Voltech Power Supply Measurements

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements

Table of Contents

Measuring power supplies ....................................................................................3 The key to Measuring Volts, Amps and Watts: .....................................................5 RMS (Root mean squared value)..........................................................................6 Average value .......................................................................................................8 Real and apparent power (W & VA)......................................................................8 Power factor........................................................................................................10 Peak Inrush Current............................................................................................11 Crest factor .........................................................................................................12 Harmonic distortion .............................................................................................12 Voltech Harmonic analysis:.................................................................................13 Flicker .................................................................................................................14 What types of Power Supply ...............................................................................15 Voltech Power Analyzer Range ..........................................................................16 Voltech Power Analyzer Comparisons................................................................17

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements

Measuring power supplies


Power supplies convert electrical energy as efficiently as possible with constraints of practical components and compliance to international standards such as FCC part 15 for EMC, UL and CE for safety and IEC61000-3-2 (harmonics) and IEC61000-3-3 (flicker). Power supply types cover a vast range of applications from microwatts (plug top chargers) to megawatts (large inverter systems for example). Using a power meter capable of analyzing complex waveforms having high bandwidth and accuracy is essential to designers, production and QA. If a complex waveform is not correctly represented in measurements misleading results may result.

Critical Power Supply Measurements Parameter Volts RMS Amps RMS Line regulation, drop out voltage, testing power fail circuits Critical for Power meter essentials
True RMS measurements made with high frequency waveform sampling

Input and output power Power consumption and efficiency

Non linear current and voltage sampled and averaged to provide RMS Watts, - the equivalent dc heating effect

VA VRMS x ARMS

Total (apparent) demand, for power factor measurement

Measurement is independent of phase between voltage and current

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements


Apk Max (Inrush Current)
Typical inrush waveform. Inrush current is the current that flows when a circuit is first energized. Switching occurs at the highest current.

Qualified fuse rating Limiting circuit design Verification of inrush

PF (Power Factor)

Required for compliance Optimizes use of available voltage and current

Power factor =

Real Power Apparent Power

CF (Crest Factor) Analyzing current waveforms with high peak value

Instruments with high crest factor measurement capability are able to analyze these typical switch mode waveforms

THD (Total Harmonic Distortion) Integrator W-Hrs A-Hrs

Required to analyze the effect of non linearitys

Powerful DSP analysis capability for accurate measurement of THD Integrator function for Watts, VA and current

Low Power standby measurements Energy consumption measurements

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements


Standby Power A year 2000 study in the US claimed that standby power accounted for around 10% of household powerconsumption ($6 billion) Shown here an IEC62301 test report
Example of results from automated PC software showing harmonic series

Requirement of Energy Star and IEC62301

IEC61000-3-2 (Harmonics) Required to meet IEC standards CE marking

IEC61000-3-3 (Flicker) Required to meet IEC standards CE marking


Example of results automated PC software for flicker measurement

The key to Measuring Volts, Amps and Watts:


Power Supplies connected to the AC line generally draw distorted, non-linear currents. Many AC voltage and current meters respond to the average value of a waveform and although calibrated in RMS are only accurate for pure sine waves. Voltech power analyzers obtain RMS values by taking a large number of instantaneous voltage and current samples over many cycles of the voltage and current waveform. The true RMS value is obtained even for highly distorted waveforms. Voltech power analyzers are ac and dc coupled to be able to make accurate power measurements over all frequencies and wave shapes.

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements


Phase and amplitude samples of current and voltage are the fundamental building block for algorithms to derive the many parameters needed to characterize power supplies. Measuring input and output power provides an efficiency specification for the power supply. High efficiency measurements demand high accuracy of input and output power measurements. Power supplies are generally characterized for normal operating power and standby power (equipment with power continually applied but turned off by electronics). Current drawn will be non-linear making it essential to measure True RMS current and voltage

The current and voltage waveform from a typical switched mode power suppy shown here. A power analyzer with high frequency sampling is essential to accurately measure all essential design parameters including RMS power, power factor, harmonics and flicker etc.

RMS (Root mean squared value)


The RMS value is the most commonly used and useful means of specifying the value of both AC voltage and current. The RMS value of an AC waveform indicates the level of power that is available from that waveform and is equivalent DC at the same voltage. This is one of the most important attributes of any AC source. The calculation of an RMS value can best be described by considering an AC current waveform and its associated heating effect such as that shown in Figure 1a below.

