Professional Documents
Culture Documents
technical updates
Role and Protection of Neutral in a LV Installation
In a well-designed three-phase installation, with the exception of singlephase terminal distribution circuits, the Neutral conductor does not convey current (or only very little: less than 15% of phase current). Its potential with respect to the ground is consequently often zero. In practice, this conductor is very rarely "neutral" and can be a source of disturbance for the operator if no precautions are taken. The function of the Neutral in the Earthing systems is to ensure: Proper operation of the installation (safety with power ON) Proper protection of persons in contact with de-energized parts of the installation (safety with power OFF) Protecting the Neutral against overloads and short circuit is essential.
A In=250 Io .7
.63 .5 x In .8 .9 1 .88 .85 .8 x Io
push to trip
200/250
90 105 5 6 7 8 10 test x Ir
Isd 4
3 2
%Ir alarm
.98
P4D
Ir Isd
200/250
90 105 5 6 7 8 10 test x Ir
P4D
Ir Isd
.37 .3
Isd 4
3 2
x In
Ph Id Id N
Figure 1: Sn = Sph
technical updates
VOLUME 4 DECEMBER 2004
Sn = Sph
N 1 2 3
Neutral Conductor with a Smaller Cross-Section than the Phases The Neutral conductor only conveys currents when there is a high unbalance and even then these currents rarely exceed 10% of phase current in well-designed installations. Consequently, it is tempting and economically advantageous to reduce its cross-section. The crosssection Sn = Sph / 2 is the one normally chosen. Thus, if Sn = Sph / 2, the Neutral conductor must be protected against Phase to Neutral faults by a specific overcurrent protection. If this protection acts directly on the phases, protection of the Neutral is guaranteed without need to break.
Imax
The IEC 60364 standard then stipulates in Section 431.2.1: b) When the cross-section, Sn, of the Neutral conductor, is smaller than the cross-section, Sph, of the phase conductors, it is necessary to provide an overcurrent detector on the Neutral conductor, adapted to the cross-section of this conductor. This detector must cause the Phases conductors, but not necessarily the neutral conductor, to break. In point of fact, this type of protection is not always reliable or economic. The use of four-pole 4P 3D-N/2 circuit-breakers (Half Neutral) is an optimum solution which also guarantees breaking (often recommended) of the Neutral conductor.
In << Iph
4P3D-N/2
P Neutral breaking: No effect for the same reason P De-energised installation P Disconnection compulsory as in the IEC 60364 Section 536.2 Indeed in the event of overvoltage on the MV (transformer breakdown or fault), the Neutral potential rises causing a very dangerous potential to appear (a few hundred volts) between the Neutral and the application ground (Figure 6). Consequently, a person performing maintenance on the machine may in this case be in direct contact with the Neutral conductor at this high voltage and the risk is at its greatest. Installation standards, in particular the IEC 60364 Section 536.2, take account of this risk by stipulating disconnection of Neutral conductors. If disconnection is performed by a multipole breaking function ensuring both simultaneous breaking then disconnection of the phases and the neutral, the result is increased safety of maintenance with power off. Disconnection is thus a necessity. A four-pole circuit-breaker enabling multipole breaking and disconnection naturally meets all the requirements of the IEC 60364 standard.
Some countries make disconnection a requirement on the basis that, just as in TT, the potential of this conductor cannot be guaranteed. The two examples below highlight these problems.
technical updates
VOLUME 4 DECEMBER 2004
Example 1: If a lightning wave (frequency around MHz) reaches the MV, it will not be stopped by grounding the transformer (as the inductive component L of the grounding Neutral connection is dominant at these frequencies since = 2 f) and the potential (dangerous) will be automatically transmitted to the Neutral conductor. Figure 7: Consequence of a MV lightning stroke In this case, the maintenance operator will be in direct contact with the overvoltage. Disconnection is recommended and thus breaking of the Neutral in the TN-S system. Example 2: High-rise buildings It is harder to guarantee the quality of grounding connections in the various storeys of high-rise buildings. The potential of the frames moves away from the potential of the ground at the bottom of the foundations due to the exceptionally long cables used. To avoid generating dangerous situations, breaking the Neutral is recommended.
General Problem Relating to Source Coupling in the Event of an Insulation Fault and Neutral Not Broken
S1 S2
GFP
When two sources, S1 and S2, are coupled using the TN-S system without breaking of the Neutral (Figure 9), if an insulation fault occurs, part of the fault current (ld1) returns normally to the source via the PE, but another part (ld2) may return to the source via the metal structures. This ld2 current is detected by the Ground Fault Protection (GFP) protection of source S2.
PE
Id2
Ground bus
Loads
Service ground
Service ground
According to current distribution, the protection of source S1 where the fault occurred may not trip as the sensitivity threshold is no longer reached. However the ld2 current may, on the contrary, disturb the GFP and cause untimely tripping if its threshold is lower than that of the coupling switch.
technical updates
VOLUME 4 DECEMBER 2004
This natural pollution of S2 can be considerable and serious if the equipment supplied is sensitive.
GFP Id2 Neutral S1 S2 GFP
PE
Ground bus
Loads
For example, if in Figure 10 a distribution of 3000 A is considered, 5% of 3rd order harmonics cumulating in the Neutral generate a flow of 3 x 3000 x 5% = 450 A. With 10% of current returned via the coupling, this gives a current of 45 A in the PE and structures, a zero sequence current, which thus generates electromagnetic radiation. Multipole breaking on the coupling switch will eliminate this harmonic pollution. Moreover if breaking is performed on both the source circuitbreakers, proper operation of the installation is guaranteed in all circumstances. A transfer switch of four-pole is recommended by IEC 60364 Section 444.4.9.
Service ground
Service ground
Figure 10: Harmonic current without insulation fault with Neutral not broken
Conclusion
Circuit-Breaker Protection Article 530.3.1 of the IEC 60364 standard stipulates that: All the moving contacts of all the poles of the multipole devices must be mechanically coupled so that their opening and closing is virtually simultaneous. In this case, a four-pole circuit-breaker must be used which ensures simultaneous opening and closing of phases and Neutral. As a result, protection of circuits using a four pole circuit breaker/disconnector guarantees the quality of the electrical power supply during operation and safety with power off.
Masterpact NW/NT
For a more detailed datasheet on the Merlin Gerin range of circuit breakers, please contact us at: Email: helpdesk@my.schneider-electric.com Helpdesk Toll Free: 1-800-880-877; General Line: 03-7883 6333 or Discover them at www.merlin-gerin.com or www.schneider-electric.com.my Should you know of others who could benefit from receiving Schneider Technical Updates, please fill in the coupon below and we will include them in our mailing list.
Yes!
NAME: COMPANY:
I would like to receive a copy of Schneider Technical Updates. I am not on your mailing list.
TECHNICAL UPDATES IS PUBLISHED BY
(139220-D)
POSTAL ADDRESS:
No.11, Jalan U1/19, Seksyen U1, Hicom-Glenmarie Industrial Park, 40150 Shah Alam, Selangor Darul Ehsan, Malaysia.
TEL: FAX:
H/P:
FAX :
HELPDESK:
1-800-880-877
EMAIL: helpdesk@my.schneider-electric.com
WEBSITE:
www.schneider-electric.com.my