You are on page 1of 72

TICEL BIO PARK- II

ACMV WORKS

TICEL BIO PARK II


INTERNATIONAL COMPETITIVE TECHNO COMMERCIAL TENDER VOLUME 4 BILL OF QUATITIES PROVIDING SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF ACMV WORKS IN CONSTRUCTION OF LABORATORY COMPLEX TICEL BIO PARK II AT TARAMANI, CHENNAI (3 BASEMENTS+G+12 UPPER FLOORS) DUE DATE FOR SUBMISSION: ON OR BEFORE 28th July, 2011 at 15.00 Hours TO BE SUBMITTED TO: M/s.TICEL BIO PARK LTD (First Floor) CSIR Road, Taramani, Chennai - 600 113. Telephone No.: +91 44 22542061 Fax No: 91-44-2254 2055 E-Mail:ticel@vsnl.net

ENGINEERING CONSULTANTS: M/s .TAAMAESEK ENGINEERING CONSORTIUM Architects & Engineers No 5, 1 st Floor, Bishop Wallers Avenue West. Off TTK Road, Mylapore, Chennai- 600 004 INDIA. Tel No: 044-24671139 / 57 Fax No: 044-24672237 E-Mail: info@taamaesek.com OWNERS ENGINEERS: M/s.SPECTRAL SERVICES CONSULTANTS PVT LTD No.51, R.K.Mutt Road, Mylapore, Chennai - 600 004. TEL : +91 44 2461 3006 / 2461 8050 FAX : +91 44 2461 7956

TENDER SUBMITTED BY: M/s._________________________ Address_____________________ ____________________________ ____________________________

JUNE- 2011

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

TICEL BIO PARK-II ACMV WORKS AND OPERATION AND MAINTENANCE SUMMARY OF PRICES ABSTRACT - I S.NO 1 DESCRIPTION Cost of capital works ( Vide abstract -II) AMOUNT REMARKS

Cost of Operation

Cost of non comprehensive maintenance

GRAND TOTAL

Signature of Tenderer
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

TICEL BIO PARK-II ACMV WORKS -ABSTRACT-II S.NO 1 2 3 4 5 6 7 8 9 10 A B C D E F G H I J DESCRIPTION Service block plant room Trench header line for Phase 2&3 Ticel Bio Park-II-Main Building Car park ventilation system Fumigation system Faade ventilation system Ground floor and common area AHUs Lab typical floor BTCIF LAB AHUS Interior GRAND TOTAL C/o ABSTRACT-I AMOUNT REMARKS

Signature of Tenderer / Contractor


ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No A 1 SERVICE BLOCK-PLANT ROOM Supply, installation, testing and commissioning of (imported) Act.cap. of 340TR Brine Air cooled screw chillers, temp: 4 deg C leaving and 9 deg C entering condition, at normal mode and charging mode at - 5 deg C leaving and 0 deg C entering, chiller should able to run variable flow, VFD ( BMS compatible ), vibration Isolator and required adapotor box for cable termination, main disconect switch, Plant manager integerator (consider provision for five chillers), addtional pressure diff.sensor,.incoming adaptor box, flow swtich, grooved coupling coupling for inlet and outlet connection, Black Epoxy coated fins, Condensor fins covered with 12 guage SS316 mesh. compressor sound jacket using Armosound material required thickness with 22G Al cladding with suitable vibration isolator. Supply,installtion, testing and commissioning of 4500TRH Thermal staorge tank cooling capacity, with necessary isolation valves, comprising of BMS compatible ice inventory metering system with BTU meters, Sizing of tank as per manufacturer standard, Available space 1.8m height at first basement & second basement , Selection of tank as per site requirment with inclusives of required civil foundations. Supply,installation testing and commisioing of Plated type heatexchangers with extended stub flange and 12Gauge SS try,Transfering of heat from mono ethyline glycol 30% water solution to water for the following condition 1500TR, Brine side flow temp. 4 and 9deg C and water side flow temp 14 and 6 deg C selection of heatexchanger pressure difference 0.5bar Supply,installation, testing and commissioning of (imported) Endsuction long coupled base mounted for primay Brine air cooled chiller pumps with bronze impeller, capacity of 1020gpm@22m head with suitable insulation and 24g AL cladding. Description Qty Units
Unit Rate Supply Erection Supply Amount Erection

nos

set

nos

nos

Supply and installation of commissioning of suitable VFDs with indoor panel(cubical) with individual Isolator and required adapotor box for cable termination and each pump having a dp sensor and releated cabling between sensor to vfd - Brine primary pump(2 nos vfd + 2nos space provision )

set

Supply,installation testing and commissioning of (imported)Endsuction long coupled base mounted with bronze impeller for PHE brine side pumps, capcity of 3225 gpm@26m head with suitable insulation and 24g AL cladding.

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

1 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 7 Description Supply, installation and commissioning of comprising of suitable VFDs with indoor panel(cubical) with individual Isolator and required adapotor box for cable termination,each pump having a dp sensor/tempreature sensor and cabling between sensor to vfd - Phe brine side pump(3nos vfd+1No space provision) Supply, installation and commissioning of (imported) Endsuction long coupled base mounted with Bronze impeller for PHE water side pumps, capacity of 3202 gpm@26m head with suitable insulation and 24g AL cladding. Qty Units
Unit Rate Supply Erection Supply Amount Erection

set

nos

Supply, installation and commissioning of comprising of suitable VFDs with indoor panel(cubical) with indoor panel,each pumps is having pressure cum temprature sensor based vfd operation and related cabling between sensor to vfd - PHE water side pumps (3nos vfd + 1No Space provision)

set

10

Supply,installation and commissioning of (imported) double suction top discharge, long coupled base mounted for Secondary pumps with bronze impeller with , capacity of 3800 gpm@36m head with suitable insulation and 24g AL cladding. Supply,installation and commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination (3nos vfd+1No space provision) and pump prgram logic controller for pump operation, 3 nos of dp sensor and appx.1560 rmt related cabling and GI conduits Supply,installation and commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination for 7.5 kw (3nos vfd ) each VFD having 1no of dp sensor and related cabling from sensor to vfd, for existing chilled primary pumps & removal of existing starter panel & related cables and refixing of same cables for new VFD. Supply, installation and commissioning of commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination for 7.5 kw (3nos vfd ) each VFD having 1no of dp sensor and related cabling sensor to vfd for existing brine primary pumps & removal of existing starter panel & related cables and refixing of same cables for new VFD. Supply and installation of Pump Inertia base with spring of 20mm deflection

nos

11

set

12

set

13

set

14

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

2 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No a b c d 15 Chiller Brine primary pumps Chilled water Secondary pumps PHE pumps- Brine side PHE pumps- water side Supply,installation and commissioning of Butterfly Valve with extended stem of 100mm length, pressure rating of PN16, Suitable for pipes - SS wafer/stem for brine application, with insulation and 24g AL cladding 650 mm dia 600 mm dia 500 mm dia 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250mm dia 200mm dia 150 mm dia 100 mm dai qro 2 qro 4 34 8 qro qro 16 qro 74 nos nos nos nos nos nos nos nos nos nos nos Description Qty 2 3 3 3 Units nos nos nos nos
Unit Rate Supply Erection Supply Amount Erection

a b c d e f g h i j k

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

3 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No l 16 a b c d e f 17 a b c d e f 18 a Description 80 mm dia Qty qro Units nos


Unit Rate Supply Erection Supply Amount Erection

Supply,installation and commissioning of Swing type Non return Valve suitable for the pipes, pressure rating of PN16, with insulation and 24g AL cladding 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia qro 9 qro qro qro 2 nos nos nos nos nos nos

Supply, installation and commissioning of Metallic bellows suitable for pipes, pressure rating of PN16 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia Supply, installation and commissioning of Suction Guide suitable for pipes with pressure rating of PN16-with insulation and 24g AL cladding 450 mm dia qro nos qro 18 qro qro qro 6 nos nos nos nos nos nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

