You are on page 1of 7

2005 IEEE/PES Transmission and Distribution

Conference & Exhibition: Asia and Pacific


Dalian, China
1

Benefits of FACTS for Power System


Enhancement
L. Kirschner, D. Retzmann, G. Thumm
Siemens AG, Germany

Abstract— The performance of power systems decreases with Fixed Series Compensation (FSC) is widely used to
the size, the loading and the complexity of the networks. This is improve the stability and to increase the transmission capacity
related to problems with load flow, power oscillations and in long distance transmissions. A huge number of these
voltage quality. Such problems are even deepened by the applications is in operation. If system conditions are more
changing situations resulting from deregulation of the electrical complex, Thyristor Controlled Series Compensation (TCSC)
power markets. The power systems have not been designed for is used. TCSC has already been applied in different projects
wide-area power trading with daily varying load patterns where for load-flow control, stability improvement and to damp
power flows do no more follow the initial planning criteria of the
existing network configuration. Large blackouts in America and
oscillations in interconnected systems. Special FACTS
Europe confirmed clearly, that the favorable close electrical devices are UPFC (Unified Power Flow Controller [3]) and
coupling might also include risk of uncontrollable cascading GPFC (Grid Power Flow Controller [8]). UPFC combines a
effects in large and heavily loaded interconnected systems. shunt connected STATCOM with a series connected
FACTS (Flexible AC Transmission Systems), however, STATCOM (=S3C, Solid State Series Compensator) which
provide the necessary features to avoid technical problems in the can exchange energy via a coupling capacitor. GPFC is a
power systems and they increase the transmission efficiency. special DC back-to-back link, which is designed for power
and fast voltage control at both terminals. In this way, GPFC
Index Terms—Blackout, FACTS, FSC, HVDC, Increase of is a “FACTS Back-to-Back”, which is less complex than the
Transmission Capacity, Parallel Operation of FACTS and
UPFC at lower costs.
HVDC, Short-Circuit Current Limitation, Stability
Improvement, SVC, System Interconnection, TCSC For most applications in AC transmission systems and for
network interconnections, SVC, FSC, TCSC and GPFC/B2B
I. FACTS TECHNOLOGIES - OVERVIEW are fully sufficient to match the essential requirements of the
grid. STATCOM and UPFC are tailored solutions for special

F ACTS, based on power electronics, have been developed


to improve the performance of long distance AC
transmission. Later, the technology has been extended to the
needs.
FACTS devices consist of power electronic components
and conventional equipment which can be combined in
devices which can also control power flow. Excellent different configurations. It is therefore relatively easy to
operating experiences are available worldwide and the develop new devices to meat extended system requirements.
technology became mature and reliable. FACTS is applicable Such recent developments are the TPSC (Thyristor Protected
in parallel connection or in series or in a combination of both. Series Compensation, [5]) and the Short-Circuit Current
The rating of shunt connected FACTS controllers is up to 800 Limiter (SCCL, [4]), both innovative solutions using high
MVar, series FACTS devices are implemented on high power thyristor technology [1].
voltage levels up to 765 kV. They can increase the line
z SVC - Static Var Compensator (Standard for Parallel Compensation)
transmission capacity up to several GW.
Fig. 1 shows the principal configurations of FACTS devices z STATCOM - Static Synchronous Compensator
(Fast SVC, Flicker Compensation)
[1, 3]. Main shunt connected FACTS application is the Static
Var Compensator (SVC) with line-commutated thyristor z FSC - Fixed Series Compensation
technology. A further development is STATCOM using z TCSC - Thyristor Controlled Series Compensation
voltage sourced converters. Both devices provide fast voltage z GPFC - Grid Power Flow Controller (FACTS-B2B)
control, reactive power control and power oscillation damping z UPFC - Unified Power Flow Controller
features. As an option, SVC can control unbalanced system
voltages. There are hundreds of SVCs in operation world- SVC/STATCOM FSC GPFC/UPFC
wide. Since decades, it is a well developed technology and the
demand on SVC is increasing further [1]. AC AC AC AC AC AC

