Professional Documents
Culture Documents
D103261X012
Supplement to Fisherr FIELDVUEt DVC6000 or DVC6200 Digital Valve Controller Instruction Manuals
Implementation of LockinLast Strategy
Many applications require a valve assembly to remain in the position it was prior to a specific control system failure (lockinlast position). Functionality and safety can be designed into valve assemblies with FIELDVUE digital valve controllers by utilizing an array of accessories. The following paragraphs describe standard solutions for a number of generic lockinlast applications with DVC6000 or DVC6200 digital valve controllers.
Note This instruction manual supplement is for use with HARTr communicating FIELDVUE DVC6000 or DVC6200 digital valve controllers only.
Note The lockedin valve position depends on the exhausting speed of the actuator.
www.Fisher.com
Figure 1. LockinLast on Loss of Supply Pressure for an Assembly with a SingleActing Actuator (Fisher DVC6000 Depicted)
FISHER 164A THREEWAY SWITCHING VALVE D B C A
OUTPUT SUPPLY
In a fail condition, the pressure at port D is below the switching valve's set point, causing the switching valve to trip. This closes port B, which locks the pressure in the actuator. Port C is plugged so the digital valve controller output will not exhaust to the atmosphere.
FISHER 64 REGULATOR
DIGITAL VALVE CONTROLLER
AIR SUPPLY
Connection of the digital valve controller output to a doubleacting actuator determines the action of the actuator. Figure 2 shows the digital valve controller providing lower cylinder pressure through ports D and E, and upper cylinder pressure through ports A and B. When the supply pressure falls below the set point of the trip valve, the trip valve closes ports D and A and connects port B to C and port E to F. Because C and F are plugged, the control valve is locked in place by locking pressure on both sides of the actuator piston. The assembly returns to normal operation once supply pressure is restored at the trip valve INPUT port.
Note Doubleacting actuators with a 377L trip valve require a Fisher 64 or 95H regulator. Regulators with smaller flow capacities may cause the trip valve to cycle (lock and unlock repeatedly) due to air flow demand as the assembly attempts to reset. Use a Fisher 252 or 262C pilot filter to filter supply air. Both the 164A switching valve and the 377L trip valve have a deadband that must be overcome. The switching valve must be calibrated to reset upon restoration of adequate supply pressure to the regulator. The 377L trip valve has only one spring selection. However, for minimal deadband, the lightest appropriate spring should be selected for the 164A switching valve.
Note Solenoid valves placed between the output of a DVC6000 or DVC6200 digital valve controller and the input to an actuator require a minimum Cv of 0.49. Greater restrictions can affect the response of the assembly. An example of an appropriate threeway solenoid valve for use with the digital valve controller is the ASCO 8327 Series solenoid valve from ASCO Valve, Inc.
Figure 3. LockinLast Strategy for an Assembly with a SingleActing Actuator Using a Solenoid Valve (Fisher DVC6000 Depicted)
1
3 1
OUTPUT SUPPLY
AIR SUPPLY
NOTE: 1 A SOLENOID VALVE WITH A MINIMUM CV OF 0.49, SUCH AS THE ASCO 8327 SERIES OR EQUIVALENT, IS REQUIRED FOR THIS ASSEMBLY
FISHER 64 REGULATOR
DIGITAL VALVE CONTROLLER
NOTE: 1 THE ASCO 8320 SERIES SOLENOID VALVE OR EQUIVALENT IS APPROPRIATE FOR THIS ASSEMBLY.
The solenoid valve in this solution does not require a Cv greater than 0.49. Flow capacity of this valve can be much smaller. An example of a proper solenoid valve for this assembly is the 8320 Series threeway solenoid valve. As with all solenoid valves, ensure that the solenoid valve operating pressure differential rating is adequate for the supply pressure.
Note The MCR2SP/UI switch is not provided by Emerson Process Management. Order this switch from Phoenix Contact.