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements

If this current is considered to be flowing through a resistance, the heating effect at any instant is given by the equation:

W = I 2R
By dividing the current cycle into equally spaced coordinates, the variation of the heating effect with time can be determined as shown in Figure 1b above. The average heating effect (power) is given by:

W=

2 2 I 12 R + I 2 R + I 32 R K + I n R n

If we wanted to find the equivalent value of current that would produce the average heating effect value shown above, then the following applies:

I 2R =
Therefore:

2 2 I 12 R + I 2 R + I 32 R K + I n R n

I=

2 2 I 12 + I 2 + I 32 K + I n n

The RMS value of the current = the square root of the mean of the squares of the current. This value is often termed the effective value of the AC waveform, as it is equivalent to the direct current that produces the same heating effect (power) in the resistive load. It is worth noting that for a sinusoidal waveform:

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements


RMS value = peak value 2 i.e. RMS = 0.707 peak value

Average value
The average value of a waveform such as that shown in Figure 2 is given by:

Average value =

Area enclosed by one half cycle Length of base over one half cycle

It is clear the average value can only have real meaning over one half cycle of the waveform since, for a symmetrical waveform, the mean or average value over a complete cycle is zero. Most simple multimeters determine AC values by full-wave rectification of the AC waveform, followed by a calculation of the mean value. Such meters, however, will be calibrated in RMS and will make use of the known relationship between RMS and average for a sinusoidal waveform, i.e.

RMS = 1.11 mean


However, for waveforms other than a pure sinewave, the readings from such meters will be invalid. RMS values will need to be calculated using techniques shown above in Fig 1.

Real and apparent power (W & VA)


If a sinusoidal voltage source of, say, 100V RMS is connected to a resistive load of, say, 100ohms, then the voltage and current can be depicted as in Figure 3a and are said to be in phase. The power that flows from the supply to the load at any instant is given by the value of the product of the voltage and the current at that instant, as illustrated in Figure 3b.

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements

From this, it can be seen that the power flowing into the load fluctuates (at twice the supply frequency) between 0 and 200W and that the average power delivered to the load equals 100Wwhich is what one might expect from 100V RMS and a resistance of 100ohms. However, if the load is reactive (i.e. contains inductance or capacitance as well as resistance) with an impedance of 100ohms, then the current that flows will still be 1A RMS but will no longer be in-phase with the voltage. This is shown in Figure 4a for an inductive load with the current lagging by 60 degrees. Although the power flow continues to fluctuate at twice the supply frequency, it now flows from the supply to the load during only a part of each half cycleduring the remaining part, it actually flows from the load to the supply. The average net flow into the load, therefore, is much smaller than in the case of a resistive load as shown in Figure 4b with only 50W of useful powering delivered into the inductive load.

In both of the above cases the RMS voltage was equal to 100V RMS and the current was 1A RMS. The product of these two values is the apparent power delivered into the load and is measured in VA as follows:

Apparent Power = VRMS ARMS


The real power delivered has been shown to depend on the nature of the load. It is not possible to determine the value of real power from the knowledge of RMS voltage and

Voltech 2011

VPN 104-161-0-05W

Power Supply Measurements


current. This can only be achieved (e.g., for assessing heat loss or efficiency) through the use of a true AC power meter, capable of computing the product of the instantaneous voltage and current values and displaying the mean of the result. VA is often measured to ensure that the ac supply has sufficient capacity PF includes effect of harmonic as well as phase distortion. Confirms operation of a PFC circuit.

Power factor
It is clear that, in comparison with DC systems, the transferred AC power is not simply the product of the voltage and current values. A further element, known as the power factor must also be taken into consideration. In the previous example (real and apparent power) with an inductive load, the power factor is 0.5 because the useful power is exactly one half of the apparent power. We can therefore define power factor as:

Power Factor =

Real Power Apparent Power

In the case of sinusoidal voltage and current waveforms, the power factor is actually equal to the cosine of the phase angle () between the voltage and current waveforms. For example, with the inductive load described earlier, the current lags the voltage by 60 degrees. Therefore:

PF = cos = cos 60 = 0.5


It is for this reason that power factor is often referred to as cos. It is, however, important to remember that this is only the case when both voltage and current are sinusoidal [Figure 5 (I1 and I2)] and that power factor is not equal to cos in any other case [Figure 5 (I3)]. This must be remembered when using a power factor meter that reads cos, as the reading will not be valid except for pure sinusoidal voltage and current waveforms. A true power factor meter will compute the ratio of real to apparent power as described in section discussing real and apparent power.

