Professional Documents
Culture Documents
W2102
W2102
network capability will change if some of its components are not available due to failure or maintenance. The capability assessment therefore needs to be conducted for a number of contingency scenarios for planning and managing the system. PV and QV curves are two most commonly used techniques to assess the capability of a network. These curves show the voltages of selected buses as functions of increased system load. The nose points of these curves are the system limit.
voltage
voltage QV curve
W2102
1. The amount of load increase should be gradually decreasing as one approaches the nose point. Namely, the incremental P becomes smaller and smaller. The purpose is to help one to zero in the nose point more accurately. 2. When solution diverges, don't record the results. The output results are not correct. 3. The PV curve plots V against P, although the system Q has also been changed in proportion to P. The exact name for PV curve should therefore be the SV curve. However, the terminology of PV curve has been accepted in industry. PV curve does not mean to increase P only. The QV curve method is a process to determine the QV curves of a network. A QV curve represents the system voltage behavior when increased reactive power is withdrawn from a bus called test bus. This is done by connecting a synchronous condenser (a generator with zero active power) to the test bus. The voltage setting of the condenser is decreased gradually, resulting increased withdrawal of reactive power from the network. There is a limit for the amount of reactive power that can be withdrawn. This limit is the nose point. The process of obtaining a QV curve is as follows: 1. Develop a solved load flow base case. 2. Select the test bus. Test bus is typically an important bus in the network. The need to select a test bus is one of the main drawbacks of the QV method. Record the test bus voltage. 3. Add a synchronous condenser to the test bus. A condenser has a zero P output. The voltage setting of the condenser is equal to the test bus voltage recorded in step 2. 4. Run the load flow. The case should be easily solved. Examine the output of the condenser. It should be zero for both P and Q. Save the case. 5. Decrease the voltage setting of the condenser by a small amount, say, 0.03pu. Run the load flow case. If the case is solved, record the Q output from the condenser. The output should be negative, indicating Q withdrawal from the system. Save the case. 6. If the case can not be solved, stop. Otherwise, repeat Step 5. The above process will result in a series of data points (V1, Q1), (Vn, Qn). Plot of the Q data versus V data is the QV curve. In the QV curve method, one only records and charts the voltage and reactive power output of the test bus.
Page 3
W2102
3.
Give the definitions of PV curve and QV curve. Why there is a "nose point" in these curves?
4. List at least four compensating devices or methods that can be used to maintain or to increase system voltage stability. Explain the advantages and disadvantages of each.
5. If the reactive power output from a generator reaches its limit, will the generator help voltage stability? Explain why.
Page 4
W2102
6. Plot qualitative PV curves for the following cases: 1) base case, 2) if a parallel line is added to an existing line, 3) if a shunt capacitor is added to the system, 4) if a series compensation is added to a line.
7. If a shunt capacitor is switched off in an industry plant, what could happen to the bus voltages? Use PV curve to explain your answer.
Page 5
W2102
The simulator has a special tool to scale cases. This function is illustrated here. Select Scale Case from Other Tools group in Tools ribbon, the following System Scaling dialog box will appear.
Scale Options
Total Load
There are several options to scale the cases: scaling the buses, areas, zones or super areas. In this lab, we scale the case on selected buses. As shown in the above figure, click Buses button, all available buses in the system appear in the table. Double click the cells in the Scale? column, no can be changed to Yes, indicating the bus has been selected for scaling. Select load buses 4, 6, 8 and 9. After selecting the buses, the total load attached to these buses will appear in Bus Load. Shown in the above figure, the original load MW of this lab is 9.99MW.
Page 6
W2102
Determine the scaling factor that you want to use. Enter that number is the Scale by field. The new load values will appear in the New Value field. In this lab, we dont scale up the generation in order to simplify the procedure. The following items need to be unchecked: Enforce Gen MW Limits Scale Gen to Keep ACE Constant Scale Only AGCable Generator and Load To keep changing both P and Q, check following item. Constant P/Q Ratio In the Option ribbon, select Simulator Options and set the Min. pu. volt for constant power load to 0.00. Also, check the item Initialize from Flat Start Values. (Why?)
Monitoring buses:
In this case, both real and reactive power load demand will be scaled up to determine the PV curve. This is done one step at a time using the Scale Case Tool of the program. Consult section 2.2 for more information. 1. Run base case to get the initial voltages at BUS #4, BUS#8 and BUS #9, which is the starting point when you draw the P-V curves. 2. Proportionally increase the total load demand (both active power and reactive power) by using the Scale Case Tool. The scaling factors to use have been listed in the following table. 3. Run power flow solution for the case. If it converges, save it as the starting point for the next step and record bus voltages. 4. Steps 3 and 4 are repeated until the case diverges, which means it cannot be solved. When the case diverges, the following window will appear:
Page 7
W2102
5. Fill in the following table. Draw P-V curves electronically for Bus#4, Bus#8 and Bus#9. These curves will be used as the base case for comparative studies in subsequent tasks. Scaling Factor Total Load (Real Power) MW 9.99 ( original load) 19.98 Voltage at Bus#4 Per unit Voltage at Bus#8 per unit Voltage at Bus#9 per unit
1.0 ( original load) 2.0 3.0 4.0 5.0 6.0 6.6 7 ...... ...... ......
Questions associated with this task: 1. Plot the PV curves obtained in this task and attach to your report. 2. Why software should initialize from flat start for this study?
