You are on page 1of 7

Interconnection of electric power

systems in the Arab worl

Economic and technical considerations are usually the underlying factors for
interconnecting neighbouring electric power systems. Among some of the
benefits that may be realised are plant capacity savings, interchange due t o
diversity, emergency power interchange, spinning reserve savings. However,
planning of interconnections is a demanding task and must cover a wide
range of technical aspects. This article presents the advantages, requirt=merits
and problems arising from the interconnection of electric power systems in
the Arab world. It also presents the planning principles for grid system,
procedure for power system development planning, technical aspects of
interconnection, and possibilities of increasing interconnection capacity by
limited means. The results of studies investigating the feasibility of
interconnecting the power networks of the six countries which form the Gulf
Co-operation Council (GCC) are presented. The article also shows existing and
future interconnections of power systems in the Arab world.

by Emad S. lbrahim

Introduction economical, and may be summarised as


The interconnection of electric power has fol 1ows:2,3,4
been a well established practice since the
development of three-phase AC systems. Systems when interconnected need less
Many interconnections run across installed generation plant t o achieve a
international boundaries linking countries given level of security of supply than
w i t h varying political, social and economic would be required for separated systems.
systems. The reasons for interconnection Interconnections enable systems t o share
are based o n economic, strategic and spinning reserve so that each system can
technical considerations. Among the best carry less spinning reserve than would be
known interconnections are the Canada-US required without interconnection.
Eastern interconnection, the Pacific West Catastrophic multiple outages, such as
interconnection and the Texas interconnection the simultaneous loss of several
in North America, the interconnection systems generation units, can lead t o widespread
of Western and Eastern Europe, and the interruptions of supply and possibly t o
Japanese National Grid.’ the total collapse of the power system.
In the Arab world, the interest in the Strong interconnections t o neighbouring
interconnection of electric power systems systems limit the effects of, ancl help
started at the Tenth Engineering Conference recovery from, such catastrophic events.
held at Al-Quds in 1966. In the Middle East, Interconnections enable interchange of
several interconnections exist or are under planned or incidental energy between
consideration. For example, the electric systems resulting in a lowering of the
networks of the eastern and the central total operating costs.
provinces of Saudi Arabia are interconnected. Interconnections also permit assistance
The interconnection of the power systems of from neighbouring systems t o cope with
Egypt and Jordan is in the implementation unforeseen construction delays and
stage. In addition, investigations have been unexpected load growth.
conducted t o study the feasibility of Quality of supply is improved by better
interconnecting the power systems in the system frequency and voltage c m t r o l .
Mashreq Arab countries and of
interconnecting Turkey t o the Northern Arab Planning principlesfor grid systems
States. The following fu nda menta I principles
The reasons for the interconnection of guide the lanning of bulk transmission
power systems are both technical and networks:
P
POWER ENGINEERING JOURNAL JUNE 1996 121
1 Procedure for long-
range system
development planning

Q service level

, technological
innovation

i policy ------

I The power system must be planned and However, when out-of-merit operation
constructed in such a way that there is of generation may defer transmission
sufficient generation and transmission system reinforcement, this should be
capacity t o cover the load forecast. considered if the overall system
2 The system must, without interruption economics favour it.
bf power supply t o the consumer, be 6 A flat voltage profile should be the
able t o withstand most of the faults that objective in planning the bulk
may occur. Basically no single fault transmission network as well as a
contingencyshould cause loss of bulk minimum of reactive power transfer
supply continuity. between the bulk transmission and the
3 The interconnected network must be various subtransmission systems. The
planned and operated in such a manner overall grid system power factor should
that there are no oscillation phenomena be lagging.
in the power system or thermal overload
of network components during normal Procedure for power system
operation. Oscillations in connection development planning
with faults must be sufficiently damped The procedure adopted generally in
and temporary permissible overloading power system long-range planning is
removed in time. shown in Fig. 1 . 6 The first step is t o
4 It is technically not possible t o construct a conduct an accurate demand forecast.
power system with 100°/~reliability of Secondly, several plans are carefully
supply and a compromise between developed for t h e generation, transmission
security of service and cost of service and distribution systems, and the system
must be selected. Interruptions that operation facilities. These plans must meet
occur should, however, as far as possible the reliability requirements, conform t o t h e
be limited in time and space, with help of utility policy and guidelines, and must take
a suitable programme of action (load into account the existing system elements
shedding scheme etc.). and characteristics. Finally, a com pa rative
5 The network should, in general, enable study is made o n these plans by
the most economic generation dispatch. emphasising reliability and economic
122 POWER ENGINEERING JOURNAL JUNE 1996
efficiency, and the most appropriate plan is Generating plants
selected based o n management policy and The generating plants in an interconnected
available funds.’ system have t o be designed with respect t o
certain specifications concerning sensitivity
Technical aspects of interconnection t o frequency and voltage deviations, and
Several studies are required t o assure the facilities to control active and reactive power.
technical viability of the system or systems For frequency requirements, as all units will
under consideration. These are load-flow be affected by the same frequency drop at a
studies, reactive power and voltage control loss of generation, it is of the utmost
requirements, short-circuit levels, stability, importance that the units fulfil certain
insulation problems and others. The requirements with respect t o the frequency.
techniques used t o conduct such studies are If not, the most sensitive units may trip
well established. However, the interpretation causing further frequency decay, thus
of the results and the relative importance of increasing the risk of cascade tripping and
each of these items have t o be weighted blackout.
properly.’