4 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia Qty 9 qro qro qro 2 Units nos nos nos nos nos
Unit Rate Supply Erection Supply Amount Erection

b c d e f 19

Supply,installation and commissioning of two way on/off motorised isolation valve suitable for pipes, with actuator 230v power supply,BMS compatible, pressure rating of PN16,suitable for brine application-with insulation and 24g AL cladding 650 mm dia 600 mm dia 500 mm dia 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia qro 2 qro 4 2 2 qro qro 1 nos nos nos nos nos nos nos nos nos

a b c d e f g h i

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

5 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No j 20 Description 150 mm dia Supply,installation and commissioning of Semi automatic Balancing valve suitable for pipes digital display, BMS compatible, suitable for 230 volt supply,pressure rating of PN16-with insulation and 24g AL cladding 500 mm dia 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia qro 2 2 qro qro 1 nos nos nos nos nos nos Qty qro Units nos
Unit Rate Supply Erection Supply Amount Erection

a b c d e f 21

Supply, installation of glycol/water mixing syntex tank of 2000 lits with 100mm thick rigid Puff insulation with 24g Al clading

nos

22

Supply,installation of glycol open expansion Steel tank of 5000 lits with related valve aux. with supports, 100mm thick rigid puff insulation with 20G GI galding with float valve arrangement

nos

23

Supply,installation of pressurised closed expansion tank with stand by motor and bms compatible -capacity of 3000 lit. for water. 100mm thick rigid puff insulation with 20G GI galding with float valve arrangement

nos

24

Supply and installation of small pump for mixing purpose of capcity 2m3/hr @18m head with level controller, starter panel & related power cabling between starter to motor approximately 30rmt

nos

25

Supply and installation of 50mm GI piping for the above

60

Rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

6 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 26 a b 27 Description supply,installation of MS channel works for following supply and instaltion of ms angle suport for plant room supports supply and instaltion of Ms Checkered platr for shaft closings etc. Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, anchors, saddles, sleeves, brackets, welding, smooth finishing, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil foundation inclusive of scope including, excavation, dewatering, brickworks, pedestals, covers, etc., 600mm dia 550mm dia 500mm dia 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250mm dia 200mm dia 150mm dia 180 qro qro 70 90 30 qro qro 40 qro Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt 4000 1000 kg kg Qty Units
Unit Rate Supply Erection Supply Amount Erection

a b c d e f g h i j
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

7 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

k l m 28 29 a b c d e f 30

125mm dia 100 mm dia 50 mm dia

qro 200 qro

Rmt Rmt Rmt

Supply, charging and commissoing of mono ethylene glycol-30% concentration-App. Volume 320 cum of glycol Supply,Laying and commisioing of PVC insulated, copper conductor 1.1kv grade, Armoured copper cable 1C x 240 sqmm xlpe 4C X70 sqmm xlpe 4c X35 sqmm xlpe 4C x 16sqmm xlpe 4C x 10sqmm xlpe 4c x 2.5sqmm Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 1C x 240 sqmm xlpe 4C X70 sqmm xlpe 4c X35 sqmm xlpe

lot

180 144 152 175 125 60

Rmt Rmt Rmt Rmt Rmt Rmt

a b c

10 12 10

set set set

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

8 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No d e f 31 a b c 32 a Supply and installation of Aluminium earth plate 50 x6mm 40 x6mm 25 x6mm Supply and installation of GI Perforated Tray with angle supports 600mm width 60 rmt 240 48 144 Rmt Rmt Rmt Description 4C x 16sqmm xlpe 4C x 10sqmm xlpe 4c x 2.5sqmm Qty 10 10 24 Units set set set
Unit Rate Supply Erection Supply Amount Erection

b c d e 33

450mm width 300mm width 200mm width 150mm width

240 60 48 72

rmt rmt rmt rmt

Supply and installation of Pressure gauge with SS syphons,niddle Valves,100mm dia range 0 to 15 kg/cmsq

28

nos

34

Supply and installation of Temp. gauge with SS thermowell,100mm dia, -10 to 20 deg C Supply and installation of 25mm Ball valves with flange end, pressure rating PN 16 with insulation and 24g AL cladding

10

nos

35

24

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

9 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 36 Description Supply and installation of Auto air vent size 25mm dia with 9 rmt 20mm copper piping Supply , installation , testing and commissioning of Electromagnetic Descaler for Chilled water flow suitable capacity-600 mm dia Qty 10 Units nos
Unit Rate Supply Erection Supply Amount Erection

37

nos

38

Supply , installation , testing and commissioning of Centrifugal, Side Stream Filter for Chilled water, 600mm dia-6480 gpm. Supply, installation and commissioning of trible duty valves for pumps, pressure rating of PN16 -with insulation and 24g AL cladding 450 mm dia 400 mm dia 350 mm dia 300 mm dia 250 mm dia 200 mm dia

nos

39

a b c d e f

qro qro qro qro 2 9

nos nos nos nos nos nos

Total
Note : Whereever BMS compatible shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

10 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. B 40 TRENCH PIPING-HEADER LINE FOR FOR PHASE 2 & 3 Supply, installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc., 600mm dia 450mm dia 400mm dia 350mm dia 250mm dia 220 340 90 qro qro rmt rmt rmt rmt rmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

a b c d e 41 Supply,installation and commissioning of Butterfly value, pressure rating of PN16 a b

450 mm dia 400 mm dia

qro qro

nos nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

11 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No c d Description 350 mm dia 250 mm dia Supply,installation and commissioning of Semi automatic Balancing valve with BMS compatible, pressure rating of PN16-with insulation 1 1 qro 2 nos nos nos nos Qty qro qro Units nos nos
Unit Rate Supply Erection Supply Amount Erection

42

a b c d

450 mm dia 400 mm dia 350 mm dia 250 mm dia Total Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

12 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No C 43 TICEL BIO PARK - II MAIN BUILDING Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required. 450mm dia 400mm dia 350mm dia 300 mm dia 250 mm dia 200 mm dia 150 mm dia 125 mm dia 100 mm dia 80 mm dia 65 mm dia 10 24 40 80 80 90 30 930 360 880 380 rmt rmt rmt rmt rmt rmt rmt rmt rmt rmt rmt Description Qty Units
Unit Rate Supply Erection Supply Amount Erection

a b c d e f g h i j k

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

13 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No l m n o p 44 Description 50 mm dia 40 mm dia 32 mm dia 25 mm dia 20 mm dia Supply and installation of GI pipe with Insulated Condensate Drain piping-25mm thick regid puf density 48 Kg/m3, 24G AL. cladding 50 mm dia 40 mm dia 32 mm dia 25 mm dia Supply,installation and commissioning of Semi automatic Balancing valve with BMS compatible, pressure rating of PN16-with insulation,suitable for 230v supply 12 2 12 2 nos nos nos nos 900 800 500 210 rmt rmt rmt rmt Qty 2100 300 4200 350 qro Units rmt rmt rmt rmt rmt
Unit Rate Supply Erection Supply Amount Erection

a b c d

45

a b c d

125 mm dia 100 mm dia 80 mm dia 65 mm dia

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

14 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 46 Description Supply,installation and commissioning of CHILLED WATER MANIFOLD rating of PN16-with insulation and 24G al cladding. Chilled Water Manifold size suitable to AHU ( Includes 5 Nos butterfly valve/ ball Valve, 1 self modulating valve(auto balancing/modulating with thermostat), 1 No Y strainer, 2 Nos Pressure gauges(with ss styphon&Needle valve), 2 Nos temperature Gauges(with ss thermowell), 1 No drain valve, 1 no fo auto air vent and inclusive Flange provision for one BTU. 80 Dia Size Manifold 65 Dia Size Manifold 50 Dia Size Manifold 40 Dia Size Manifold 32 Dia Size Manifold 25 Dia Size Manifold 20 Dia Size Manifold Supply,installation and commissioning of Butterfly Valve with extended stem of 100mm length, pressure rating of PN16, Suitable for brine application -SS wafer/stem for brine application.-with insulation and 24g AL cladding 400 mm dia 300 mm dia 125 mm dia 100 mm dia qro qro 24 qro nos nos nos nos qro 4 94 12 104 16 qro nos nos nos nos nos nos nos Qty Units
Unit Rate Supply Erection Supply Amount Erection

a b c d e f g 47

a b c d

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

15 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No e f 48 Description 65 mm dia 50 mm dia Supply,installation and commissioning of Self Dynamic Valve with extended stem of 100mm length, pressure rating of PN16, SS wafer/stem for brine application.-with insulation and 24g AL cladding,suitable for 230v supply power 65 mm dia 50 mm dia 40 mm dia 32 mm dia 25 mm dia Supply,installation and commissioning of Ball valve with flange end, pressure rating of PN25with insulation and 24G al cladding 32 mm dia 25 mm dia 12 50 nos nos 20 18 16 12 12 nos nos nos nos nos Qty 24 2 Units nos nos
Unit Rate Supply Erection Supply Amount Erection

a b c d e 49

a b

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

16 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 50 Description 2 TR capacity, 4 row cooling coil, CHILLED WATER cassette Units. The cassete units shall be complete with f valves(ball valve with y sainer,self modulating valve and copper pipe for valve connections) - ATM Supply and installation of isolator panel for the above Supply and installation of Pressure differencial valves for rasier shaft, BMS compatibility with insulation & 24G al cladding.- for Header line 450mm dia 300mm dia 250 mm dia 200 mm dia Supply, instalation and commissioning of Double skin low leakage VAVs, selection of VAV 5 to 6 m/sec, dba level less than 30db,A in built thermostart and controller, suitable size of cabling, conduiting, cat 5 cable for between thermostart to VAV, and VAV to isolater, required 5A isolator, fast activating type of VAV that is 3 to 5 seconds, interlocking arrangement between AHU to VAV for on/off operation 450 to 550 CFM 700 to 800 CFM 900 to 1000CFM 1000 to 1200 CFM 1800 to 2000 CFM 3400 to 3600 CFM 2 178 2 1 1 1 nos nos nos nos nos nos 2 2 2 2 nos nos nos nos Qty Units
Unit Rate Supply Erection Supply Amount Erection

