You are on page 1of 11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

Considerations for Power Transformers Applied in Distributed Photovoltaic (DPV) - Grid Application*

By Task Force for DPV-Grid Transformers Power Transformers Subcommittee, IEEE-Transformer Committee

_____________________________________________________________________________ *Photovoltaic transformers addressed in this paper belong to the Class I category with the present maximum voltage level of 33 kV and a present maximum capacity of 5 MVA.

Copyright 2011 IEEE. All rights reserved. This is an unapproved draft of IEEE Task Force position paper, subject to change.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

Participants

The members of the Task Force on DPV Grid Transformers prepared this paper. At the time of its completion, the task force had the following membership: Hemchandra M. Shertukde, Chair Mathieu Sauzay, Vice Chair Aleksandr Levin, Secretary

Donald Ayers Enrique Betancourt Paul Boman Bill Chiu Philip Hopkinson CJ Karla Thomas Lundquist Amitav Mukerji Sanjay Patel Marnie Roussell Dinesh Sankarakupur Stephen Schroeder Sanjib Som Craig Stegemaier Subhash Tuli Kiran Vedante JaneAnn Verner Joe Watson Jennifer Yu Kipp Yule

Copyright 2011 IEEE. All rights reserved. This is an unapproved draft of IEEE Task Force position paper, subject to change.

Abstract: Keywords:Voltage flicker / Variation; Harmonics / Wave form distortion; Frequency Variation; Power Factor (PF) variation; Safety/ Protection; Islanding; Relay Protection; DC Bias; Thermo cycling; Power quality; Power Storage; Transients; Magnetic Inrush Current; Eddy Current and Stray losses; Design Considerations; Special Test Consideration. 1. Introduction Distributed Photovoltaic (DPV) Grid Transformers (DPV-GT), that are the solar energy converters step-up transformers, are gradually increasing in their numbers in the field due to the recent focus on renewable energy sources. In the case of the photovoltaic solar power, electrical power is generated by converting solar radiation into direct current electricity using semiconductors that exhibit the photovoltaic effect. Photovoltaic power generation employs solar panels comprising a number of cells containing a photovoltaic material. The dc energy is then converted to a 3-phase ac power using an inverter. The inverter is subsequently connected to a DPV - Grid Transformer (DPV-GT). This DPV-GT is further connected to a bus which can feed a suitable load. The following diagram illustrates the process of conversion of energy from solar radiation into usable electrical power.

BUS SUN Solar panel


INV

DPV-GT

L O A D

Figure 1. A typical one line diagram is shown with the solar panel connected to an inverter which is in turn connected to a DPV-GT, a bus and further down to a load. This Task Force was formed to investigate the application considerations of power transformers as relates to the DPV-GT installations. Some key design, operation, and maintenance aspects to be considered are listed below: 1) Islanding 2) Voltage flicker Revision 5
April 6, 2011

3) Voltage operating range 4) Frequency variation 5) Waveform distortion 6) Power factor variation 7) Safety and protection functions Currently there exist a variety of available industry standards that address many of these design, operation, and maintenance aspects. The objective of this paper is to summarize the findings of the Task Force and identify potential gaps if any.

Revision 5
April 6, 2011

Subsequently on the recommendation of the membership of this TF (IEEE TC meeting in Miami, FL, Houston, TX and Toronto, ON), a matrix of individual items for investigation of IEEE and IEC standards was created as shown below:

Std 1547.4

C57.18.10

Item #

Salient Feature

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Voltage flicker / Variation Harmonics / wave form distortion (losses, power rating) Frequency Variation Pf variation Safety/protection Related to public Islanding Relay Protection DC Bias Thermo cycling (loading) Power quality Power Storage Voltage Transients (insulation coordination) Magnetic Inrush current Eddy Current and Stray losses Design ConsiderationsInside/Outside Windings Special tests consideration Assigned individual

~ X ~ X X X X X

X X

X X X X X X

X X

X ~ X X X X X X X X ~ X X X X X MS HMS SAL CJK SKS EBR JV X X X X X X X X

JV

Table 1. Assignments for IEEE Standards Investigation * This table shows that, at this stage and unless we discover new subject to be addressed, no subject is totally uncovered. 2. Existing Standards and areas of the differentiation of DPV-GT. 2.1. Voltage Flicker / Variation - C57.91 [2], Std. 519 [10], Std. 1547.4 [7], UL 1741 [8], Std. 519 [10] - Solar transformers operate at a steady voltage, with the rated voltage controlled by inverters. Therefore, voltage and load fluctuations are considerably reduced. The voltage variation is generally in the range of +-5% of the nominal voltage rating. Thus standard design considerations for transformer windings are readily applied from experience. IEEE 519-92 Table 10-2 establishes limits for allowable commutation notch depth introduced by power converters at
critical points of the power system, normally coincident with points of transformer allocation. - IEEE 519-92, Table 10-2 establishes limits for an allowable commutation notch depth introduced by power converters at critical points of power system, normally coinciding with the points of transformer location.