Transient a n d dynamic behaviour


The dynamic behaviour of internal systems
may change as they become interconnected.
Damping techniques may be used such as
the power system stabilisers. However,
reinforcing the tielines and internal systems
are basic means.

Frequency control a n d spinning reserve For voltage requirements, although the


The tripping of a unit in any subsystem will voltage disturbances are more local, voltage
affect frequency controlled reserves in any dips of certain levels and duration must not
part of the system. A few aspects are cause tripping of the unit.
important t o note:’ Hydro and thermal units should meet
certain standards of control facilities.
The tielines (and the internal system)
should be strong enough t o transfer the Network configuration and switchgear rating
extra transfers deriving from reserves in The updating of the network configuration
one country, when a unit trips in another may be carried out by load-flow calculations,
cou nt ry . while the updating of the switchgear and
0 Large units may be used in rather small circuit breakers may be obtained using short-
systems, as reserves may be used in other circuit studies for the overall interconnected
parts. system. The underrating of the circuit
breakers may be avoided by using either
In case of serious disturbances the tielines busbar limiting reactors or feeder reactors.
may split. Thus an emergency plan should be However, the protective relay systern must be
prepared t o maintain the systems in separate updated as well as the regulator parameters
operation, i n ~ l u d i n g : ~ and configurations should match the new
conditions.’
0 local spinning reserves and load shedding
preparations of control centres and Protective system
generating units, including possibility t o The protective system strategy is not
rapidly change the frequency control limited t o the tripping operation of an
strategy. overloaded transmission line or transformer.
It can go up t o the utilisation of reactive
In case there are a number of tielines, the power compensators in order t o reduce the
remaining lines should be strong enough t o consumer voltages and therefore reduce the
keep the total system stable, in case one main loads in the system. A decrease of the
tieline trips. busbar voltages by 5% will lead t o a
corresponding decrease in the load power of
Load shedding 10% which can greatly help the generating
Load shedding based on local frequency stations and transmission links during peak
criteria is often used as a back-up system t o loads.7
prevent total blackout. In case t w o separate
systems become interconnected, the load Control systems7
shedding has t w o purpose^:^ When the generator is connected t o a
weak system, the automatic excitation
t o support the individual systems in case control has the object of controlling the
tielines trip machine voltage, and the speed governor has
t o support the total system in case there the object of controlling the machine speed
are internal faults. and participating in the control of the system
frequency.
The latter purpose requires co-ordination If the generator is connected t o a strong
between the shedding schemes. system the machine voltage and system

POWER ENGINEERING JOURNAL JUNE 1996 123


Table 1 Means t o increase the interconnection capacity

means

new ines
large conductors
higher voltage level
rapid relay protection
series capacitors
shunt capacitors/reactors (breaker switched)
shunt capacitors/reactors (thyristor controlled) *
nchronous condensers
pplementary control of generators