2 2

nos nos

a 51

a b c d 52

a b c d e f

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

17 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

HEAT RECOVERY UNITS Supply, installation, testing and commissioning of HEAT RECOVERY WHEEL UNIT with assembled condition all Sheet metal cabinet type double skin HRU, the inner and outer sheets of the double skin shall be 0.8 mm thick pre-coated and pre plasticized sheets with 50 mm thick . Backward aero foil curve fan, fan motor,fan casing insulation for accoustic, with enthalpy recovery, Filter section with Pre Filter, Bag Filter, Hepa filter ( Box type 450mm length ) & UVGI lamp on both sides, HEPA filter 450 mm box type,sound level shall be 60dbA from 1 mtr for both sides of air stream Units shall be complete with opposed blade volume control dampers at both oulets, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, Fresh air temp DB:103F, WB: 82F, Exhaust air temp DB:76F, RH:55%, duct static pressure sensor (range 100-150pa), cabling between sensor to VFD, with neccessary conduits, 2 runs of 12gauge copper earth rod, apprx. 75-90 rmt. 53 Supply,installation and commissioning fo HRUs with wheel -capacity of 21600cfm@ external static 50mm for both supply air and exhaust air, 75% of efficieny for sensibel and latent heatLAB - TYPICAL FLOORS (2-12) - LAB 1- 8, exhaust/fresh air side consist of EU3,EU9 and and HEPA filter 0.1micron 99% efficiency, with Ultra violet germicidal irradiation Lamp on both sides

11

nos

IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe

22

nos

248

rmt

44 11

Set nos

Supply and installation of Starter panel for the wheels

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

18 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 54 Description Supply,installation and commissioning fo HRUs with wheel -capacity of 2080cfm@ total 50mm supply air and exhaust air cfm@ total 50mm, without hepa filter & uvgi lamp, 75% of efficieny for sensibel and latent heat- GF- FOOD COURT IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe d 55 Supply and installation of Starter panel for the wheels Supply,installation and commissioning fo HRUs with wheel -capacity of 1720cfm@ total static 50mm supply air and exhaust air cfm@ total static 50mm, without hepa filter and uvgi lamp, 75% of efficieny for sensibel and latent heat- GF - RETAIL AREA IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe 56 Supply & installation of false ceiling type suitable terminal Box of double skin 25mm thick puf panel hooded type hepa filter with SS316 perforated grilles gear type vcd with insulated canvas, 450mm height Supply ,installation and commissioning of Hepa terminal filter for 600x600 with SS 316 grille Supply & installation of SS 316 pipe of 50mm dia for pressure difference 25 rmt 6 1 Set nos 25 rmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

nos

nos

nos

nos

200

nos

57 58

200 164

nos rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

19 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 59 Description Magnahelic gauges 0-50 pascal with fixing box, complete CRA powder coated with ss304 covered sheet. Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM, 500pa (foodcourt,retail,HRW,lift lobby,service corri. ), using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealent 18G 20G 22G 24G Supply and installation of al.powdered coated grilles with VCD and wooden frame for grille erection (atrium & corridors ) Supply and installation of VCD with gear operated type Supply and installation of S/R diffuser Supply and installation of UL listed fire dampers with actuator, BMS compatible, fire sensors and actuators,suitable for 230v poer supply Supply and installation of flexiable duct dia 300mm,25 micron poly laminated type with heavy duty type clamp Supply and installation of flexiable duct dia 250mm with heavy duty type clamp 145 1900 6600 5160 sqmt sqmt sqmt sqmt Qty 94 Units nos
Unit Rate Supply Erection Supply Amount Erection

60

a b c d 61

60 22 96 90

sqmt sqmt sqmt sqmt

62 63 64

65

180

rmt

66

225

sqmt

67 68

Supply and installation of flexiable duct dia 200mm with heavy duty type clamp Supply and installation of Plenum boxes with inside 6mm thick nitrile rubber insulation (525x525x450 mm)

115

sqmt

135

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

20 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 69 Description Supply and installation of Plenum boxes with inside 6mm thick nitrile rubber insulation (1000Lx250Wx300H mm) Supply and installation of Butterfly dampers dia 300 mm Supply and installation of Butterfly dampers dia 250 mm Supply and installation of Butterfly dampers dia 200 mm Supply and installation of Duct Thermal Insulation of 19mm thick nitriyle rubber for SA duct passing through the Conditioned space, class O range, with 0.5 mm thick al. foil faced Supply and installation of Duct Thermal Insulation of 13mm thick nitriyle rubber for SA duct passing through the Conditioned space, class O range, with 0.5 mm thick al. foil faced Supply and installation of Duct Thermal Insulation of 20mm thick nitriyle rubber with 0.5 mm thick al. foil faced for SA/RA duct passing thrugh the un Conditioned space Qty 75 120 150 75 Units nos nos nos nos
Unit Rate Supply Erection Supply Amount Erection

70 71 72 73

420

sqmt

74

10000

sqmt

75

300

sqmt

76

Supply and installation of Duct Thermal Insulation of 13mm thick nitriyle rubber with 0.5 mm thick al. foil faced for RA duct passing through the un Conditioned space

2000

sqmt

77

Supply, installation and commissioning of Duct Accoustic(Nitrile rubber base, Open cell material 24mm thick, Thermal conductivity 0.047w/m.k@20deg C, excellent absorption, 99.9% reduction of bacterial growth, class1 fire performance, with a density of 140180Kg/cubicmeter) Supply and installation of non return air dampers low leakage type with spring loaded

90

sqmt

78 79

60

sqmt

Supply and installation of external curved prole and shperical inner nozzle using the mechanical principle of eye ball ( ball & sacket principle ) engineered to swivel 360deg made of high quality aluminium, jet nozzle 250 dia to 300 dia Supply and installation of low leakage bubble type damper with spring acturator Supply, installation of heavy duty gripples for large duct, attenuators & VAVs supports

24

nos

80 81

5 150
21 of 64

sqmt nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description charges for air balancing for all erected ducts supply and installation armasound open cell nytrile rubber material thickness of 30mm thick,wall primer paintting, including GI stips for regidity for wall acousting in AHU rooms Qty 25000 Units sqmt
Unit Rate Supply Erection Supply Amount Erection

82 83

800

sqmt

Ventilation System 84 Supply, installation and commissioning of out door mounted - cabinet type Toilet Exhaust Air Fan for exhaust(13900 CFM/ 125 mm external static) IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination, water proof. Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade, Armoured copper cable 3 C x 4 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 4 sqmm xlpe 85 Supply, installation and commissioning of out door mounted cabinet type Toilet Fresh Air Fan (12005 CFM/50 mm external static) IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 4 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 4 sqmm xlpe 4 Set 50 rmt 4 Set 2 nos

nos

50

rmt

nos

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

22 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 86 Description Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 440 CFM/25 mm external static-For Drivers toilet @ B1) Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 460 CFM/25mm external static -For Mens & womens toilet @ GF) Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 88 Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 1566 CFM/25mm external static-For Mens & womens toilet @ GF) Supply and installation of respective motor kw starter panel with 16A DP Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

Qty 2

Units nos

Unit Rate Supply Erection Supply

Amount Erection

nos

20

rmt

Set nos

87

nos

20

rmt

Set nos

nos

10

rmt

23 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 89 Supply, installation and commissioning of cabinet type Toilet booster fan(inline fan 900 CFM/25mm external static -For womens toilet @ Typical Floors 1-12) Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe Supply, installation and commissioning of cabinet type Toilet booster fan(inline fan 1250 CFM/25mm external static -For Mens toilet @ Typical Floors 1-12) Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 91 Supply, installation and commissioning of cabinet type Pantry booster fan(inline fan 300 CFM/30mm external static-For Pantry Room @ GF) 24 Set 125 rmt 125 rmt 2 Set nos Qty Units
Unit Rate Supply Erection Supply Amount Erection

12

12

nos

24

Set nos

90

12

12

nos

2
24 of 64

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe

nos

25

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 4 Set

92

Supply, installation and commissioning of out door mounted cabinet type Stair well pressurization fan, with flexible fire proof connection at inlet & outlet. (25025 CFM/ 50 mm external static),motor tempreature rating 300 deg C 2Hrs rating IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

nos

50

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe Supply, installation and commissioning of out door mounted cabinet type Lift well pressurization fan, with flexible fire proof connection at inlet & outlet. (26655CFM/ 35 mm ex Static)-Temp.Rating 300 deg C 2Hrs rating. IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination

Set

93

nos

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

25 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No b Description Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 94 Supply, installation and commissioning of out door mounted cabinet type Lift well pressurization fan, with flexible fire proof connection at inlet & outlet. (17770CFM/ 35 mm ex Static)-Temp.Rating 300 deg C rating. 6 Set 50 rmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

nos

IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

15

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 2 Set

95

Supply, installation and commissioning of out door mounted SISW type Kitchen Exhaust fan (9000 cfm/ 200mm total static),outdoor mounted type IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

nos

35

rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

26 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No c Description Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 96 Supply, installation and commissioning of out door mounted cabinet type DIDW, Kitchen Fresh fan (8000 cfm/ 50mm external static), DIDW type, with pre filter 4 Set Qty Units
Unit Rate Supply Erection Supply Amount Erection

nos

IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe

nos

30

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 4 Set

97

Supply, installation, testing and commissioning of out door mounted dry scrubber electrostatic type 9000 cfm for kitchen exhaust application, 230V 50HZ power supply, with BMS compatibility multi arrangement of scrubber, Outdoor type, for kitchen exhaust application, inbuilt control panel ( starter panel ) and related power cables between scrubber and panel approximately 52rmts end terminations, it capable of handling the Kitchen exhaust gases coming out of the Kitchen hoods. The scrubber shall be able to control SPM at 150 mg/ NM and 99% of SO2 removal. The scrubber shall behaving cyclonic inlet / outlet with honeycomb type impingement plates complete with FRP / epoxy lining, structural supports, water spraying arrangement, mist collection, painting etc. The srubbing system shall have an induced draught fan capacity of handling flue gases of the specified DG set with motor, base plate, vibration isolation pads, flexible inlet & outlet connection, outlet damper & V belt drive mechanism. The fan shall be designed to have an inlet to with stand for the temperature of 80degree temperature

set

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

27 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description The scrubbing system shall have a water circulating pump complete with motor, base plate, pressure gauge on delivery side, coupling etc., The scrubbing system shall also have a dosing system consisting of a metering tank, a metering pump with adjustable capacity as required complete with motor, base plate, coupling etc., and a high speed motor mounted agitator with SS shaft / impeller and supporting arrangement. The scrubbing system shall be complete with HDPE interconnecting piping with valves, NRV, strainer etc., including pipefittings, flange nuts & bolts. Clamps, pipeline supports, painting etc., The scrubbing system shall also be provided with motorized damper. The scrubbing system shall be complete with motor control center consisting of cubicle outdoor type panel with incoming & outgoing MCCBs, starters, indicating lamps, indicating meters etc., a b IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 98 Supply, installation and commissioning of out door mounted cabinet type STP room fresh air fan (24200 cfm/ 65mm external static) IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 99 2 Set 15 rmt 20 rmt 2 nos Qty Units
Unit Rate Supply Erection Supply Amount Erection

2 1

Set nos

a b

nos

Supply, installation and commissioning of out door mounted cabinet type STP room Exhaust fan (24400 cfm/ 125mm external static)

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

28 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

a b

IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 16 sqmm xlpe

nos

15

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 16 sqmm xlpe 2 Set

100

Supply, installation and commissioning of out door mounted cabinet type Service corridor exhuast fan for exhaust(47520 CFM/150 mm external static)

nos

a b

IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

nos

20

rmt

3 C x 10 sqmm xlpe

Set

101

Supply, installation and commissioning of out door mountedcabinet type fan (8400 cfm/ 50mm external static) with filter - Transformer Room

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

29 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No a Description IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Qty 2 Units nos
Unit Rate Supply Erection Supply Amount Erection

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe 30 rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 4 Set

102

Supply, installation and commissioning of out door mountedcabinet type fan (8400 cfm/ 50mm external static) with filter - Panel Room IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

a b

nos

30

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 4 Set

103 Supply, installation and commissioning of out door mountedcabinet type fan (15800 cfm/ 50mm external static) with filter - Pump Room

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

30 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No a Description IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Qty 2 Units nos
Unit Rate Supply Erection Supply Amount Erection

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe 30 rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 4 Set

104 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 105 Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM 500pa, (Toilet ,stairwell ,liftwell,hru's,lobby smoke,sercorr ex, kit, Sdp vent.) Risers, using food grade type of sealant for leakage arresting,wall to wall duct crossing area to be sealed with fire retardant sealent. a b c d 106 18G 20G 22G 24G

1850

rmt

610

sqmt sqmt sqmt sqmt

588

2900

1500

Supply and installation of al.powdered coated exhaust / fresh air Dia 125 DISC Valve

300

nos

107 Supply and installation of al.powdered coated exhaust/ fresh air grilles with al co damper

18.0

sqmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

31 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty


20

Units
Sq.m

Unit Rate Supply Erection Supply

Amount Erection

107a Fresh air louvers made of 16 gauge GI sheet duly epoxy powder coated with filter fixing frame with 20 micron filter suitable to fix in wall / window.

108 Supply and installation of low leakage VCDs for fresh/exhaust air control 109 Supply and installation of cabinet type smoke check lobby ventialtion fans (supply/exhaust)1000cfm@30mm exterenal static 110 Supply and installation of above item fan motor, starter panel with Disconect Switch 111 PVC insulated ,copper conductor 1.1kva grade,Armoured copper cable ,brass heavy duty glands, soldering crimping type of copper sockets,app. Distance 30rmt 112 Charges for Duct pressure testing -Ishare std. for entire ducting 113 Supply and installation of al.powdered coated grilles with wooden frame for grille erection ( staircase, lobby press., smoke check & kit. ) 114 Supply and insualtion of 20mm thick nitrilye Rubber with 0.5mm thick al. Foil faced for under deck insulation 115 Supply and instalation and closing of raiser shafts with 9mm thick ms plate without air leakage using fire retardant sealant Total Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. D CAR PARK VENTILATION SYSTEM 116 Supply, installation, testing and commissioning of Car aprk Jet Fans, Dual speed type with disconect switch-1850cfm with silencer(both sides) for normal operation and 3700CFM Fire mode operation
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

90

sqmt

nos

nos

6 17000

nos sqmt

30

sqmt

2900

sqmt

530

sqmt

90

nos

32 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

117 Supply erection testing and commissioning & handing over of AXIAL fresh air fans of11000 CFM @ 25 MM TOTAL STATIC, with silencer MOTOR RATING 300DEG TEMPERATURE 2Hrs rating,low sound level - Normal mode - FRESH AIR 118 Supply & Installation of IP 55 VFD-HVAC series, VFD panel with related motor KW VFD (fresh air fan-3nos of fan) with necessary Isolators etc., as per technical specification to receive the power to the equipment. ( cubical type vfd panel with 3 mos of VFDs per room), with one incomer main Isolator and three out going isolators for vfds with required adapotor box , cables and cable termination with necessary indication lamps, ammeter,voltmeter) BMS compatible.

27

nos

nos

119 Supply erection testing and commissioning & handing over of AXIAL exhaust air fans of 34000 CFM @ 25 MM TOTAL STATIC- MOTOR RATING 300DEG TEMPERATURE 2Hrs rating,low sound level - same fan should be operated in Normal mode / fire mode with VFD control - EXHAUST AIR 120 Supply & Installation of IP 55 VFD-HVAC series, VFD panel with related motor KW VFD (fresh air fan-3nos of fan) with necessary Isolators etc., as per technical specification to receive the power to the equipment. ( cubical type vfd panel with 3 mos of VFDs per room), with one incomer main Isolator and three out going isolators for vfds with required adapotor box, cables and cable termination with necessary indication lamps, ammeter,voltmeter) Incase of fire or smoke all the exhaust fans must run at maximum flow capacity and in normal mode the fan must run at required flow capacity, required control cables for the proper operation to be considered, BMS compatible.

27

nos

nos

121

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

6C x 2.5 sqmm xlpe

3000

Rmt

3C X10 sqmm xlpe

1500

Rmt

122 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM 33 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

6C x 2.5 sqmm xlpe

110

set

3C X10 sqmm xlpe

56

set

123 Supply and providing 8 SWG Copper earth bare wires clamped on the wall / run along with the cables as required 123a Supply and installation of 25x3 Copper flat 124 150 mm wide GI Perforated Cable Tray for above cables 125 300 mm wide GI Perforated Cable Tray for above cables 126 450mm wide GI Perforated Cable Tray for above cables 127 600 mm wide GI Perforated Cable Tray for above cables 128 CFD (Computational Fluid Dynamics ) analysis for all 3 basements.its should cabaple and witnessesd to chech after completion works-fire mode/normal mode 129 CO/CO2 detector head (Analog sensor-Should match the specifications),0- 250 ppm, with nessesary arrangement of suitable fixing 130 PLC based control panel for CO detectors and control of JET Fans with starter panel for demand ventilation with a logic contoller .Should also enable auto on/off of fans for power saving BASED ON SENSING OF CO LEVEL. WITH STARTER 131 CIRCULAR ATTENUATOR FOR SUCTION/DISCHARGE SIDE OF Normal mode(fresh/exhaust) operation of main extract Fans 132 Supply and installation of SMACNA standard, Sheet Metal Ducting as per Specification. Pressure 500 Pa, Ducting 18 G with angle Iron flange and related fire rated canvas with 300 deg C 2Hrs rating

1800 3000 1600 1450 1100 750 3

Rmt Rmt Rmt Rmt Rmt Rmt Set

45

nos

set

54

nos

170

Sqmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

34 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

133 2 Runs of copper armoud 3C 1.5 Sqmm power cable for jet fans with end termination and at the fan posistion required isolation for maintanance aux.