L. Kirschner, D. Retzmann, G. Thumm are with Siemens AG, PTD High


Voltage Division, Power Transmission Solutions, 91050 Erlangen, Germany
TCSC/TPSC
(e-mail: lutz.kirschner@siemens.com; dietmar.retzmann@siemens.com;
gerhard.thumm@siemens.com) Fig. 1. Basic Configurations of FACTS Devices

0-7803-9114-4/05/$20.00 ©2005 IEEE. 1


2

In the following sections, solutions for system 400 kV became the highest voltage level, in Far-East countries
enhancement, for Blackout prevention and for system mostly 550 kV, and in America 550 kV and 765 kV. The 1150
interconnection are presented and their advantages are kV voltage level has been anticipated in the past in some
explained. Examples of large project applications in Asia, countries and also some test lines have already been built. In
America and Europe are depicted, including hybrid China for example, AC voltages of 1000 kV are actually
configurations with parallel operation of FACTS and HVDC. under discussion with regard to very long transmission
distances between generation and load centers and for
II. TRENDS IN POWER SYSTEMS supplying strong AC links between the different systems of

T HE development of electric power supply began more


than one hundred years ago. Residential areas and
neighboring establishments were supplied first by DC via
the country. However, it is not expected in the near future that
AC voltage levels above 800 kV will be utilized to a larger
extent.
short lines. At the end of the 19th century, however, AC
transmission has been introduced utilizing higher voltages to
transmit power from “remote” power stations to the Extensions of Interconnected Systems
consumers.
Increased Power Exchange among the
Globalisation/ Deregulation - Privatization: Opening of the
Privatisation
Liberalisation markets, Independent Transmission Companies Interconnected Systems
ITCs, Regional Transmission Organisations RTOs

Transmission of large Power Blocks over long


Problem of uncontrolled Loop Flows
Distances * (Hydro Resources, Solar Energy)
Bottlenecks in
Privatisation
Transmission Overloading & Excess of SCC Levels
System Instabilities & Outages
Renewable Energy Resources at favorable
Locations *
System Enhancement & Interconnections:
Investments in Š Higher Voltage Levels *
**by
byuse
useof
ofHVDC
HVDC/ /FACTS
FACTSfor
for“remote”
“remote” Infeed
Infeed
Privatisation
Power Systems Š New Transmission Technologies
Š Renewable Energies Fig. 3. Trends in Power System Development
*Example
*ExampleUCTE:
UCTE:400
400kV
kVisisactually
actuallytoo
toolow
low
4 x GIL, 4 x SVC, 2 x HVDC GIL in Tunnel
Fig. 2. Power Market Development – Problems and Solutions to avoid 40-50
Cables nearby
The growth and extension of AC systems and consequently the Coasts
the introduction of higher voltage levels have been driven by a
fast increase of power demand over decades. Power systems
have been extended by applying interconnections to the
neighboring systems to achieve technical and economical
advantages. Regional systems have been built-up towards
national grids and later to interconnected systems with the
neighboring countries. Large systems came into existence,
covering parts of or even whole continents, to gain the well
known advantages, e.g. an ability to use larger and more AC or DC
economical power plants, reduction of reserve capacity in the Cables
systems, utilization of the most efficient energy resources, and
to achieve an increase in system reliability. Global studies
show that power consumption in the world follows closely the Medium-term
increase of population. In the next 20 years, power Long-term: 30 - 50 GW Planning
consumption in developing and emerging countries is
expected to increase for 220%, in industrialized countries, Fig. 4. Embedding of large Off-Shore Wind-Farms in the North Sea – DENA
however, only for 37% [2]. Study 02-24-2005 (Germany)
In future, in the course of deregulation and privatization, Additional problems are expected when renewable
the loading of existing power systems will strongly increase,
energies, such as large wind farms, have to be integrated into
leading to bottlenecks and reliability problems. System
the system, especially when the connecting AC links are weak
enhancements will be essential, to balance the load flow and
in total to get more power out of the existing grid. In Fig. 2, and when there is no sufficient reserve capacity in the
the problems and solutions of the market developments are neighboring system available. Fig. 4 shows a solution, which
depicted and Fig. 3 summarizes the trends of power system is actually under discussion for embedding of very large
developments. amounts of wind energy in Germany (status 2003: in total 12
One of the possible solution for power system enhancement GW, in future 30-50 GW) to be delivered from planned off-
is to increase the transmission voltage level. In West Europe, shore wind farms in North and Baltic Sea regions, were the