frequency are almost constant and the main links have higher risks of insulation flashover,
object of the automatic excitation control is and can be more expensive than an AC
t o control the reactive power fed by the system with the same ratings.’
generator while the speed governor is t o
control the active power fed by the generator Increasing interconnection capacity by
t o the network. limited means5
As the system capacity increases, either by Normally the transmission capacity of a
installing new large generating stations or by line is defined by i t s thermal limit. For a line
interconnection with another system, the interconnecting t w o systems, stability may be
system may transfer from a weak t o a strong the limiting factor as well.
one and the function as well as the
parameters of the control systems must be Stability as limiting factor
u pda ted . Every perturbation during normal
The updating of the control systems could operation, i.e. load change, generation
also be done by the addition of new control change, line tripping or line fault, is followed
systems such as: by an oscillatory transient. In an
interconnected system, the severity of these
secondary control systems for load oscillations increases when the
frequency control (SCSLFC) interconnection length or the power
economic dispatching centre (EDC) transmitted increases.
co-ordination between SCSLFC and EDC The stability problem can be divided into
optimisation of both location and values the following aspects. Stable operation is
of static VAR compensator for the obtained if all of these are managed:
interconnected network
replacing of old control equipment by 0 first swing stability and damping of large
new, such as static excitation, hybrid oscillations, i.e. transient stability
control system or digital control systems 0 damping of small oscillations, i.e. dynamic
stability
DC interconnection 0 frequency control
DC is the only alternative for 0 voltage collapse.
interconnecting power systems operating a t
different frequencies, e.g. 50 and 60 Hz. Means of in creasing interconnecting capacity
Long cable links can be built for DC A number of means t o increase the existing
transmission, since the capacitance does not or planned transfer capacity between systems
need t o be taken into account. In fact, in are listed in Table 1 .
some cases DC will be the only feasible The factors which should be evaluated
solution. during the selection between different means
The fast-acting power control of DC links a re:
gives a number of possibilities:’
0 the increase of transfer capacity
0 improved transient stability limits of costs and benefits taking into account
subsystems also operational costs and losses
0 stabilising of power oscillations giving reliability.
improved transfer capacity when
damping is a limiting factor New lines normally mean high cost but at the
emergency power assistance from one same time it improves the reliability. Also
subsystem to the other. using higher voltage is expensive but it
usually decreases losses.
It is important t o mention here that DC links Series capacitors decrease the electrical
provide superior performance in limiting the length between subsystems. Their benefit is
spread of system disturbances and in limiting that they increase the reactive power when
the contribution t o the fault current between the power transmitted increases.
interconnected systems. However, the DC The idea of shunt compensation is t o
124 POWER ENGINEERING JOURNAL JUNE 1996
maintain constant voltage in the system. Table 2 Demand forecast for GCC network
Breaker-switched compensators are used t o (MW)
take care of the excess or shortage of reactive
power during normal operation. utility year
Static, thyristor-controlled compensators
1995 2000 2005 2010 2015
are used for fast control of reactive power. By
this fast control the system damping can be
improved. In this case control is based on the
speed of voltage variation or in practice on
signals from active power. The drawbacks of
static compensators compared with breaker
switched compensation are higher price,
need for more maintenance and bigger
losses. On the other hand, compensators can
be com pa red with synchronous
compensators. In this comparison, static The adopted interconnection concept and tie
systems are faster in control and they are capacities for the GCC countries are shown in
cheaper. Fig. 2. In this interconnection, the 510Hz
Damping can also be improved with a systems of Kuwait, Bahrain, Qatar ;lnd UAE
power system stabiliser, to control generator are interconnected by a double-circuit 400
voltage and further the electrical output kV backbone extending from Kuwait t o the
according t o the oscillations. The advantage UAE. Oman power system is connected t o
of stabilisers is that almost all modern UAE system by a 275 kV double-circuit line.
exciters already include the electronics The 60 Hz SCECO East system is
needed or it can be easily installed and, interconnected t o the 50 Hz backbone by a
consequently, the extra cost is mini mal. 1800 M W back-to-back link. Bahrain and
Qatar are connected t o this backbone via
GCC interconnected systems4 220 kV circuits.
Studies to investigate the feasibility of
interconnecting the power networks of the Requirements and problems of
six countries which form the Gulf Co- interconnection
operation Council (GCC), Bahrain, Kuwait, Requirements and problems of
Qatar, Saudi Arabia (SCECO East), Oman and interconnection can be classified in to four
the UAE have been completed.8~9~10 Plans categories:”
exist for the implementation of such an
interconnect ion. I Capital a n d international financing
Table 2 shows the demand forecast for situation
each of the GCC power networks up t o the Most Arab countries face problerns of
year 201 5. finance shortage for electricity development
The size of the interconnection proposed projects.
for each of the GCC countries was based on a
strategic criterion.8This criterion is: 2 The technological a n d manpower
situation
‘The size of the interconnection would be This category leads t o the following
such that each system could import u p t o problems with their long-term effects:
half the installed capacity of the largest
power plants, but no more than 30% of the 0 insufficient transfer of technology
peak load in 201 0, even during an outage of 0 lack of training of the indigenous
any one element of the interconnection t o population
that system. ‘ 0 delay in project execution mainly caused
by bottlenecks in the overburdened civil
The use of this criterion resulted in the construction sector
interconnection shown in Table 3. emigration of scarce Arab skilled labour,
The principal factors influencing the mostly t o the OPEC-Arab countries.
development of schemes t o implement the 0 migration of non-Arab unskilled (and in
interconnection are: limited cases skilled) Asian manpower t o
the Arab oil producing countries.
(a) The power system in Saudi Arabia
operates at a frequency of 60 Hz, while Table 3 Interconnection tie capac:ity(MW)
the systems in the other five states
operate at 50 Hz. county capacity
(b) The distances involved are relatively __ . .
large. For example, the distance from
Kuwait t o the United Arab Emirates is KJWdll 1200
over 1000 km. Saud Alaoia 1800
(c) Bahrain may be separated from the other Bd hrain 600
countries by water, but there is n o w a Qatai 750
bridge connecting Bahrain and Saudi UAE 900
Arabia and therefore a submarine cable Oman 400
may not be necessary.
POWER ENGINEERING JOURNAL JUNE 1996 125
2 GCCsystem
interconnection