Voltech 2011

10

VPN 104-161-0-05W

Power Supply Measurements

Voltech power meters retain high accuracy even at very low power factor, which is very important for product characterization and development.

Peak Inrush Current


Inrush is important for: Correctly specify I2t rating of fuses and circuit breakers. Determine peak current rating required for rectifier diodes etc. Determine effect of the inrush current on the a.c. supply Inrush may also be significant after switch on during a power interruption. This may be a critical condition due to the fact that components used to limit inrush at switch on may not be effective at the point of power interruption. The Voltech PS1000 solid-state switch controls the turn-on of an AC supply to allow accurate measurement of the inrush current into an AC load. It is designed for use with Voltech power analyzers A push-button switch on the PS1000 front panel allows the turn-on point of the AC supply to be selected between the zero crossing or peak value of the AC voltage waveform. Trigger point accuracy for supply frequencies in the range from 40Hz to 440Hz is automatically maintained by a phase-locked loop in the unit. A fully isolated trigger output is provided on a rear-panel BNC connector, so that other equipment, such as a storage oscilloscope, can be triggered when the PS1000 turns the AC supply on. Selfpowered from the AC supply that it controls, the PS1000 connects directly into the load circuit via 4mm safety sockets on its front panel. It is housed in a fully insulated, impact resistant ABS case.

Voltech 2011

11

VPN 104-161-0-05W

Power Supply Measurements


Inrush setup

Typical inrush waveform

Crest factor
Voltech power analyzers can measure a high Crest Factor (~20). This is critical for characterization of switched mode power supplies, which usually have high peak current draw. It has already been shown that for a sinusoidal waveform:

Peak value = RMS 2


The relationship between peak and RMS is known as the crest factor and is defined as:

Crest factor =
Thus, for a sinusoid:

Peak value RMS value

Crest factor = 2 = 1.41


Many items of modern equipment connected to the AC supply take non-sinusoidal current waveforms. These include power supplies, lamp dimmers, and even fluorescent lamps. Power supplies can often exhibit a current crest factor of around 4 and sometimes up to 20.

Harmonic distortion
If a load introduces distortion of the current waveform, it is useful, in addition to knowing the crest factor, to quantify the level of distortion of the wave shape. Observation on an oscilloscope will indicate distortion but not the level of distortion. It can be shown by Fourier analysis that a non-sinusoidal current waveform consists of a fundamental component at the supply frequency plus a series of harmonics (i.e.

Voltech 2011

12

VPN 104-161-0-05W

Power Supply Measurements


components at frequencies that are integral multiples of the supply frequency). For example, a 100Hz square wave consists of the components shown in Figure 7. A square wave is clearly very distorted compared to a pure sine wave. However, the current waveform drawn by, for example, a SMPS, a lamp dimmer or even a speed-controlled washing machine motor can contain harmonics of even greater significance. Figure 8 shows the current drawn by a popular SMPS model together with the harmonic content of that current.

The only useful current is the fundamental component of current, as it is only this that can generate useful power. The additional harmonic current not only flows within the power supply itself, but in all of the distribution cables, transformers and switchgear associated with the power supply and will thus cause additional loss. There is an increasing awareness of the need to limit the level of harmonics that equipment can produce. Controls exist in many territories to provide mandatory limits on the level of harmonic current permitted for certain types of load. Such regulatory controls are becoming more widespread with the use of internationally recognized standards such as EN61000-3. Thus, there is a need for an increased awareness amongst equipment designers as to whether their products generate harmonics and at what level. It is only the fundamental which generates power, harmonics in general do not.

Voltech Harmonic analysis:


The Voltech PM6000 and PM1000+ have automated PC software to measure IEC61000 harmonics and flicker. The PM1000+ is capable of pre compliance testing whereas the PM6000 is capable of full compliance testing and is used extensively in compliance test laboratories. Voltech can perform dual harmonic measurement (input and output) simultaneously, important for performance testing.