2
3

neighboring grids are too weak for such a large additional III. LARGE BLACKOUTS 2003
power infeed. By means of two HVDCs in combination with
four SVCs, the energy can be “bundled” and then transported A. Probability of Blackouts
point to point to the load centers in the middle of the country. Fig. 7 shows, that the probability of large Blackouts is
The off-shore connection to the main grid will be done by much higher than calculated with mathematical modeling,
high power GIL (Gas Insulated Lines), in order to avoid huge especially when the related amount of power outage is very
numbers of cables nearby the coasts, as it is indicated in the large [2].
figure. The benefits of this “remote infeed solution” are:
• load sharing and
• generation reserve sharing
Both are essential for the safe and reliable operation of the
power system.
If power should be transmitted through the interconnected
system over longer distances, transmission needs to be
supported. Actual
Expected
This is for example the case in the West-European UCTE Source:

system (Fig. 5), where the 400 kV voltage level is actually too
low for large cross-border and inter-area power exchange.
Bottlenecks are already identified (NTC - Net Transfer Fig. 7. Reasons for high Probability of Blackouts
Capacity, Fig. 6), and for an increase of power transfer,
advanced solutions need to be applied. The reasons for this result are indicated in the figure. This
means, that, when once the cascading sequence is started, it is
… Zone 1 & 2 “resynchronized” since 10.10. 2004 mostly difficult or even impossible to stop it, unless that the
direct causes are eliminated, ref. to the figure.
NORDEL
B. The Events in North-America
Options for Grid The Blackout sequence started on august 14, 2003, around
Interconnection noon [2]. Reactive power and voltage problems have been
IPS/UPS reported, but no major ones.
Giant Loop Flows
2.2 - 4.8 GW
UCTE - 1

UCTE - 2
Turkey

AL MAGHREB System Enhancement necessary:

Source: ITC 8/2003 – “Blackout”

Fig. 5. A View on the European Scenario - with further Options for Grid
Interconnection to UCTE
Source: National Transmission Grid Study;
Source: UCTE - 5 / 2003 U.S. DOE 5/2002 – “Preview”
Bottlenecks
in the UCTE Fig. 8. Comparison of Study Results 2002 with the real Blackout 2003
System Scenario

Fig. 8 shows the results of a study on the related


transmission systems, which was published in may, about one
year earlier. It can be seen, that the load flow in the system is
not well matching basic design and planning criteria, ref. to
the “hot lines”, shown in red color. On the upper right-hand
side of the figure, one of the later Blackout events with
“giant” loop flows is attached, which happened just in the
same area under investigation one year before.
NTC Values
for East- The Blackout sequence took about 4 hours, before it came
West Power to the final collapse. At 4:06, a wrong relay operation
Transfer
(Sammis-Star Line) initiated the final cascade, and shortly
after, at 4:14, there was the “point of no return” with huge
Fig. 6. Bottlenecks in UCTE: NTC – Net Transfer Capacity
loop flows across several states and the beginning of voltage

3
4

collapse. This led to further disconnections of lines and large IV. ELIMINATION OF BOTTLENECKS IN TRANSMISSION –
amounts of generation capacity, with significant voltage and LESSONS LEARNED
frequency fluctuations, up and down. A full voltage collapse
and the final Blackout was the consequence. The affected area A. Use of Power Electronics for System Enhancement
out of supply is shown in Fig. 9. Fig. 10 gives an “Application Guide” for transmission
enhancement by means of Power Electronics (ref. to the
system in Fig. 8).