3900

rmt

134 2C 1.0 Sqmm FRLS Communication cable in 19 mm MS Contuit between PLC Panel to co sensors 135 Supply and installation of Smoke damper with BMS compatible actuator for fire mode fresh air fan,suitable for 230v power supply 136 Supply and installation of UL listed Firedamper cum smoke damper with BMS compatible actuator and related cabling betwenn actuator to plc panel , including supply of smoke/fire sensor , its is controlled by PLC panel

1800

rmt

27

sqmt

54

sqmt

137 Supply and instalation of MS Grating for raiser shaft- service acces

88

sqmt

Total
Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. E FUMIGATION SYSTEM

138 Supply, installation, testing and commissioning of outdoor mounted Cabinet type, fan (outdoor) at terrace open mounted type a 18000CFM@130mm external static

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

35 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty 2 Units nos


Unit Rate Supply Erection Supply Amount Erection

139 IP 55 VFD-HVAC series with 63A TPN Isolator and required adapotor box for cable termination 140 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable a 3 C x 6 sqmm xlpe 141 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. a 3 C x 6 sqmm xlpe

50

rmt

Set

142 Supply, installation, testing and commissioning of outdoor mounted Cabinet type, fan (outdoor ) at terrace open mounted type a 12000CFM @ 130mm external static 1 1 nos nos

143 IP 55 VFD-HVAC series with 63A TPN Isolator and required adapotor box for cable termination 144 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable a 145 3 C x 6 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 6 sqmm xlpe Supply, instalation and commissioning of Double skin low leakage VAVs, selection of VAV 5 to 6 m/sec, dba level less than 30db,A iDiauilt thermostart and controller, suitable size of cabling, conduit, earth between thermostart to VAV, and VAV to isolater, required 5A isolator, fast activating type of VAV that is 3 to 5 seconds, interlocking arrangement between AHU to VAV for on/off operation 1800 to 2000 CFM

25

rmt

a 146

Set

90

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

36 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 147 Description Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM, 500pa, using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealent 20G 22G 24G Supply and installation of Low leakage bubble type damper with BMS compatible actuator 50 1800 200 30 2250 sqmt sqmt sqmt sqmt sqmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

a b c 148

149 Charges for Duct pressure testing -ishrae std. Total Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. F FAADE VENTILATION SYSTEM 150 Supply, installation, testing and commissioning of axial type fan at Ground/terrace open mounted type -2700cfm@25mm ex Static,low speed less than 450 rpm ,less than 40 dba 151 Supply and installation of cubical panel for the above , ( cubical type starter panel with 6starters per floor ,with one incomer isolator and six outgoing isolator , with necessary indication lamps, ammeter,voltmeter -3nos)

24

nos

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

37 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No 152 Supply and installation of cubical panel for the above ,( cubical type starter panel with 2starters per floor ,with one incomer isolator and two outgoing isolator , with necessary indication lamps, ammeter,voltmeter -3nos) 153 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable a 3 C x 2.5 sqmm xlpe 600 rmt 3 nos Description Qty Units
Unit Rate Supply Erection Supply Amount Erection

154 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. a 3 C x 2.5 sqmm xlpe 48 950 20 20 Set rmt sqmt sqmt

155 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 156 Supply and installation of GI ducting,180GSM ,24G 157 Supply and installation of Non Vision louvers Total Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. G GROUND FLOOR & COMMON AREA AHUS DOUBLE SKIN AIR HANDLING UNITS

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

38 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Supply, installation, testing and commissioning of AHUs with assembled condition All Sheet metal cabinet type double skin air handling units, with 50mm thickness RPUF panels complete with Fan section with DIDW centrifugal Backward aero foil curve fan, water inlet temp 6deg C & water outlet temp 14deg C, outer and inner skin0.8mm thick pre-coated and pre plasticized sheets, fan motor, fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 10kw heater strip bank section with thyrister control type, Filter section with Pre Filter & Bag Filter, two pass SS316 18Gauge eliminator , sound level shall be 60dbA from 1 mtr. Qty Units
Unit Rate Supply Erection Supply Amount Erection

Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve, return air plenum sections of 910mm length with top entry provided with SS316 12Gauge mesh, magnolic gauges, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator cabling and termination and duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD with neccessary conduits apprx. 45-55rmt

158

4 TR capacity, 2261 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- LIFT LOBBY TYPICAL FLOORS (2-12)

12

nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination and required adapotor box for cable termination 12 nos

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe

840

Rmt

24

Set

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

39 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty 1 Units nos


Unit Rate Supply Erection Supply Amount Erection

159 3 TR capacity, 2261 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- LIFT LOBBY GROUND FLOOR a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 160 3 TR capacity, 1568 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- BASEMENTS

nos

70

rmt

Set

nos

IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe

nos

310

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 6 Set

161 5TR capacity, 2671 Dcfm, 25 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - IBMS ROOM @ B1 a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination

nos

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

40 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 4 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 4 sqmm xlpe 162 22TR capacity, 13147 Dcfm, 50 mmwg fan external static, 6 row cooling coil, ceiling suspended unit - ATTRIUM a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 6 Set 75 rmt 2 3 Set nos 20 rmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

nos

163 31 TR capacity,9636 Dcfm, ext.static 30 mmwg fan static, 8 row cooling coil, floor mounted unit - FOOD COURT AHU a b IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

nos

25

rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

41 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No c Description Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. Qty Units
Unit Rate Supply Erection Supply Amount Erection

3 C x 10 sqmm xlpe

Set

164

34 TR capacity,13090 Dcfm, 30 mmwg fan external static, 6 row cooling coil, floor mounted unit - RETAIL AREA AHU IP 55 VFD-HVAC series with 63 A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe

nos

nos

25

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

3 C x 10 sqmm xlpe 165 6TR capacity, 3150 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - GF LOBBY&CORRIDOR a b IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

Set

nos

nos

25

rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

42 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description 3 C x 2.5 sqmm xlpe 166 8TR capacity, 4275 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - GF CORRIDOR a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Qty 2 Units Set
Unit Rate Supply Erection Supply Amount Erection

nos

nos

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe 25 rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 2 Set

167 6TR capacity, 2612 Dcfm, 25 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - GF.BUISINESS CENTER a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 168 22TR capacity, 5286 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - GF CONVENTION CENTER
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

nos

nos

25

rmt

Set

1
43 of 64

nos

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description IP 55 VFD-HVAC series with 63 A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 10 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 169 9TR capacity, 4575 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - TYPICAL FLOORS CORRIDOR (1-11) a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 170 6TR capacity, 3705 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - TYPICAL FLOORS CORRIDOR (1-11) a b IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable
44 of 64

Qty

Units

Unit Rate Supply Erection Supply

Amount Erection

nos

25

rmt

Set

11

nos

11

nos

250

rmt

22

Set

11

nos

11

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 171 9TR capacity, 3947 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended / floor mounted Units - 12TH FLOOR CORRIDOR a b IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 172 6TR capacity, 3705 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - 12TH FLOOR CORRIDOR a b IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe Total
ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM 45 of 64

Qty 250

Units rmt

Unit Rate Supply Erection Supply

Amount Erection

22

Set

nos

nos

25

rmt

Set

nos

nos

25

rmt

Set

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation. H LAB TYPICAL FLOOR DOUBLE SKIN AIR HANDLING UNITS ( 100% FRESH AIR ) Supply, installation, testing and commissioning of clean room type, AHUs with assembled condition All Sheet metal cabinet type double skin air handling units with 50mm thickness RPUF panels complete with Fan section with high efficient type PLUG FAN, water inlet temp 6deg C & water outlet temp 14deg C, outer skin 0.8mm GI, inner skin SS316 0.8mm, above 95% efficiency motor,fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 7.5kw heater strip bank section with thyrister control, RH cum Temp sensor, required controller for RH and heater, power control panel, interlocking arrangement for heater and VFD, return air plenum of 910mm length, Filter section with Pre Filter & Bag Filter filter, Hepa filter( Box type 450mm length ), run around 6row deep heatpipes, two pass 18g SS 316 eliminator , sound level shall be 60dbA from 1 mtr. Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve. Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator, cabling and termination ,duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD, heater to VFD, RH sensor to controller with neccessary conduits apprx. 75-90 rmt. 173 18TR capacity, 3200 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 20 nos