Saudi
Arabia
(SCECO
East)

(ii
3 Standardisation Existing and future interconnections”
The construction process of electric power The existing interconnections are:
facilities in some Arab countries has involved Morocco-Algeria, Algeria-Tunisia, Syria-
consultants from various countries Lebanon and Jordan-Syria. Two lines of
participating separately according t o specific 225 kV and 200 M W already exist between
projects. As a result, those facilities which Algeria and Morocco.
lack uniformity are growing in number and The interconnection of the power systems
sizes. The effect of such discrepancies may of Egypt and Jordan is in the implementation
not raise serious problems as long as the stage. The interconnection across the Red
systems are operated separately. However, Sea is being done by submarine cables. For
they may result in large amounts of trouble the interconnection of electric power systems
when the structuring of large-scale electric in the eastern and western Arab countries,
systems is considered.’ these submarine cables will work on AC a t
Because of the piecemeal approach, there 600 M W in the first stage. Also, these
has been no unification of electricity submarine cables can work on DC at 1200
standards (frequency, voltages, equipment, M W , but it becomes necessary t o build a
fittings etc.) inside most of the Arab DYAC convertor station.
countries and the Arab world as a whole. The Egypt-Jordan interconnection is the
All Arab countries adopted 50 Hz as a first stage in the interconnection project
standard national frequency, except Saudi Egypt-Jordan-lraq-Syria and Turkey. The
Arabia which n o w utilises 50 Hz and 60 Hz interconnection of these five countries
systems. started operation in 1995. The t w o 400 kV
In high-voltage distribution, the Gulf networks in Syria and Iraq make such
countries use 132, 220 and 380 kV while connection easy.
the other eastern countries (Iraq, Syria, Two lines of 225 kV and 200 MW are n o w
Jordan and Lebanon) use 132, 150, 230 implemented between Libya and Tunisia, and
and 400 kV. The western countries use 132, it is expected that they will start operation in
230 and 400 kV for high-voltage 1997.
distribution. In Egypt, the high-voltage The possibilities of other interconnections
distribution used is 132, 220 and 500 kV. are:
The 132 kV used in lower Egypt will be
gradually phased out. Saudi Arabia and Sudan
A DC link between Saudi Arabia and Sudan
4 National networks under the Red Sea may be feasible if large
There are nine Arab countries whose water dams were constructed on the Nile in
national networks are not yet Sudan.
interconnected. These countries are UAE,
Gibote, Saudia Arabia, Sudan, Somalia, Sudan and Egypt
Oman, Libya, Mauritania and Yemen. It is A link is not feasible n o w since the
important t o complete the design of national northern Sudan load centre is about 900 km
grids before any interconnection steps are from the High Dam in Egypt and the load in
taken. Sudan does not warrant such a connection.
126 POWER ENGINEERING JOURNAL JUNE 1996
Kuwait and Iraq functions, where each function becomes
The project has been thoroughly studied more and more sophisticated in order t o
and proved t o be feasible since the t w o daily get optimal performance.
load curves are different (peak loads occur at Total Arab electricity production was
different times). The amount of energy which 236.4 TWh in 1992, compared to 85.2
may be exchanged merits such connection TWh in 1980. This calls for an additional
since the t w o consumption centres are not investment in the electricity sector in the
far away. The connection may be made using Arab World from n o w until the end of the
a 400 kV line connecting Kuwait to Basrah. century.
0 The interconnection of electric power
Egypt and East Libya systems in the Arab world will reduce the
A connection between the eastern part of spinning reserve by 1 4 3 2 0 M W (1 3 320
Libya to the Egyptian network by t w o lines M W in the eastern countries and 1000
has been studied. The first stage includes a M W in the western countries).
