized to Stop 24V-DC Energized to Stop Optional Two (2) 24V-DC

Two (2) 12V-DC Adjustable Speed Control, Tamper Proof Poly-Vee Belt Drive w/Guard

MODEL NOMENCLATURE: (8 Digit Models)


J ohn Deere Base Engine 250 Series 6 Cylinders Heat Exchanger Cooled JU6H-NL34 Power Curve Number Not Listed

UK, Ltd. Grange Works, Lomond Rd., Coatbridge, ML5-2NN United Kingdom Tel +44-1236-429946 Fax +44-1236-427274 www.clarkefire.com

Fire Protection Products, Inc. 3133 E. Kemper Rd., Cincinnati, Ohio 45241 United States of America Tel +1-513-771-2200 Fax +1-513-771-0726 www.clarkefire.com

C131176 4/09

Specifications and information contained in this brochure subject to change without notice.

Printed in U.S.A.