Short-Circuit Current Limitation for Connection of new Power Plants

SVC & HVDC for Prevention of Voltage Collapse


Source: Blackout Summary, U.S./Canada
Power Outage Task Force 9-12-2003
Load Management by HVDC

The FACTS & HVDC “Application Guide”

Load Displacement by Series Compensation

Fig. 10. Use of Power Electronics for System Enhancement

Fig. 9. The Area of the Blackout [2] Depending on the grid structure, there are four basic cases:
Approximately 50 million people in 7 states were out of • load displacement in case of parallel lines by
supply for hours or days. A total amount of 62 GW customer impedance variation (FACTS for series compensation)
loads was lost (this corresponds to half of the installed • fast load-flow control in meshed structures with
generation capacity in Germany) of which 49 GW have been B2B/GPFC or UPFC (or very slow with phase shifting
reconnected within 16 hours. transformer)
• voltage collapse: reactive/active power injection by
C. The Events in Europe
means of FACTS/HVDC
These events can be summarized as follows: • excess of allowed short-circuit level: short-circuit
Great Britain (August 28): current limitation (FACTS/HVDC)
„ 1 Transformer out of service due to Buchholz Alarm and
a wrong Protection Relay Setting. However, only a P
limited Area (South London) was affected V1 , δ 1 V2 , δ 2
Denmark-Sweden (September 23):
G~ G~
„ A large Collapse in the Synchronous Area due to
Power Station Outages in Combination with a double X
Busbar Fault (storms and wrong “construction”)
V1 V2
Italy (September 28): P= ( 1 - δ 2)
sin (δ
X
„ Outage of 2 major Transmission Lines; Overload on the __
remaining Lines – Full Blackout – very similar to the US-
Canada Event Power-Flow Control
The Italian Blackout was initiated by a line trip in Parallel Compensation
Switzerland. Reconnection of the line after the fault was not
Series Compensation
possible, due to a too large phase angle difference (about 60
degrees, leading to blocking of the Synchro-Check device). 20 Fig. 11. Power Transmission – The basic Equation
min later a second line tripped, followed by a fast trip-
The basic equation for power transmission (Fig. 11)
sequence of all interconnecting lines to Italy due to overload.
explains the solutions for system enhancement in a clear way.
It is one of the key-consequences of deregulation, that the
power transfer across the systems is nowadays much more The power transmitted between two subsystems depends on
wide-spread and fluctuating than initially designed by the voltages at both ends of the connecting line, the line
system planners. The system elements are going to be loaded impedance and the phase angle difference between the
up to their limits, with risk for loosing the n-1 safety criteria. connecting points. Power electronics can actively influence
System enhancement will be essential in the future, in Europe one ore more of these parameters and control or direct the
too. power flow through the interconnection.

4
5

As mentioned before, also Phase Shifting Transformers are 1000 km 500 kV AC interconnection between North and
suitable for load-flow variation, however with major South systems has been realized. In the interconnection two
constraints regarding the controllability in case of transient TCSC devices have been installed at both ends of the line
and emergency conditions: which damp the inherent oscillations that occur between the
systems. Additionally, 5 FSCs have been necessary to reduce
Phase Shifting Transformer the transmission angle. The recordings from on-site staged
 Designed for Steady-State Conditions: fault tests during commissioning show that the interconnection
The principle is Voltage Source Injection is unstable without the damping function of TCSC. If only one
TCSC is in operation, the interconnection becomes already
 However, Tap-Changing is very slow:
stable, and with both devices acting the inter-area oscillations
5 - 10 s per Tap, in total 1 min or more for a Full- are quite well damped, and redundancy is provided. From site
Range Operation
experience, it has been reported, that under increased load
 Remedial Action in Emergency Situations: conditions, the TCSC damping function is activated up to
Reaction Time must be ≤ 100 ms (e.g. for Voltage Collapse) several hundred times per day, thus saving power transmission
and keeping the return on investments constantly “running”.
 This requires FACTS or HVDC
2 TCSCs - Redundant
V. USE OF FACTS FOR SYSTEM ENHANCEMENT 1000 km Line Job sharing
0 MW