Revision 5
April 6, 2011

UL 1741 X X X X X X X X X X X X

C57.110

C57.129

C57.116

Std 519

C57.91

2.2. Harmonics / Wave Form Distortion - C57.18.10 [3], C57.110 [4], C57.129 [6], Std. 519 [10], Std. 1547.4 [7], UL 1741 [8], Std. 519 [10] - The solar inverter system's typical harmonic content is less than 1 percent, which has almost no impact on the system. The lower harmonic profile is because there are no generators and switching and protective controls such as those found on wind turbines. - C57.129 standard sufficiently describes the requirements to the system designer to provide information on the harmonic content and the current waveform, including the cases where there is more than one valve winding on a core leg. - C57.129 and C57.18.10 standards use a definition of kVA rating based only on the fundamental frequency, additional losses due to the harmonic content are taking into account during heat-run test. - IEEE 519-92 establishes limits for allowable harmonics levels in power systems. Table 10-3 sets current distortion Limits for General Distribution Systems (120 V Through 69 000 V), as a function of the short circuit ratio and the harmonics order. In case a significant harmonic content in DPV-GT, please refer to C57.110, which is an IEEE Recommended Practice to establish a transformer capability when supplying non-sinusoidal load current. 2.3. Frequency Variation - C57.110 [4], C57.91 [2], C57.116 [5], Std. 1547.4 [7], UL1741 [8] Since the frequency variation can come from the network only, therefore no difference to a standard power transformer is expected to be made in its design and manufacture.. 2.4. Power Factor (PF) Variation - C57.110 [4], C57.91 [2], Std. 1547.4 [7], UL 1741 [8] No significant difference with standard power practices is expected. C57.110 ( 5.3Power factor correction equipment) - Power factor correction equipment is frequently installed to decrease utility costs. Care should be taken when this is done, since current amplification at certain frequencies due to resonance in the circuit can be quite high. In addition, the inductance which is reduced in the circuit generally allows higher harmonic currents to exist in the system. Harmonic heating effects from these conditions may be damaging to transformers and other equipment. The additional losses produced may also increase utility costs due to increased wattage requirements, even though the load power factor was improved. 2.5. Safety / Protection Related to Public C57.129 [6], Std. 1547.4 [7], UL 1741 [8] - If residential and industrial (non-distributed) PV systems are covered with this white paper, the safety requirements can have specific features compare to the ones for power transformers, especially when it comes to the residential application. - C57.129 the converter transformer pollution aspects are extremely important and shall be accurately defined, so that proper external insulation (particularly bushings) may be provided. 2.6. Islanding - Std. 1547.4 [7], UL 1741 [8] In this conditions, when the system is functioning, but is not connected to the high inertia network, then the system could be less stable and the subject of the frequency variation, but no significant differences with the standard transformers are expected.

Revision 5
April 6, 2011

2.7. Relay Protection - UL 1741 [8] 2.8. DC Bias - C57.110 [4], UL 1741 [10] C57.110 ( 4.1.4 DC components of load current) - harmonic load currents are frequently accompanied by a dc component in the load current. A dc component of load current will increase the transformer core loss slightly, but will increase the magnetizing current and audible sound level more substantially. Relatively small dc components (up to the rms magnitude of the transformer excitation current at rated voltage) are expected to have no effect on the load carrying capability of a transformer determined by this recommended practice. Higher dc load current components may adversely affect transformer capability and should be avoid. 2.9. Thermo Cycling (Loading) - C57.91 [2], Std. 1547.4 [7], UL 1741 [8] - In most of the geographical locations in the United States solar power facilities experience a steady state loading when inverters are operating. When the sun comes out, there is a dampened reaction process and loading on the transformer is more constant. The entire process is controlled by the isolation number in a particular location. The no-load operation of such transformers is completely controlled by different set of parameters. - Nominal loading average - Solar power systems typically operate very close to their rated loads. Since the load variation from the rated value is appreciably low, the operation of transformers is not adversely affected to cause deterioration of parameters that guide the insulation coordination of the core-coil structure. Thus forces experienced by the primary and secondary windings are not out of the ordinary, thus alleviating problems that may occur in the design of the mechanical structure. - Note on the no-load operation: PV system transformers are subject to long-term no-load operation conditions, at least at night. This might have an impact on loss capitalization, that customer usually take into account, but also on the transformer design. The storage battery interaction with the transformer in PV system may control the load consistency and alleviate the perceived problems. - C57.129 standard requires a detailed thermal study, if transformer or some of the terminals operate above rated capacity. Standard power transformer loading tables should not be used for loading determination because of the effect of the harmonic currents and dc bias on the valve windings (for the HVDC converter transformers). Even with the loss correction addressing the harmonic content during the heat run, the hot spot temperature may not be representative of the real conditions due to the nature of the harmonic current distribution in the winding and how its different during the heart run. extended load run with overload is recommended by CIGRE Joint Task Force 12/14.10-01 for the HVDC converter transformers. 2.10. Power Quality - C57.18.10 [3], C57.110 [4], C57.129 [6], C57.116 [5], Std. 519 10], Std. 1547.4 [7], UL 1741 [8] Power quality aspects are generally addressed in other sections of this positionpaper. 2.11. Low Voltage Fault Ride Through - Fault ride through has yet to be defined for solar systems, this could be because it is easier to turn solar power systems on and off quickly. Revision 5
April 6, 2011