Figure 5. LockinLast on Loss of Loop Current and/or Supply Pressure for an Assembly with a SingleActing Actuator (Fisher DVC6000 Depicted)
FISHER 164A THREEWAY SWITCHING VALVE B C +
DIGITAL VALVE CONTROLLER
D A
420 mA + -
1 2
7 8
NOTE: 1 THE ASCO 8320 SERIES SOLENOID VALVE OR EQUIVALENT IS APPROPRIATE FOR THIS ASSEMBLY.
Upon loss of loop current, the relay of the current threshold switch opens. This cuts power to the solenoid valve, causing the solenoid valve to trip. When the solenoid valve trips, the supply pressure that was holding the switching valve open is exhausted to atmosphere. This simulates a loss of supply pressure, causing the switching valve to trip.
Note Use a single power source for both the analog output (AO) card providing loop current to the digital valve controller and the solenoid valve. This ensures power will be maintained to the solenoid valve so long as power is maintained to the AO card.
Figure 6. LockinLast on Loss of Loop Current and/or Supply ressure for an Assembly with a DoubleActing Actuator (Fisher DVC6000 Depicted)
+ + 420 mA 1 2 7 8 12 PHOENIX SWITCH MCR2SP/UI 13 1 DA EB FC AIR SUPPLY FISHER 64 REGULATOR OUTPUT SUPPLY OUTPUT FISHER 252 AIR/GAS FILTER 3 24VDC POWER SUPPLY + SOLENOID VALVE (ENERGIZED) 2
1
NOTE: 1 THE ASCO 8320 SERIES SOLENOID VALVE OR EQUIVALENT IS APPROPRIATE FOR THIS ASSEMBLY.
Note DVC6000 and DVC6200 digital valve controllers require approximately 0.5 seconds to initialize upon power up. During this time, the digital valve controller cannot provide control. In the case where control of a previously locked valve is restored to a digital valve controller prior to the completion of initialization, the valve will travel toward its failsafe position. A relay with an engagement deadtime, such as the MCR2SP/UI from Phoenix Contact, can be used to delay the release of the locking system until the digital valve controller has completely initialized. An engagement delay of 1.0 seconds will adequately minimize the dip in travel.
Note While the valve is in a locked state, the set point from the digital valve controller may change in response to changes in process conditions. This change in set point may result in a process bump when control is restored to the digital valve controller.
Related Documents
DFisher FIELDVUE DVC6000 Digital Valve Controllers Instruction Manual (D102794X012) DFisher FIELDVUE DVC6000 Digital Valve Controllers Quick Start Guide (D102762X012) DFisher FIELDVUE DVC6200 Digital Valve Controller Instruction Manual (D103409X012) DFisher FIELDVUE DVC6200 Digital Valve Controller Quick Start Guide (D103410X012) These documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com.
Phoenix Threshold Switch Specifications(1) Switch Model Number MCR2SP/UI-DC Size 44.5 X 76.2 X 108 mm (13/4 X 3 x 41/4 inches) Mounting Mounts in control room (DIN rail mount) Wiring Connect switch in series between control loop and field device Control Loop + to switch terminal 2 Control Loop to switch terminal 1 24 VDC Power Supply to switch connections Power Supply + to switch terminal 8 Power Supply - to switch terminal 7 Connect switch in series between the solenoid valve and 24 VDC power supply Power Supply + to switch terminal 12 Power Supply - to switch terminal 13 Configuration Set point 1: 15% (3 mA) Engagement Deadtime: 1 second Switch Settings
Switch 1 2 3 4 5 6 7 8 Setting On On Off On Off Off Off Off Description SP 1 SP 2 In In Out 1 Out 2 Hys. 1 Hys. 2
1.The Phoenix threshold switch is not supplied by Emerson Process Management. Order the switch from the manufacturer, Phoenix Contact (www.phoenixcontact.com). For complete installation details, see the instruction manual provided by the switch manufacturer.
Note Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end user.
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the HART Communication Foundation. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
8 EFisher Controls International LLC 2006, 2011; All Rights Reserved