IP 55 VFD-HVAC series with 63A TPN MCB Isolator

20

nos

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

46 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No b Description Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable 3 C x 10 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe 174 12TR capacity, 2200 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 20 Set 400 rmt Qty Units
Unit Rate Supply Erection Supply Amount Erection

70

nos

IP 55 VFD-HVAC series with 63A TPN MCB Isolator Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable 3 C x 10 sqmm xlpe

70

nos

1400

rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 10 sqmm xlpe DOUBLE SKIN AIR HANDLING UNITS ( RECIRCULATORY ) Supply, installation, testing and commissioning of AHUs with assembled condition All Sheet metal cabinet type double skin air handling units with 50mm thickness RPUF panels complete with Fan section with DIDW centrifugal Backward aero foil curve fan, water inlet temp 6deg C & water outlet temp 14deg C, outer and inner skin0.8mm thick pre-coated and pre plasticized sheets, fan motor, fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 5kw heater strip bank section, with thyrister control type, Filter section with Pre Filter & Bag Filter, two pass SS316 18Gauge eliminator 20G, sound level shall be 60dbA from 1 mtr. 70 Set

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

47 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve, return air plenum sections of 910mm length with top entry provided with SS316 12Gauge mesh, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator cabling and termination and duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD with neccessary conduits apprx. 45-55 , apprx. 75-90 rmt. Qty Units
Unit Rate Supply Erection Supply Amount Erection

175

6TR capacity, 2628 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB IP 55 VFD-HVAC series with 32A TPN MCB Isolator

20

nos

20

nos

Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable 3 C x 2.5 sqmm xlpe 400 rmt

Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required.. 3 C x 2.5 sqmm xlpe 20 Set

176 9TR capacity, 3947 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB a IP 55 VFD-HVAC series with 32A TPN MCB Isolator Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable 3 C x 2.5 sqmm xlpe c Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

70

nos

70

nos

1400

rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

48 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description 3 C x 2.5 sqmm xlpe 177 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 178 Qty 70 Units Set
Unit Rate Supply Erection Supply Amount Erection

1000

rmt

Supply, installation and commissioning of Hepa filter module for AHUs Total Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

1015

sqft

BTCIF LAB AHUS


Air Handling Units (AHU) (Classified Areas) (Recirculatory)

179 Pharma grade stericlean double skin Air handling unit with Thermal Break Profile internally

coved 43 mm thk PUF insulated Air handling Unit made out of 24G GI Plain inside and 24G GI outside pre coated sheet, with cold bridge free door on discharge side of fan, water inlet temp 6deg C & water outlet temp 14deg C, return air plenum with provision to fix G4 filter, Coil section with 6 row deep chilled water coil, 5 to 7.5kw heater strip bank section, thyrister control type/RH cum Temp sensor, required controller for RH and heater, power control panel, interlocking arrangement for heater and VFD, velocity across coil not to exceed 2.5 m/s. Bypass damper for 20% capacity of AHU. All coils to be sized for full supply air capacity of AHU. SS insulated drain tray, fan section with DIDW backward curved centrifugal fan, suitable TEFC squirrel cage induction motor (NFLP), drive set consisting of taper lock pulleys & V-belts, Inspection window, filter section after the fan to fix F6 filter. Fresh air, return air, supply air damper & bleed of damper of aluminium extruded construction with provision for fixing H13 HEPA filter in bleed off module. Provision for fixing Magnehelic guages across F6 filter. (Excluding filters). (AHU height should not exceed 1100mm)

AHU-01: 6000 CFM @ 125 mm ext. Static Pressure

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

49 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

AHU-02A: 3600 CFM @ 125 mm ext. Static Pressure AHU-02B: 2900 CFM @ 125 mm ext. Static Pressure AHU-03: 1850 CFM @ 125 mm ext. Static Pressure AHU-04: 4250 CFM @ 125 mm ext. Static Pressure AHU-05: 1700 CFM @ 125 mm ext. Static Pressure AHU-06: 1000 CFM @ 125 mm ext. Static Pressure AHU-08: 3600 CFM @ 125 mm ext. Static Pressure AHU-09: 3800 CFM @ 125 mm ext. Static Pressure AHU-10: 4000 CFM @ 125 mm ext. Static Pressure AHU-11: 4000 CFM @ 125 mm ext. Static Pressure AHU-12: 1150 CFM @ 125 mm ext. Static Pressure AHU-13: 5700 CFM @ 125 mm ext. Static Pressure AHU-14: 3250 CFM @ 125 mm ext. Static Pressure AHU-15: 2900 CFM @ 125 mm ext. Static Pressure AHU-16: 4400 CFM @ 125 mm ext. Static Pressure

nos.

nos.

d e

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

50 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


q

Description AHU-17: 3600 CFM @ 125 mm ext. Static Pressure

Qty
1

Units
nos.

Unit Rate Supply Erection Supply

Amount Erection

Air Handling Units (AHU) (Classified Areas) (100% fresh air) 180 Pharma grade stericlean double skin Air handling unit with Thermal Break Profile internally

coved 43 mm thk PUF insulated Air handling Unit made out of 24G GI Plain inside and 24G GI outside pre coated sheet, with cold bridge free door on discharge side of fan, fres air plenum with provision to fix G2 filter(20micron, 85% efficiency), G4 filter, Coil section with 8
row deep chilled water coil and 15kw heater strip bank section, thyrister control type/RH cum Temp sensor, required controller for RH and heater, power control panel, interlocking arrangement for heater and VFD, velocity across coil not to exceed 2.5 m/s. Bypass damper for 20% capacity of AHU. All coils to be sized for full supply air capacity of AHU. SS insulated drain tray, fan section with DIDW backward curved centrifugal fan, suitable TEFC squirrel cage induction motor (NFLP), drive set consisting of

taper lock pulleys & V-belts, Inspection window, filter section after the fan to fix F6 filter(5 micron, 95% efficiency). Fres air inlet with GI Powder coated louvers, Supply air damper. Provision for fixing Magnehelic guages across F6 filter. (Excluding filters). (AHU height
should not exceed 1100mm)

AHU-07: 5700 CFM @ 100 mmWC ex.Static Pressure

nos.

181 Treated Fresh Air Unit

Double Skin type Pre-cooling unit made out of 24G GI inside plain & 24 G GI powder coated sheet with 25mm thick PUF insulation, comprising of Pre filter section with provision to fix G4 filters(10micron, 90% efficiency), 8 row deep chilled water coil, fan section with centrifugal fan with suitable Non flame proof motor with anti vibration mounts, out let connections complete with service doors, outlet damper. (Including filters). (TFA height should not exceed
1100mm)

TFA-17 : 2100 cfm @ 25 mm ex.Static pressure (For AHU-17)

nos.

182 Fan Coil Unit

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

51 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Double Skin type Fan Coil unit made out of 24G GI inside plain & 24 G GI powder coated sheet with 25mm thick PUF insulation, comprising of Pre filter section with provision to fix G4 filters (10micron, 90% efficiency), 4 row deep chilled water coil, fan section with centrifugal fan with suitable Non flame proof motor with anti vibration mounts, out let connections complete with service doors, outlet damper. (Including filters).
a

Qty

Units

Unit Rate Supply Erection Supply

Amount Erection

FCU-01 : 3000 cfm @ 40 mm To.Static pressure

nos.

Total INTERIOR 183 Ventilation Unit Single skin Ventilation Unit made out of 18G pre-painted GI sheet and essentially comprising of Pre filter section with provision for fixing G2 filter, G4 filters (10micron, 90% efficiency), fan section with DIDW forward curved centrifugal fan, Non flame proof TEFC squirrel cage induction motor and complete with anti vibration mounts, provision for magnehelic gauge across F6 filters (5micron 95% efficiency), Filter section with provision for fixing F6 filters, out let connection complete with service doors / inspection windows with fire retardent canvas connection supply air damper in G.I. construction. (Excluding filters). (VENT height should J
not exceed 1100mm)

a b

VENT-01 : 1000 CFM @ 65 mm ext.Static Pressure VENT-02 : 1150 CFM @ 65 mm ext.Static Pressure

1 1

nos. nos.

184 Exhaust Unit

Single skin Exhaust Unit made out of 18G pre-painted GI sheet and essentially comprising of filter section with provision to fix G4 filters (10micron, 90% efficiency), fan section with DIDW centrifugal fan belt driven by suitable Non flame proof motor and complete with anti vibration mounts, inlet and out let connections complete with service doors/inspection windows and with outlet damper. Single skin rexin flexible connection for fan outlet. (Excluding filters).
(EXU height should not exceed 1100mm)

EXU-01 : 1100 CFM @ 40 mm ext. Static Pressure (For VENT-01)

nos.