In Great Britain, in the course of deregulation, new power PLINE


-880 MW
stations where installed in the north of the country, remote
from the southern load centers and some of the existing power 50 Ω

TCSC 5 FSCs TCSC ZTCSC


stations in the south were shut down due to environmental 0Ω
5s/Div
constraints and for economic reasons, see Fig. 12, left side. To
No TCSC - System instable -
strengthen the transmission system, a total number of 27 Line Trip after 70 s 1 TCSC - System stable
SVCs have been installed, because there was no right of way
for new lines or higher transmission voltage levels [2]. Fig. 12 0 MW
PLINE
0 MW
PLINE

c) shows the very effective power oscillation damping (main -880 MW -880 MW

control function) with two of these SVCs, installed in Harker 50 Ω 50 Ω

Substation in a parallel configuration. ZTCSC ZTCSC


0Ω 0Ω
5s/Div 5s/Div

Results of Dynamic
System Tests:
Fig. 13. 500 kV TCSC Furnas/Brazil – Essential for Transmission
a) No SVC Connected
b) Both SVC in
Voltage Control Mode Significant Increase DE CZ

c) Both SVC in Power of Power Transfer b)


Oscillation Damping
Mode

Uncontrolled Load Flow


Power-Flow Controller
CZ
DE
Benefits:
a)
Directing of Load Flow
Basis for Power
Purchase Contracts

Source: PTD
SE PT 1998

Fig. 14. UCTE: Load-Flow Improvement with Power-Flow Controller

Fig. 14 a) shows an example of the West-European system:


500 MW should be transported from Hungary to Slovenia. It
Fig. 12. Europe: UK goes ahead with FACTS - 27 SVCs in the Grid
Example Harker Substation - 2 parallel SVCs can be seen, that this power flow is spread widely through the
neighboring systems. Only a limited amount of power is
In Fig. 13 it is shown, how problems with large inter-area flowing directly to the target location. Using a power
oscillations have been solved in the Brazilian System. In the electronic device for power-flow control, e.g. GPFC/B2B or
Brazilian grid, the situation is critical because of a very long UPFC, the power exchange between the two countries can be
transmission distance between the interconnected systems: a improved significantly, as shown in the figure.

5
6

1500
360 km
Loads
3~ 1200
400 MW
900

Power flow in one line


Huishui -Hechi (MVA)
A B
200 MW
600
Loads 3~
300 b
200 MW 0
Power- Flow
b Power
a Flow in one Line
Controller … quite Easy -300
Huishui-Hechi (MW)
Restoration of the initial Power Flow – from A to B -600
c a
-900
Fig. 15. Elimination of Loop Flows by means of Power-Flow Controller 0 5 10 15 20
Time (s) Time / s
In a similar way, as shown in Fig. 15, critical power loop a – without Power Modulation
flows (ref. to Fig. 8) across the interconnections between two b – with Power Modulation Dynamic Results
systems, caused by the installation of a new power station of HVDC Control
(shown in red color) in grid B, can be eliminated by means of c – further Improvements with
a Power-Flow Controller. Pingguo TCSC/FSC
Fig. 16 gives an example of a power system simulation of
the Chinese grid [6], in which FACTS and HVDC has been POD Output Signal (pu) TCSC 1 (= TCSC 2)

