1KHW001489-EN
6.6.3.4.5.
Fig. 6-25
Caution
Connecting a load between terminals NO (normally open) and NC (normally closed) is not allowed. Use only one contact set NO or NC. Power supplies connected to alarm relay contacts must be short circuit and over current protected.
Caution
July 2008
6-29
1KHW001489-EN
ETL600
6.6.3.5.
Eight relays with switchover contact are provided. Each relay or alarm contact can be switched to any one of three user alarms. Each user alarm bus can be programmed with HMI600 to respond to a desired combination of alarm criteria. All alarm relays in the ETL600 equipment are picked up during a no fault condition. This is indicated with a dashed line on the alarm contact. Example: Terminals 1 and 2 of V9MR are closed when no alarm is present. Terminals 2 and 3 are closed when an alarm is present. Terminals 2 and 3 are also closed when the power to the ETL600 is switched off.
Caution
Connecting a load between terminals NO (normally open) and NC (normally closed) is not allowed. Use only one contact set NO or NC. Power supplies connected to alarm relay contacts must be short circuit and over current protected.
Caution
6-30
July 2008
ETL600
1KHW001489-EN
Fig. 6-26
July 2008
6-31
1KHW001489-EN
ETL600
6.6.3.6.
The remote inquiry kit R7AP allows to connect RS-232 ports to an RS485 station bus, for element management networking as described in Chapter 4 'User Interface Program'. While ETL600 has its RS-485 bus signals available at the HMI connector on the front plate of P4LT, ETL500 requires R7AP for conversion of RS-232 to RS-485 interface signals. The R7AP base plate can be mounted in a standard 19 inch frame. If used for ETL500, the plate is mounted directly below the channel rack P7LC, and the special 9 pole serial cable V9KH included in the kit has to be inserted between ports COM1 of P4LQ and COM N located on the front plate of the remote inquiry kit. The RS-485 bus is formed by connecting all TD(A) wires, all TD(B) wires and all GND wires at the KRONE connection strip of all R7AP in a substation together. To minimize reflections, a linear network structure should be formed instead of a star structure as shown in Fig. 6-27.
ETL600
ETL500 R3
ETL600
PC with HMI600
ETL600
ETL500 R3
ETL600
PC with HMI600
Fig. 6-27
HMI
RXD TXD DTR GND DSR RTS 2 3 4 5 6 7 8 GND
V9KH
3 2 6 5 4 8 7 TXD RXD DSR GND DTR CTS RTS
RS485
CTS
TD(A)
TD(B)
GND
GND
+12V
GND
WH
BU
TQ
VT
X..
.1a
.1b
.2a
.2b
Fig. 6-28
6-32
July 2008
ETL600
1KHW001489-EN
6.6.4.
Interconnection of interfaces
Table 6-2 shows cables and patch panels for interconnection of V.11, G.703.1, RS-485 or IRIG-B interfaces.
Interface V.11 Type V9OX Device Transit cable Sub-D 15 male to Sub-D 15 male Patch panel Sub-D 9 pole male Patch panel 3 x RJ-45 Interconnection cable to be used at patch panel terminals -
V9OY V9OZ
Shielded twisted pair (STP) cable 120 Ohm, ABB identity number 1KHW001554R0001, (2 pairs, stranded 0.22 mm2)
Table 6-2
July 2008
6-33
1KHW001489-EN
ETL600
6.6.4.1.
Fig. 6-29
6-34
July 2008
ETL600
1KHW001489-EN
6.6.4.2.
Fig. 6-30
6.6.4.3.
Fig. 6-31
July 2008
6-35
ETL600
1KHW001489-EN
7.
7.1.
COMMISSIONING
Safety instructions Personnel qualification
DANGER
An authorized and properly trained personnel only is admitted to carry out installing, programming, commissioning, maintenance, troubleshooting and work of the equipment.
Mechanical Installation
DANGER
DANGER
Cabinets, which are not secured to the floor, tip forwards when the hinged frame is opened. Do not open the hinged frame without precautions.
DANGER
Do not work on the system or connect or disconnect cables during periods of lightning activities.