Voltech 2011

13

VPN 104-161-0-05W

Power Supply Measurements


The following is a real time harmonic display:

Example of harmonic results from automated PC software Voltech employ a DFT (Discrete Fourier Transform) for DSP harmonic analysis as required by the IEC61000 standards There are significant advantages using a DFT compared with conventional FFT algorithms used by competitors. A DFT provides accurate measurements without the uncertainty for synchronizing waveforms. Voltech analyzers have greater computing power required by this type of algorithm. Also, if an FFT is used it accumulates errors; with a DFT errors are the same for each order.

Flicker
Voltech automated flicker testing employs a reference impedance network required by the standards, a typical result is shown below. Voltech have been producing a fully compliant reference impedance network for many years.

Example of flicker results from automated PC software

Voltech 2011

14

VPN 104-161-0-05W

Power Supply Measurements

What types of Power Supply


Designs generally fall into two categories, either linear or switched mode. In general switched mode power supplies are used in high efficiency applications such as computers and wall chargers. They are also compact and inexpensive Linear power supplies are generally chosen where the output (and possibly input) needs to be very clean (low EMI/EMC) and low noise. However they are inefficient and bulky. Inverters There is significant interest in micro- to large-scale inverters for solar power applications, taking DC from a PV (Photo voltaic) cell and converting this to single or multiphase AC for grid connection. There are some special considerations for standards compliance and measurement of inverter systems covered in Voltech applications notes. LED Drivers Also, power supplies (drivers) for LED (Light Emitting Diode) lamp systems have many topologies with the driving force being low cost and high efficiency. Often the output voltage is AC or rectified DC with PWM (Pulse Width Modulation) control for brightness. Click here for details.

Voltech 2011

15

VPN 104-161-0-05W

Power Supply Measurements

Voltech Power Analyzer Range

All Voltech power analyzers feature fully isolated voltage and current inputs for direct connection to the product under test. A broad range of current transducers plus an inrush current waveform switch can be used with the analyzers to extend their range from milliwatts to megawatts. Call for detailed information or a free one-week evaluation. Lab view drivers are also available.

Voltech 2011

16

VPN 104-161-0-05W

Power Supply Measurements

Voltech Power Analyzer Comparisons

Analyzer
Product No of Input Channels Basic Power Accuracy (50/60 Hz) Power Frequency Range Voltage Ranges PM1000+ 1 0.05% of Reading DC and 10 Hz to 1MHz 900/215/46/10Vpk PM300 3 0.1% of reading DC and 5Hz to 50KHz 7.5/15/30/60/120/24 0/480/1000 Vpk Direct input 0.1/0.3/0.9/2.7/8.1/2 4.3/72.9/200 Apk External shunt 12.5mV RMS to 2.0V pk LCD Harmonics to 50th Datalog to PC RS232, IEEE, parallel printer VPASlite for data logging and remote operation PM3000ACE-001 3 0.05% of Reading DC and 0.1Hz to 500 kHz 0.5 to 2000Vpk, 12 ranges in 1-2-5 sequence Direct 30ARMS 0.05A to 200Apk in 12 ranges in 1-2-5 sequence External shunt 6.25mVRMS to 2.5Vpk Single display 7 segment LED Harmonics to 99th Datalog to PC IEEE or RS232 and parallel printer VPAS software, IEC61000-3-3 Flicker, torque and speed PM6000 1 to 6 (selectable when purchasing) 0.02% of Reading DC to 1MHz (30A shunt) and 10MHz (1A shunt) 5/10/20/50/100/200/50 0/1000/2000Vpk 1A shunt: 0.01/0.02/0.05/0.1/0.2/ 0.5/1.0/2.0/5.0Apk, 30A shunt: 0.5/1/2.5/5/10/20/50/10 0/250Apk External shunt: 2.5Vpk max VGA Display Harmonics to 99th Internal 6Mbytes, optional hard drive and datalog to PC Ethernet, RS232, parallel printer port Compliant Automatic PC software for IEC61000-3-2 harmonics and IEC61000-3-3 flicker, External VGA monitor, 1 or 30 Amp Shunts, Torque and speed, VPAS software

Current Ranges

Direct input: 100,25,6.25,1.6,0.4,0. 1 Apk

External shunt Display Type Harmonics Storages

External 1250mVpk 6.4 inch color TFT LCD Harmonics to 50th USB flash drive option and datalog to PC USB(master/host) or RS232, IEEE optional Pre compliance Automatic PC software for IEC61000-3-2 harmonics and IEC61000-3-3 flicker, inrush current, Ballast transformer and remote operation

Interface

Optional Features

Voltech 2011

17

VPN 104-161-0-05W