EXU-02 : 1400 CFM @ 40 mm ext.Static Pressure (For VENT-02)

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

52 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

EXU-03 : 1500 CFM @ 40 mm ext.Static Pressure (For Media Room of AHU-07)

nos.

EXU-04 : 1250 CFM @ 40 mmext.Static Pressure (For Wash Room of AHU-07)

nos.

EXU-05 : 700 CFM @ 40 mm ex Static Pressure (For Discard Room of AHU-07)

nos.

EXU-06 : 3250 CFM @ 40 mm ext. Static Pressure (For Discard Corridor of AHU07)

nos.

g EXU-07 : 2000 CFM @ 40 mm ext. Static Pressure (For Wash room of AHU-17) 1 nos.

185 Bleed off module Bleed Off module consisting of H13 super flow HEPA Filter with GI powder coated perforated Grill for the following sizes a 670 x 365 mm (Double flange type) qro nos.

365 x 365 mm (Double flange type)

nos.

186 Filters a AHU fitted G2(20 micron, 85% efficiency), prefilter sealant sealed complete with flange type fixing gadget. (including flange). Size 50 mm thick b AHU fitted G4 (20 micron, 85% efficiency), prefilter sealant sealed complete with flange type fixing gadget. (including flange). Size 150 mm thick AHU fitted F6 (5 micron, 95% efficiency), fine filter sealant sealed complete with flange type fixing gadget. (including flange). Size 300 mm thick

sqm

23

sqm

16

sqm

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

53 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

187 Terminal HEPA filter Module, Filter & Grill Supply of HEPA Filter module with Volume Control damper, DOP port, made out of 18 G G.I. sheet duly epoxy powder coated suitable for fixing the following size HEPA Filters & SS perforated grill. (Room servicable)

610 x 610 x 150 mm Filter size

69

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

54 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

610 x 305 x 150 mm Filter size

41

nos.

305 x 305 x 150 mm Filter size

36

nos.

188 Super flow H13 HEPA filters of following sizes a

610 x 610 x 150 mm (1000 cfm)

69

nos.

610 x 305 x 150 mm (500 cfm)

41

nos.

305 x 350 x 150 mm (250 cfm)

36

nos.

189 16G SS 304 perforated grill suitable for HEPA Module with following filter sizes

610 x 610 x 150 mm Filter size

69

nos.

610 x 305 x 150 mm Filter size

41

nos.

305 x 305 x 150 mm Filter size

36

nos.

190 Return Air Grill Module (Classified area) a False ceiling suitable return air grill module (suitable to fix perforated grill) made out of 18G GI powder coated sheet with GI collar damper and double skin flexible connetion. b

29

sqm

16G SS 304 perforated grill suitable for the above mentioned modules

32

sqm

191 Supply / Return Air Grill (Un-Classified area)

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

55 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


a

Description
Aluminium linear bar grill with GI collar damper suitable fix in duct.

Qty
17

Units
sqm

Unit Rate Supply Erection Supply

Amount Erection

192 Return Air Riser a Return air risers made out of 22G GI sheets suitable for fixing module & perforated grill - wall concealed type.

1639

sqm

Return air riser module (suitable to fix perforated grill) made out of 18G GI powder coated sheet with GI collar damper with filter collar G4 (10 micron, 90% efficiency), filter suitable to fix in above module

20

sqm

14

sqm

SS 304 perforated grill suitable for return air riser module

25

sqm

193 Dampers a Duct mounted CRCA epoxy powder coated opposed blade Volume control damper suitable for supply and return ducts. b

10

sqm

16G GI powder coated fusible link type fire damper at AHU inlet.

sqm

194 Ducting Sheet Metal work comprising of G.S.S.(Min 120 GSM GI Sheet) ducting complete with all supports and as per the specification with bolts, nuts neoprene gaskets and sealed with silicon sealant & quantities are as under: a

24 G GI

2300

sqm

22 G GI

qro

sqm

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

56 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

195 Duct Insulation Al. foil faced polyethylene insulation for ducting. a

19 mm thick for supply air duct & HEPA modules

2246

sqm

9 mm thick for return air duct, return air risers and modules

1286

sqm

Acoustic Insulation of Supply air duct and return air duct with 25mm thick fibre glass wrapped in cora cloth and finished with Aluminium perforated sheet for ducting catering to Auditorium

223

sqm

196 Pressure Monitering system a Magnelic gauges for rooms with epoxy coated box and SS 304 flush cover with necessary tubings Range : 0-6 mm WC Magnehelic guages b Magnehelic gauges for AHUs across F6 filters Range : 0-50 mm Magnehelic guages 197 Chilled Water Manifold for AHUs & TFAs Chilled Water Manifold size suitable to AHU includes 5 Nos. Butterfly / Ball Valves, 1 No. Balancing valve, 1 No. Y-strainer, 1 No. 3 Way mixing Valve with Actuator (Suitable for BMS integeration) (with interconnected wiring between thermostat & mixing valve), 2 Nos. Pressure gauges, 2 Nos. Temperature Gauges (with thermowell), 1 No drain valve without insulation. a 25 Dia Size Manifold 3 nos. 20 nos 70 nos

40 Dia Size Manifold

14

nos.

50 Dia Size Manifold

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

57 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


d 65 Dia Size Manifold

Description

Qty
qro

Units
nos.

Unit Rate Supply Erection Supply

Amount Erection

80 Dia Size Manifold

nos.

198 Chilled Water Manifold for FCUs Chilled Water Manifold size suitable to FCU includes 2 Nos. Ball Valves, 1 No. 3 way Solenioid Valve (with interconnected wiring between thermostat & solenoid valve), 1 No drain valve without insulation. a 40 Dia Size Manifold 2 nos.

199 VFD Panels Variable frequency drive for the following AHUs with local AHU panel in 16 G G.I. powder coated construction suitable to house VFD for fan motor of AHUs, control swithchgears with bypass starters. This panel shall be provided with ventilation fan & shall be installed near to AHU. a AHU-01 (7.5 KW) 1 nos.

AHU-02B (3.7 KW)

nos.

AHU-02A (3.7 KW)

nos.

AHU-03 (2.2 KW)

nos.

AHU-04 (5.5 KW)

nos.

AHU-05 (2.2 KW)

nos.

AHU-06 (1.5 KW)

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

58 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


h AHU-07 (5.5 KW)

Description

Qty
1

Units
nos.

Unit Rate Supply Erection Supply

Amount Erection

AHU-08 (3.7 KW)

nos.

AHU-09 (3.7 KW)

nos.

AHU-10 (5.5 KW)

nos.

AHU-11 (5.5 KW)

nos.

AHU-12 (1.5 KW)

nos.

AHU-13 (5.5 KW)

nos.

AHU-14 (3.7 KW)

nos.

AHU-15 (5.5 KW)

nos.

AHU-16 (5.5 KW)

nos.

AHU-17 (3.7 KW)

nos.

200 Flow measuring station with provision for fixing Pressure sensor for following supply duct sizes. a Duct face area 4.2 sft for AHU-01 1 nos.

Duct face area 3.0 sft for AHU-02A

nos.

Duct face area 2.4 sft for AHU-02B

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

59 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Qty Units


Unit Rate Supply Erection Supply Amount Erection

Duct face area 1.7 sft for AHU-03

nos.

Duct face area 3.3 sft for AHU-04

nos.

Duct face area 1.5 sft for AHU-05

nos.

Duct face area 1.1 sft for AHU-06

nos.

Duct face area 4.2 sft for AHU-07

nos.

Duct face area 3.0 sft for AHU-08

nos.

Duct face area 3.0 sft for AHU-09

nos.

Duct face area 3.3 sft for AHU-10

nos.

Duct face area 3.3 sft for AHU-11

nos.

Duct face area 1.1 sft for AHU-12

nos.

Duct face area 4.2 sft for AHU-13

nos.

Duct face area 2.7 sft for AHU-14

nos.

Duct face area 2.4 sft for AHU-15

nos.

Duct face area 3.3 sft for AHU-16

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

60 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


r Duct face area 3.0 sft for AHU-17

Description

Qty
1

Units
nos.

Unit Rate Supply Erection Supply

Amount Erection

201 Static pressure sensor with transmitter suitable fix in flow measuring station and suitable for integeration with above mentioned VFDs 202 Static Pass Box a Supply, Installation and Commissioning of Static Pass box made out of SS 304 including interlocking of size: 500 x 600 x 600 203 Dynamic Pass Box a Supply, Installation and Commissioning of Static Pass box made out of SS 304 including interlocking of size: 500 x 500 x 1000 204 Sterile Garment Cubicle a Supply, Installation and Commissioning of Garment cubicle of SS 304 with pre filter section with filters, HEPA filters and blower assembly. Size: 450 x 450 x 2000mm 205 Laminar Air Flow Units a Supply, Installation and Commissioning of Ceiling suspended Vertical Laminar Flow Unit made of SS304 with pre filter section with filters, HEPA filters and blower assembly and SS 304 table top of size: 1200 x 750mm

18

nos.

