Problems of Power System Frequency and Active Power Control

N.Gurov V.Chuvychin 1.Andreevsky A.Vorzhev


Dr. Sc. Eng. Professor, Dr.Hab.Sc.Eng. Ph.D student Ph.D student
nonmember Senior Member, IEEE nonmember nonmember
Department of Power and Electrical Engineering, Riga Technical University

-.
Abstract This paper illustrates the result of research done control process to follow pre-set law for any parameters of
by authors in the area of frequency and active power control. the generator. Simulation results are presented in paper.
For interconnected power system besides of common To approve suggested regulation method the authors
frequency regulation there is a need to control tie-line load have done experimental investigation of hydrogenerator’s
flows. . Control problem can be divided into two parts:
loading process at the Riga power plant using dynamic
.
control of normal and emergency conditions. The reasons of
control law. Experiments proved possibility of practical
interconnection’s oscillations are considered as well as new
method for regulation of frequency without oscillations. For implementation at different power stations.
efficient control the authors propose a method based on the 111. FREQUENCY AND ACTIVE POWER CONTROL
use system phase plane. This method is efficient for control of DURING EMERGENCY
normal and emergency situations in the power system. Results In modern power systems there is a big variety of
of simulations presented in the paper. emergency conditions with a wide range of dynamics. The
Keywords: frequency control, governor, dynamic misbalance of generation and load can cause an overload of
characteristics intersystem tie, loss of its stability and as a result -
I. INTRODUCTION islanding in the power system. In a part of the system with
For interconnected utilities besides frequency control surplus of generation frequency can go up. Especially it is
active power tie-line control was accomplished by dangerous in an island containing nuclear power plant with
comparing net actual interchange to net scheduled narrow allowed frequency operational range. After
interchange. Problems became very actual with creation of disconnection of nuclear station emergency process may
the new power systems in the Eastern Europe. have avalanche character.
Frequency control problem is especially topical for the Existing automation is not adaptable to the variety of
power systems, having not uniform structure of generating emergency situations in the power system. Authors
unit. In the power system with almost equal amount of suggested new effective method for frequency control in
hydro and steam type generation it is difficult to the power system during emergency situation.
synchronize participation in frequency control for all units. Measuring the initial and current values of frequency
Control problem can be divided into two parts: control and rate-of-change of corresponding frequencies,
of normal and emergency conditions. Existing control determining point at the phase plane ( df/dt, f ) which
systems are designed to control precalculated normal and determines the state of the system at considered moment,
especially emergency situations and they are nod adaptive and knowing control law at the any instant, the final value
to the situation in utility. of frequency can be determined. Thus, control system is
11. PROBLEMS OF FREQUENCY AND ACTIVE POWER adaptable to the situation. To prevent high frequency
CONTROL FOR NONUNIFORM POWER SYSTEM increase hydro generators should be disconnected from the
Quality of the frequency control in the power system is system. Method proposes disconnection of generators one
related to dynamics of power regulation by the power after another with control of frequency and rate-of-change
stations participating in control. Dynamics of regulation of frequency. It allows to implement frequency control in
depends on dynamic properties of governors and all control effective manner without overshooting.
system. IV. CONCLUSION
Specially selected electric power stations are 1. Frequency control problem is topical especially for the
contributing to interconnection frequency regulation. The power systems having not uniform structure of
distribution of the load among parts of a system influences generating units.
electric power oscillation’s character along the tie-line. 2. Quality of the frequency control in the power system is
Especially large oscillations take place for dynamic control related to dynamics of power regulation by the power
in pool with different types of generations stations. Paper stations participating in control. Dynamics of regulation
consideres examples of dynamic load behaviour between depends on dynamic properties of governors and all
two systems with prevailing hydropower structure. control system.
Analysis allowed authors to come to the following solution 3. To avoid tie-line power oscillations governor’s
of frequency regulation problem. It is more effective to parameters of regulating stations should be similar.
control frequency and active power using dynamic control 4. The authors expanded the phase plane method for a
law. For efficient control the authors propose a method new frequency (active power) governor control. The
based on the use of system phase plane. In this case at the method requires measuring both the frequency and the
any instant generator’s state may be described by the point rate-of-change of frequency to estimate the system state
at a phase plane with coordinates f and dfldt, or P and at any given time.
dP/dt. Let us assume the desired dynamic control law as a 5. To approve suggested regulation method the authors
curve at a phase plane. This curve should be set in the have done experimental investigation loading the
memory of microprocessor-based governor which forces generator using dynamic control law.

-7-