integrated for grid interconnection and point to point long


1a)
distance transmission. Because of the long distances, the
More Action of TCSC required HVDC not active
system experiences severe power oscillations after faults,
close to the stability limits. In the recordings in Fig. 17, upper
POD Output Signal (pu) TCSC 1 (= TCSC 2)
part, oscillations are depicted, first for the case that HVDC is
transmitting power in constant power mode (curve a). It can 2a)
be seen, that strong power oscillations occur. If, however,
Less Action of TCSC required HVDC active
damping control of HVDC GuiGang is activated (curve b), the
oscillations are damped very effectively. Using series POD Output Signal HVDC (%)
compensation with two TCSCs and two FSCs at Pingguo
substation, the stability of the overall system can be increased 2b) Fast and strong Action of HVDC with POD
further (curve c). In the lower part of Fig. 17 it is shown, that
without HVDC, the TCSCs Pingguo need more actions for
damping. Without series compensation and without HVDC Fig. 17. Coordinated Operation of FACTS and HVDC for Power Oscillation
Damping in the Chinese Grid
damping, such a large power system would be unstable in case
of fault contingencies [6], thus leading to severe outages In Fig. 18, a view of one phase element of the two Pingguo
(Blackout). TCSCs is given.
Nayong
Anshun
Guiyang Guizhou
Conv. Stat.
Huishui Guangxi

Anshun
Anshun HVDC GuiGuang
FSC
Hechi
Guangdong

TSQ-I Liudong Hezhou Guangzhou


Luoping TSQ-II Yantan Beijiao
Liuzhou Conv. Stat.
TSQ Beijiao
Lubuge Conv. Stat. TCSC & FSC
Pingguo Laibin Wuzhou
Zhengcheng

Baise Luodong
Pingguo

Zhaoqing
Yunnan HVDC TSQ Gaomin

Yulin Zhaoqing
Guangxi Conv. Stat.

Nanning
Fig. 18. Pingguo TSC, commissioned in June 2003

HVDC Converter Hydro Power Station


In Fig. 19, a new FACTS application with SVC in
Station
Thermal Power Station combination with HVDC in Germany is shown [7]. It is
TCSC FSC actually the first high voltage FACTS controller in the
German network. Reason for the SVC installation at Siems
Fig. 16. Use of FACS and HVDC in a Hybrid System in China
substation nearby the landing point of the Baltic Cable HVDC

6
7

were unforeseen right of way restrictions in the neighboring As a consequence of “Lessons learned” from the large
area, where an initially planned new tie-line to the strong 400 Blackouts in 2003, high voltage power electronics will play an
kV network for connection of the HVDC was denied. Hence, important role for the system developments, leading to hybrid
with the existing reduced network voltage of 110 kV (see the AC/DC systems with better controllability of the power flows
dotted blacks lines in Fig. 19), only a limited amount power and to assist in prevention of cascading disturbances.
transfer of the DC link was possible since its commissioning
in 1994, in order to avoid repetitive commutation failures and VII. REFERENCES
voltage problems in the grid. In an initial first step for power [1] D. Povh, D. Retzmann, “Development of FACTS for Transmission
increase, an additional transformer for connecting the 400 kV Systems”, The IERE Central America Forum, Nov. 23-28, 2003, San
HVDC AC bus with the 110 kV bus (see the figure) was José, Costa Rica.
[2] G. Beck, D. Povh, D. Retzmann, E. Teltsch, “Global Blackouts –
installed [7]. Lessons Learned”, POWER-GEN Europe 2005, June 28-30, 2005,
Finally, 10 years later with the new SVC, equipped with a Milan, Italy.
fast coordinated control, the HVDC could fully increase its [3] FACTS Overview, IEEE and Cigré, Catalog Nr. 95 TP 108.
transmission capacity up to the design rating of 600 MW. In [4] V. Gor, D. Povh, Y. Lu, E. Lerch, D. Retzmann, K. Sadek, G. Thumm,
“SCCL – A new Type of FACTS based Short-Circuit Limiter for
addition to this measure, a new cable to the 220 kV grid was
Application in High Voltage Systems”, CIGRE Report B4-209, Session
installed, to increase the system strength with regard to 2004.
performance improvement of the HVDC controls. [5] Kirschner, L., Bohn, J., Sadek, K. “Thyristor protected series capacitor -
Part 1 Design Aspects”, IEEE-T&D Conference 2002, Sao Paulo,
Initially planned Connection Brazil.
[6] Y. Jing, X. Wu, Z. Du, X. Jin, Y.Wang, D. H. Zhang, J. Rittiger, “Digital
Simulation of AC/DC Hybrid Transmission System”, PowerCon, Oct.
2002, Kunming, China.
[7] H. Waldhauer, “Grid Reinforcement and SVC for full Power Operation
Grid Access
denied
2 of Baltic Cable HVDC Link”, The 38th Meeting and Colloqium of Cigré
Study Committee B4 ”HVDC and Power Electronics”, Technical
Colloqium Sept. 25, 2003, Nuremberg, Germany.
1 [8] M. Mohaddes, D.P. Brandt, M.M. Rashwan, K. Sadek, “Application of
Now, the HVDC the Grid Power Flow Controller in a Back-to-Back Configuration”,
2 can operate at
full Power CIGRE Report B4-307, Session 2004.
Rating