2.12. Power Storage UL 1741 [8] Battery storage impact will depend on the kind of system the DPV-GT is serving in a particular geographic environment. 2.13. Voltage Transients and Insulation Coordination - C57.110 [4], C57.129 [6] - Generator step-up duty - With solar transformers, step-up duty is required, but without the problems associated with over-voltages caused by unloaded generators. The inverter converts DC input from the photovoltaic array and provides AC voltage to the transformer, giving a steady and smooth transition, with no over-voltage caused by unloaded circuits. All general installations covered under this application have in their system considerations much attention paid to the over-voltage conditions. This problem is addressed by providing an Automatic Gain Control scheme to the inverter circuit configuration. - C57.129 standard provides the specific recommendations on the insulation test levels for the converter transformers. The development of the similar recommendation would be appropriate for insulation test levels and procedures required to warrantee the reliability of the transformers in the PV application. 2.14. Magnetic Inrush Current Std. 1547.4 [7], UL 1741 [8] Transformers experience a high current inrush when energized from a de-energized state. The inrush current is typically several times the rated current. The magnitude of the inrush current is determined by a variety of factors defined by the transformer design. The inrush current, when compared as a multiple of rated current, is generally much higher when the energization takes place from the LV side. That is due to the fact that the LV winding is generally the winding that is closest to the core and therefore has a lower air core reactance. Since the inrush current is several times rated current, each inrush event creates mechanical stresses within the transformer. Frequent energization from a de-energized state should be avoided since it wears down a transformer faster than normal. That can be a consideration for a DPV step-up transformer since the operators could consider saving energy by shutting down the transformers during the night. Such a practice can shorten a transformers life expectancy. 2.15. Eddy Current and Stray Losses - C57.18.10 [3], C57.110 [4], C57.91 [2], C57.129 [6], Std. 1547.4 [7] - Eddy currents and stray losses are present in every transformer. The primary stray and eddy losses are due to the 60 HZ frequency currents. These loss components increase with the square of the frequency and square of the magnitude of the eddy currents. If the inverter feeding the power into the step-up transformer is producing more than the standard level of harmonics, then the stray and eddy losses will increase. The increase in load loss effect on efficiency is not typically a concern. Of much greater concern is the increased hot spot temperature in the windings that can reduce the transformer life. A special design transformer can compensate for the higher stray and eddy losses. Also, a larger than necessary kVA transformer can be selected to compensate for the higher operating temperatures. However, these concerns on eddy current loss increasing generally mitigated since harmonic less than 1%.. - C57.129 the user shall clearly indicate the method to be used for evaluating of the guaranteed load losses. The harmonic spectrum to be used for load loss evaluation shall be clearly identified. This spectrum may be different from the one specified for the temperature rise tests; the latter Revision 5
April 6, 2011