Neither removing nor inserting of modules is permitted during power-up of the equipment. Preceding to plug in and out of modules the power supply of the equipment has to be switched OFF. An exception to this is the Rx filter P4RX, which has to be removed and inserted while the equipment remains powered when performing the Rx level adjustment procedure.
Unused slots
DANGER
Unused slots in the equipment subracks must be covered with blanking plates.
Commissioning
July 2008
7-1
1KHW001489-EN
ETL600
Back cover
DANGER
Hazardous voltages and/or hazardous energy level behind the back cover. Before removing the back cover, the isolating terminals of the external cables must be opened or the cables to the terminals must be disconnected.
PCB Extenders
DANGER
For measuring purposes only the original PCB extenders P4LM, P3LL and I9BK designed to work with ETL600 equipment, must be used.
The modules in this equipment contain devices, which can be damaged by electrostatic discharges. Appropriate measures must be taken before unpacking modules or withdrawing them from equipment racks. Essential precautions to prevent ESD damage when handling or working on modules are grounding straps for technical personnel and the provision of anti-static workbenches. Modules may only be shipped either in their original packing or installed in equipment racks.
The link gets disturbed while using the options 'Tuning and Testing', activating a testtone, simulating alarms, measurement of frequency response & equalization etc. of the HMI600. Appropriate measures have to be taken especially in case protection signal transmission is being used.
B5LC
DANGER
Make sure that the power supply B5LC is programmed to the correct voltage of 230 VAC or 115 VAC as described in 1KHL015788 before connecting the equipment to the power source.
P1LA
DANGER
Hazardous voltages and/or hazardous energy level on the module and the cable. Do not touch during operation.
7-2
July 2008
Commissioning
ETL600
1KHW001489-EN
DANGER
Heat sink should not be touched with conducting materials to avoid energy discharges and damage of the power amplifier. Hot surface at heat sink.
P4LT/P4LU
DANGER
Hazardous voltages and/or hazardous energy level on the module and the cable. Do not touch the module and the cable leads.
R1BC
DANGER
Hazardous voltages and/or hazardous energy level on the module and the cable. Do not touch the module and the cable leads
O4LE, O4CV
DANGER
The phone interfaces on the modules O4LE and O4CV generate dangerous voltages up to 100 V. Dont use the modules without upper and lower cover plates. Do not touch the open pins of the service phone connector, the leads of its cable, the pins of the external cable connector and the leads of the external cable.
G4AI
DANGER
Hazardous voltages and/or hazardous energy level on the module and the cable. Do not touch the module and the cable leads.
Commissioning
July 2008
7-3
1KHW001489-EN
ETL600
7.2.
It is essential that the behavior and characteristics of the line of communication between the sets of PLC terminal equipment be checked prior to finally commissioning. This is necessary to confirm the design criteria used for engineering the system, respectively if the criteria were inaccurate, to take the appropriate corrective action. The line of communication comprises: a) the coaxial cable linking the PLC equipment with the coupling device. b) the coupling device between the remote end of the coaxial cable and the LV side of the coupling capacitor. The coupling device includes the main coupling filter and protective devices. c) the line traps in the power line between the junction of the coupling capacitor with the power line and the substation. d) the HV power line itself as propagation medium.
7.2.1. Return loss
The return loss is a measure of the quality of impedance matching between the PLC transmitter and the load (input impedance of the coaxial cable). It is defined by the following equation:
Ar Z0 Z 20 log Z0 Z Z0 Z
A low value signifies a poor match, which results in a reduced transfer of power from the PLC transmitter onto the transmission line. The main disadvantage, however is the intermodulation phenomenon and associated cross-talk it causes. The level of return loss should be measured in the equipment room at the coaxial cable input. The instruments used and the test set-up can be seen from Fig. 7-1 and Fig. 7-2. A typical return loss characteristic is shown in Fig. 7-3. In the case of short lines (line attenuation < 15 dB), the remote end must be terminated at rated impedance. The measurement of the return loss over the total bandwidth of the coupling filter and the PLC line traps is recommended. Wherever possible, the measurements should be carried out twice under the following conditions: HV transmission line grounded behind the line trap HV transmission line open behind the line trap If the minimum return loss is in the range 6 to 12 dB, the value of the input impedance should also be measured. In cases where the magnitude of the system impedance is too low or too high, an
7-4 July 2008 Commissioning