VIII. BIOGRAPHIES
Final Solution: new Lutz Kirschner (1963) received his BSC in Electrical
2 SVC with TCR & TSC 1 Initial Step for Grid Access Engineering 1992 from the University of Aachen,
100 MVar ind. Enhancement Germany. He joined SIEMENS company, and worked
2 and a new 220 kV Cable
200 MVar cap. in the HVDC department as a system design engineer.
He is involved in technical and commercial design of
Fig. 19. The Problem – no Right of Way for 400 kV AC Grid Access of Baltic HVDV converter stations. Since 1995 he is
Cable HVDC Link – and the Solutions [7] responsible for Series Capacitor Design carrying out
the basic design studies. His special field are time
In Fig. 20, a photo of the Siems SVC in Germany is given. domain simulations and system studies. Since 1998 he
is member of IEEE.
Dietmar Retzmann (1947), Cigré, VDE, graduated in
Electrical Engineering (Dipl.-Ing.) at Technische
Hochschule Darmstadt/Germany in 1974. He received
Dr.-Ing. degree from the University of Erlangen-
Nuremberg in 1983. Dr. Retzmann is with Siemens
Erlangen, Germany since 1982. Currently, he is
director for Technical Marketing & Innovations
HVDC/FACTS in High Voltage Division, Power
Transmission Solutions. Dietmar Retzmann is author
of numerous technical publications. In 1998, he was
appointed guest-professor at Tsinghua University,
Beijing, and in 2002 at Zhejiang University,
Hangzhou, China. Since 2004, he gives lectures on
Fig. 20. A view on the Siems SVC HVDC/FACTS at University of Karlsruhe, Germany.
Gerhard H. Thumm (1951) received his Dipl. Ing.
VI. CONCLUSIONS degree in electrical Engineering 1977 from the
Technische Universitaet Stuttgart, and the Dr. Ing.
Deregulation and privatization is posing new challenges on degree in Electrical Engineering 1991. He joined
the high voltage transmission systems. System elements are Siemens in 1982, where he worked in the system
going to be loaded up to their limits, wide-area power trading planning department and in the department for
with fast varying load patterns will cause congestion, because reactive power compensation. Since 1985 he is
involved in the design of Static Var Compensators,
the systems are not designed for such conditions. System since 1992 he is repsonsible for the design of Series
enhancement will be essential to keep the supply reliable and Compensation Systems, also with Thyristor Control.
safe.

You might also like