Chapter 3
Outline
The following text describes: System overview of digital input modules Properties Structure Circuit and schematic diagram Technical data
Content
Topic Page Chapter 3 Digital Input Modules...................................................... 3-1 System overview .................................................................................. 3-2 321-1BH01 - DI 16xDC 24V ................................................................. 3-3 321-1BL00 - DI 32xDC 24V.................................................................. 3-5
3-1
System overview
Input Modules SM 321
In the following you find an overview over the digital input modules that are available at VIPA:
DI 16xDC24V .0 .1 .2 .3 .4 .5 .6 .7
DI 32xDC24V .0 .1 .2 .3 .4 .5 .6 .7
SM321
SM321
.0 .1 .2 .3 .4 .5 .6 .7
X 2 3 4
X 2 3 4
.0 .1 .2 .3 .4 .5 .6 .7
VIPA 321-1BL00
VIPA 321-1BH01
3-2
The digital input module collects the binary control signals from the process level and transmits them galvanically separated to the superordinated bus system. It has 16 channels and their status is monitored via LEDs. 16 entries, potential separated to the backplane bus Nominal input voltage DC 24V Useable for switches and approximate switches Status monitoring of the channels via LED
Properties
Structure
1 3
2 3 4 5 6 7 8 9
[1]
4
LEDs flap with labeling strip contact bar flap opened with inner label
[2] [3]
12 13 14 15 16 17 18 19 20 M
[4]
Pin 1 2
. . .
LED .0 ... .7
Description LEDs (green) I+0.0 to I+1.7 from ca. 15V on, the signal is recognized as "1" and the according LED is activated
9 12
. . .
SM321
19 20
12 13 14 15 16 17 18 19 20 M
.0 .1 .2 .3 .4 .5 .6 .7
X 2 3 4
VIPA 321-1BH01
3-3
Schematic diagram
Input module
Bus Mintern
Technical Data Module name Dimensions and weight Dimensions WxHxD Weight Data for specific module Number of inputs Programming specifications Input data Voltages, Currents, Potentials Isolation - between channels and backplane bus Isolation tested with Current consumption - from the backplane bus Power dissipation of the module Status, Interrupts, Diagnostics Status display Data for selecting a sensor Input voltage - Rated value - for Signal "1" - for Signal "0" Input current - for Signal "1" Input delay - from "0" to "1" - from "1" to "0" Connection of 2-wire-BEROs - Permitted bias current VIPA 321-1BH01 40x125x120mm 200g 16 2Byte yes DC 500V 25mA 3.5W green LED per channel DC 24V 15 ... 28.8V 0 ... 5V 7mA 3ms 3ms possible 1.5mA
3-4
The digital input module collects the binary control signals from the process level and transmits them galvanically separated to the superordinated bus system. It has 32 channels and their status is monitored via LEDs. 32 entries, potential separated to the backplane bus Nominal input voltage DC 24V Useable for switches and approximate switches Status monitoring of the channels via LED
Properties
Structure
1 3
2 3 4 5 6 7 8 9 22 23 24 25 26 27 28 29
[1]
4
LEDs flap with labeling strip contact bar flap opened with inner label
[2] [3]
12 13 14 15 16 17 18 19 20 1M
32 33 34 35 36 37 38 39 40 2M
[4]
Assignment not used Input I+0.0...I+0.7 Input I+1.0...I+1.7 Ground not used Input I+2.0...I+2.7 Input I+3.0...I+3.7 Ground
Circuit diagram
2 3 4 5 6 7 8 9 22 23 24 25 26 27 28 29
DI 32xDC24V .0 .1 .2 .3 .4 .5 .6 .7
=
LED .0 ... .7
Description LEDs (green) I+0.0 to I+3.7 from ca. 15V on, the signal is recognized as "1" and the according LED is activated
SM321
12 13 14 15 16 17 18 19 20 1M
32 33 34 35 36 37 38 39 40 2M
X 2 3 4
.0 .1 .2 .3 .4 .5 .6 .7
VIPA 321-1BL00
3-5
Schematic diagram
Input modul
Numeric representation
Process image:
Address 0 1 2 3
Input module:
+0 +2
.0 .1 .2 .3 .4 .5 .6 .7
00000011
Bus Mintern
0 1 2 3
SM321 +1 +3
.0 .1 .2 .3 .4 .5 .6 .7
00001100
Technical Data Module name Dimensions and weight Dimensions WxHxD Weight Data for specific module Number of inputs Programming specifications Input data Voltages, Currents, Potentials Isolation - between channels and backplane bus - between channels in groups of Isolation tested with Current consumption - from the backplane bus Power dissipation of the module Status, Interrupts, Diagnostic Status display Data for selecting a sensor Input voltage - Rated value - for Signal "1" - for Signal "0" Input current - for Signal "1" Input delay - from "0" to "1" - from "1" to "0" Connection of 2-wire-BEROs - Permitted bias current VIPA 321-1BL00 40x125x120mm 200g 32 4Byte yes yes 16 DC 500V 35mA 5.5W green LED per channel DC 24V 15 ... 28.8V 0 ... 5V 7mA 3ms 3ms possible 1.5mA
3-6
11000000