represents the worst case operating conditions. A harmonic correction is added to the measured sinusoidal load losses as part of the calculation of the appropriate total loss value for the temperature rise test. The procedure to determine the total load losses is described in the standard. Informative Annex A gives the method of determination of a loss adjustment factor . 2.16. Design Considerations- Inside/Outside Windings - C57.110 [4], C57.110 [4], C57.116 [5], C57.129 [6] - The design considerations for windings are dependent on the issues in the previous items listed. The design considerations to meet the special requirements depend on the manufacturers construction, kVA size, voltage and other factors.Since inverter technology limits the size of the inverter, there may be multiple inverters at each solar station. Some users would consider having multiple LV windings in a single transformer with each LV winding connected to an inverter. Design considerations such as impedance and short circuit cause multiple LV windings to create a much complex transformer. Additional complexity will increase cost and reduce availability of the transformer. It is advisable to keep a transformer as simple as practical so that it can be a mass produced and could be built by as many manufacturers as feasible. - In many cases the limit of the kVA on the inverter circuits forces some of the designs to incorporate the LV windings to be disposed outside the HV windings. This enables easier connections to facilitate paralleling of circuits to achieve higher kVA rating for the entire transformer under consideration. This helps to alleviate some of the problems faced due to the constraints. 2.17 Special Tests Consideration C57.129 [6] - C57.129 Extended load run with overload; Other power testing concepts and methodologies; Specifics for the transformers used with voltage source converters. In addition to the tests, design review is recommended. 2.18. Special design consideration. - Solar power systems use inverters to convert DC to alternating current (AC). Since the largest practical inverter size, to date, is about 500 kilovolt-ampere (kVA), designers are building 1000 kVA transformers by placing two inverter connected windings in one box. In this way the transformer has to have two separate windings to accept completely separate inputs. Design issues also stem from running cables long distances to convert from DC to AC. 2.19. Other aspects. - Connection diagram what are the standard connections of the PV application transformers? - Shielding requirements (electrostatic shielding, protective shielding, harmonic filtration shielding). - Inverter Technology - inverter technology has been slow to advance, because it is an electronic technology. It remains to be seen whether this comparative disadvantage will be a fatal flaw in the advancement of solar technology to the same level as wind farms in the renewable energy arena . -- Size of installation - the size of solar farm is limited by inverter technology, since inverters can currently only be built to about 500 kVA. This means that nearly all solar applications use pairs of 500 kVA inverters to drive the transformer and produce about 1000 kVA. Increasing the size by adding more inverters into one transformer box is extremely difficult, due to complexities Revision 5
April 6, 2011

associated with the size of the box required and the practicalities of running cabling to convert from DC to AC. 3. Discussion Some core needs of a DPV-GT are:

Efficient heat management: The heat generated due to uneven cooling of the coils leads to creation of hot spots. This leads to premature breakdown of the transformers Lower harmonics and grid disturbances Ability to withstand harsh weather conditions, temperature, seismic levels, etc. (HMS).

If necessary, DPV-GTs are designed and constructed to meet and exceed earthquake standards, Sometimes DPV-GT is rated for installation in the highest earthquake rating zones. In addition, it can incorporate a variety of fluids, including less flammable fluids required for enclosed applications. DPV grid step-up transformer is especially designed to meet the solar industry's need for reliable service in remote locations, and should offer advanced fault survivability. 4. Conclusions DPV-GT solar converter step-up transformer is uniquely designed to connect solar farms to the electricity grid at large-scale solar power installations. Reliable and efficient, step-up transformers are engineered solutions with the necessary design flexibility needed for the solar industry. The DPV-GT is designed for the additional loading associated with non sinusoidal harmonic frequencies often found in inverter-driven transformers, and the design with multiple windings shall be considered in case it can reduce transformer cost, minimize a transformer footprint and provide required functionality. The shell type transformers can be also considered for this application. The duty cycle seen in solar farms may not be as severe as seen in wind farms, but solar power has its share of special considerations that affect transformer design. Those engaged in harnessing solar energy need to pay heed to these special needs to ensure that the solar installation is cost effective and reliable. . 5. References [1] Considerations for Power Transformers Applied in Distributed Photovoltaic (DPV) - Grid Application, DPV-Grid Transformer Task Force Members, Power Transformers Sub Committee, IEEE-TC, Hemchandra M. Shertukde, Chair, Mathieu Sauzay, Vice Chair, Aleksandr Levin, Secretary, Enrique Betancourt, C J Kalra, Sanjib K Som, Jane Verner, Subhash

Revision 5
April 6, 2011

Tuli, Steve Schroeder, Bill Chu, white paper in preparation for final presentation at the IEEE-TC conference in San Diego, Ca, April 10-14, 2011. [2] C57.91: IEEE Guide for Loading Mineral-Oil-Immersed Transformers, 1995, Correction 12002 [3] C57.18.10a: IEEE Standard Practices Requirements for Semiconductor Power Rectifier Transformers, 1998.ammend in 2008 [4] C57.110: IEEE Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability When Supplying Non-Sinusoidal Load Current, 2008 [5] C57.116: IEEE Guide for Transformers Directly Connected To Generators, 1989 [6] C57.129: IEEE Standard For General Requirements And Test Code For Oil-Immersed HVDC Convertor Transformer, 1999 (2007- Approved) [7] Std. 1547.4: Draft Guide For Design, Operation and Integration Of Distributed Resource Island Systems With Electric Power System, Only 1547.1 is there, 2005 [8] UL 1741: A Safety Standard For Distributed Generation, 2004 [9] David Buckmaster, Phil Hopkinson, Hemchandra Shertukde, Transformers used with Alternative Energy Sources - Wind & Solar,Technical Presentation, April 11, 2011 [10] Std. 519: Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, 1992

Revision 5
April 6, 2011

You might also like