3. The PV curves can be plotted for different buses. Do all curves have the same nose point? Why?
4. If only active power is scaled up in the process, one can get another set of 'PV' curves. Draw qualitatively (no simulation is needed, draw based on your theoretical expectation) the following two curves in one chart and explain the difference: the first curve is the standard PV curve, and the second curve is the PV curve with only P scaled up. Please remember that you have to find more scaling factors for active power by trial and error until the case diverges.
Page 8
EE433 LAB#3: Voltage Stability Assessment Task #2: Impact of Adding a New Transmission Line
Monitoring Buses: Case description:
W2102
BUS #4, BUS#8 and BUS #9 This case is the same as the case in Task#1 except that an identical parallel line is added between Bus#2 and Bus#4
In this case, a second transmission line identical to the line of Branch 4 will be put into operation between Bus#2 and Bus#4. This means the new impedance of Branch 4 is half of the original impedance of the branch 4. After making modifications to the case and solving it, save the case as a new base case. PV curves will be determined for this new case. Using the PV curve procedure, complete the following table. Scaling Factor Total Load (Real Power) MW Voltage at Bus#4 per unit Voltage at Bus#8 per unit Voltage at Bus#9 Per unit
1.0 (original load) 2.0 3.0 4.0 5.0 6.0 7.0 7.35 7.4235 Questions associated with this task: 1. What is impact of adding a parallel line to the system PV curve?
2. Why does adding a parallel line mean the line impedance is halved? If a line has a shunt admittance (the shunt branch of the common PI circuit for a line), what is the impact of adding a line on the admittance?
3. Are there other methods to reduce the line series impedance? (Name at least one)
Page 9
EE433 LAB#3: Voltage Stability Assessment Task #3: Impact of Reactive Power Capacity of the Co-generator
Monitored buses: Case description:
W2102
BUS #4, BUS#8 and BUS #9 This case is the same as the case of Task #1 except that there is a limit to reactive power output of the generator. This limit is 46.8 MVar.
Important notice: Before starting this task, check the PowerWorld Simulation Option to make sure that the reactive power limit of the generator will be taken into consideration by the Simulator. Uncheck the Disable Checking Gen MVAR Limits option, shown as follows:
The new case is created by setting the Qmax of the generator at bus #2 to 46.8 MVar. Shown in the following figure, 46.8 MVar is entered into the field Max Mvars of the generator record. After making modifications to the case and solving it, save the case as a new base case. PV curves will be determined for this new case.
Page 10
W2102
1.0 ( original load) 2.0 3.0 4.0 5.0 5.5 5.61 5.6661 Questions associated with this task: 1. Are there any differences in system voltages between the new base case of this study and the base case used in Task #1? Why?
3. Why does a generator have a limit for reactive power output (think your EE332 course)?
Make sure that the reactive power Limit of the generator will be taken into consideration. Make corresponding changes as you did in Task #3 before running the case. A new base case for this task is created by switching off of the capacitor at Bus #4 for the base case of Task #3. The capacitor can be switched off by a click on the attached switch (The switch will turn green when its in off status). After making modifications to the case and solving it, save the case as a new base case. PV curves will be determined for this new case. Using the PV curve procedure to complete the following table:
Page 11
W2102
Scaling Factor
1.0 ( original load) 2.0 3.0 4.0 5.0 5.5 Questions associated with this task: 1. Are there any differences in system voltages between the new base case of this study and the base case used in Task #3? Why?
2. What is the impact of disconnecting the capacitor on the reactive power output of the generator? Why?
3. What is the impact of disconnecting the capacitor on the system capability (i.e. PV curve limit)? Why?
4. If the generator has no reactive power output limit in this case, what can happen to the PV curve? Draw qualitative PV curves for the following cases: 1) case of Task 3, 2) case of Task 4 and 3) case of Task 4 but there is no reactive power limit for the co-generator.
5. Plot PV curves for Bus #4 obtained in Tasks #1, #2, #3, and #4 in one chart and attach to the report. Discuss the differences of the curves.
There are two approaches to get the Q-V curves: Approach 1: Connect a fictitious synchronous condenser on BUS #9, reduce voltage setting of the condenser gradually. Record the reactive power output and voltage setting of the condenser. Consult section 2.2 for more information. Scale up the reactive power load of Bus #9 gradually using the PV-curve-like procedure. Record the voltage and Q load of the test bus
Approach 2:
Page 12
W2102
Run power flow solution for the case one by one in both approaches. Complete the following table. Approach 1 Approach 2 Voltage setting at Reactive output in Reactive Scaling Voltage output Bus#9 synchronous condenser (MVar) MVar at Bus#9 per unit Initial voltage: 1.04013 From tested value (original reactive load) (0.98995) 0.95 20 0.90 50 0.85 80 0.80 100 0.75 120 0.70 140 0.65 160 0.63 170 0.62 180 0.61 181 0.60 0.58 0.56 Questions associated with this task: 1. Plot in one figure the curves obtained by both approaches. 2. Is there any difference between the two curves? Why?
3. Why is the starting point of approach #1, the voltage setting of the fictitious condenser, the same as the test bus voltage of the base case?
4. Discuss the advantages and disadvantages of each approach to obtain the QV curve.
6. Lab Report
The lab report should include the following items: 1. Answers to the pre-lab preparation questions. 2. Fully completed tables listed in Section 5. 3. Your responses to the questions listed in Section 5. Mark allocation of this lab is as follows:
All the students must participate in the lab. Pre-lab preparation: 20% Report including data preparation: 80%
Page 13