220 kV, 170 M W line. The second stage 0 The interconnection of electric power
includes one 500 kV line. systems in the Arab world will reduce the
possibility of complete loss of load t o 0.2
Conclusions days per year.
0 For interconnected networks, power It is recommended that combined-cycle
supply reliability is enhanced, generation gas-turbine technology should be used t o
of power is cost efficient, shutdowns and give high efficiency. Egypt, Syria and,
outages are easily manoeuverable, even more recently, Gulf countries have already
during peak demand periods. Breakdown started t o used combined-cycle
periods are reduced t o the minimum. generation.
0 Before interconnection of different
networks, a comprehensive study References
encompassing short-circuit rating of 1 AL-SHEHRI,A. M., EL-AMIN, I. M., and
equipment being interconnected, fault OPOKU, G.: 'An overview of essential
levels of the interconnected networks, parameters for planning power system
interconnections', Proceedings of the 2nd
voltage IeveWdrops, maximum power
Symposium on Electrical Energy in the UAE,
transfer, effects of circuit outages, peak 17th-I 9th November 1991, paper 1 .I.
summer demands and frequency levels 2 EL-AMIN, I. M., AL-SHEHRI, A. M., and
needs t o be done t o ensure system OPOKU, G.: 'Power systems interconnection in
security and t o avoid collapse of the total Saudi Arabia: scenarios and options', ibid.,
system in case of faults. paper 1.2
0 The interconnection of Arab power 3 YOUSUF, M. A,, IBRAHIM, M., and AL-
networks is strictly dependent on the GOBAISI, D. M. K.: 'Development and
development of the internal networks, justification of interconnected transmission
such that interconnections become system for UAE', ibid., paper 2.3
4 EL-AMIN, I. M., AL-SHEHRI, A. M.,;Ind
economical and feasible. So, it is
OPOKU, G.: 'The UAE power system as an
important t o complete the design of the integral part of the GCC network', hid., paper
national grids before any interconnection 2.4
steps are taken. 5 HOLBERG, D.: 'Interconnection of power
For all Arab countries, it seems that 50 Hz systems: economic benefits, technical
networks should be imposed, and 400 kV possibilities and limitations', ibid., paper 1.3
should be selected for Eastern Arab 6 'Power system development planning', Tokyo
countries and 220 kV for North African Electric Power Company
Arab countries. Also, higher voltages 7 AMER, A. H.: Interconnection of the UAE
should never be selected in one country in Emirates electric power networks',
Proceedings of the 1s t Symposium on
isolation from neighbouring countries.
Electrical Energy in the UAE, 3rd-5th Arpil
0 Joint effort should be shown in
1988, pp.445-460
standardisation and development of 8 'Feasibility study for interconnectiori of Arab
electrical equipment construction. gulf States electrical power systems', GCC,
0 Updating of network configuration and 1986
control and protection systems is 9 Update feasibility study', Hydro Quebec
necessary for the interconnected network. International, GCC, 1990
It is necessary t o survey the available 10 'Feasibility study of electrical network
sources of energy in the Arab countries. It interconnection of Mashreq Arab countries',
is expected that non-conventional sources Arab fund for Economic & Social
Development, 1991
of energy (i.e. nuclear, solar etc.) should
11 AL-ABIAD, H. A. H.: 'Power system analysis
be used. Joint effort is recommended t o and planning' (McGraw-Hill, 1983)
establish a nuclear power station in one
Arab country.,
0 Electric energy generation should be in
0 IEE: 1996
conjunction with irrigation and
Emad S.lbrahim is with the Department of
desalination projects. Electrical Machines and Power Engineering,
0 The studies of interconnection in the Arab
Faculty of Engineering and Technology, Helwan
countries should take into account University, Helwan, Cairo, Egypt. Dr. Emad can be
modern energy management systems contacted a t PO Box 27, Daher, Cairo, Esgypt, or by
(EMS) with a large variety of advanced E-mail: emad-seib@frcu.eun.eg.
POWER ENGINEERING JOURNAL JUNE 1996 127

You might also like