16

nos.

nos.

nos.

13

nos.

Supply, Installation and Commissioning of Horizontal Laminar Flow Unit made of SS304 with pre filter section with filters, HEPA filters and blower assembly and SS 304 table top of size: 1200 x 750mm Cross Over Bench (SS 304) in Airlock

nos.

206

nos.

207 Chilled water piping

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

61 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No Description Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, anchors, welding, smooth finishing, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc.,
a 150 Dia 40 Rmt

Qty

Units

Unit Rate Supply Erection Supply

Amount Erection

125 Dia

40

Rmt

100 Dia

40

Rmt

80 Dia

40

Rmt

65 Dia

40

Rmt

50 Dia

80

Rmt

40 Dia

80

Rmt

208 Drain piping GI 'B' class piping, nut-bolts,supports with 25mm thick nitrile rubber / cross linked polyethylene insulation a 80 Dia 80 Rmt

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

62 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


b 65 Dia

Description

Qty
80

Units
Rmt

Unit Rate Supply Erection Supply

Amount Erection

40 Dia

80

Rmt

209 Butterfly valves a 150 Dia 2 nos.

50 Dia

nos.

210 Y Strainer with SS internal filter a 150 Dia 1 nos.

50 Dia

nos.

211 Automatic Air Vents valve 212 1/2" Ball valve

20 20

nos. nos.

213 Supply of ceiling suspended type Cassette unit with chilled water coil, 3way solenoid valve with thermostat ans ser of ball valves with strainer and 1 ball valve along with drain pump iDiauilt. a

2 TR

nos.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

63 of 64

TICEL BIO PARK II

ACMV WORKS

ACMV BILL OF QUANTITIES SI No


b 1 TR

Description

Qty
1

Units
nos.

Unit Rate Supply Erection Supply

Amount Erection

214

Fresh air louvers made of 16 gauge GI sheet duly epoxy powder coated with filter fixing frame with 20 micron filter suitable to fix in wall / window.

20

Sq.m

215 Testing, Commissioning, Validation & Documentation Charges DQ/OQ documents, Maintenance manual, Test certificate for equipment (IQ format shall be provided by us but filling will be done later). 1) Smoke Test 2) Air balancing and velocity profile test 3) Pressure balancing test 4) Temperature & RH test 5) Filter integrity test 6) Air Flow Pattern

Lot

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Total GRAND TOTAL Total For Supply and Erection Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

64 of 64

TICEL BIO PARK II

ACMV WORKS

SI No

ACMV BILL OF QUANTITIES Description PART - II

Amount

Remarks

OPERATING CONTRACT FOR 5 YEARS INCLUDING 1 1/2 YEAR DEFECTS LIABLITITY PERIOD( CONSIDERED FOR TENDER EVALUATION PURPOSE )

II

NON COMPREHENSIVE MAINTENANCE CONTRACT FEE FOR 3 1/2 YEARS AFTER DEFECTS LIABLILITY PERIOD FOR TICEL BIO PARK-II AND 5YEAR NON COMPREHENSIVE MAINTENANCE FOR TICEL-I ( CONSIDERED FOR TENDER EVALUATION PURPOSE )

Total

ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

MISCELLANEOUS WORK BILL OF QUANTITIES


SI No Descriptionof works Amount Remarks

I. OPERATING CONTRACT FOR 5 YEARS INCLUDING 1 1/2 YEAR DEFECTS LIABLITITY PERIOD( CONSIDERED FOR TENDER EVALUATION PURPOSE ) Full time round the clock and year round, operation of ACMV like air cooled chiller, primary pumps, secondary pumps, phe pumps, air handling units, heat recovery wheel units, latent energy storage tanks, exhaust fans, fresh air fans, mechanical ventilation system, car park jet fans, etc., and all other items in Ticel Bio Park II and in the previous ACMV systems installed at exsiting Ticel ( Annexure B ) including, keeping log books and records of energy consumption, Details of breakdown, hours of operation, meter reading on various parameters such as BTU metering and other functional requirements required by client by providing the minimum manpower as per the details given in the Annexure A Operation for Biopark- I & II a. First year after handing over the installation - lumpsum fee for 1 year

b. Second year after handing over the installation - lumpsum fee for 1 year c. Third year after handing over the installation d. Fourth year after handing over the installation e. Fifth year after handing over the installation - lumpsum fee for 1 year - lumpsum fee for 1 year - lumpsum fee for 1 year TOTAL Note: 1.The escalation for operating cost for any consecutive year should no exceed 5 % value of the lumpsum see quoted for Previous year by the tenderer. 2.The tenderers have to inspect the Exisiting ACMV system in Bio Park-I before Quoting. 3.The selected contractor has to operate the existing system at TICEL-I and the proposed new installations in Ticel-II C/o to ABSTRACT-I

Station :

Date :

Signature of Tenderer

ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

MISCELLANEOUS WORK BILL OF QUANTITIES


SI No Descriptionof works Amount Remarks

II. NON COMPREHENSIVE MAINTENANCE CONTRACT FEE FOR 3 1/2 YEARS AFTER DEFECTS LIABLILITY PERIOD FOR TICEL BIO PARK-II AND 5YEAR NON COMPREHENSIVE MAINTENANCE FOR TICEL-I ( CONSIDERED FOR BID EVALUATION PURPOSE ) Maintenance of the ACMV system supplied, installed commissioned by successfull tenderer for Ticel Bio Park II for a period 3 1/2 years beyond the defects liability period (DLP) and as well as the previous ACMV systems installed in existing Ticel ( Annexure B ). The above scope of maintenance includes periodical maintenance, preventive maintenance and breakdown maintenance of all the ACMV installations, Equipements and components at Ticel including Annual Maintenance / servicing of all chillers,pumps , AHUs Heat Recoverywheel units, Latent Energy storage Tanks, Exhaust fans, Fresh air fans, Mechanincal ventilation system, car park jet fans, etc., and break down repairs as and when occured, ensuring that system does not remain out of service for a period more than 8 hours in case of major breakdowns and one hour in the case of minor breakdowns due to any unforeseen circumstances by providing the minimum man power as per the details given in the Annexture A. The successful tenderer shall keep the essential spares at TICEL for Bio Park-II during the Defects Liablity period to avoid the delay in attending faults / maintenance FOR Ticel Bio Park II,no maintenance charges for one and half years shall be paid.

a. For 18months after handing over of installation for Bio Park-I ( Non comprehensive)(DLP of TICEL-II) b. For 6 months non comprehensive maintenance for Bio Park-I & II (After DLP) (for Non comprehensive Maintenance of Bio Park-I& II )- Lumpsum Fee for six months c. Third Year after Handing over the Installation of Bio Park-II (for Non comprehensive Maintenance of Bio Park-I& II )- Lumpsum Fee for one year d. Fourth Year after Handing over the Installation of Bio Park-II (for Non comprehensive Maintenance of Bio Park-I& II )-Lumpsum Fee for one year e. Fifth Year after Handing over the Installation of Bio Park-II (for Non comprehensive Maintenance of Bio Park-I& II )-Lumpsum Fee for one year TOTAL
Note: 1.The Escalation for maintenance cost for any consecutive year should no exceed 5 % value of the lumpsum fee quoted for the Preview year by the tender Station : Date : ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM Signature of Tenderer C/o to ABSTRACT-I

TICEL BIO PARK II

ACMV WORKS

ANNEXURE A MINIMUM MANPOWER REQUIREMENT FOR ACMV OPERATION & MAINTENANCE SERVICES
SI No A 1 Designation ACMV WORKS Operation & Maintenance incharge (in General Shift) Shift Supervisor for O&M (including one Reliever) Technician (General shift -2 Nos.and in shift-7 Nos.including one Reliever 1 Engineering Graduate / Mechanical Minimum 7 years experience in Operation and maintenance of ACMV Engineering system in Highrise buildings like IT parks / Star Hotels Diploma in Mechanical Minimum 7 years experience in Operation and maintenance of ACMV system in Highrise buildings like IT parks / Star Hotels No of persons Qualification Maximum Experience ( No of Years )

ITI

Minimum 7 years experience in Operation and maintenance of ACMV system in Highrise buildings like IT parks / Star Hotels

Note: The above man power is the minimum requirement for routine operation and maintenance of ACMV system. In case of any emergency major breakdowns and for annual maintenance etc., If the contractor feels that the above minimum manpower is not adequate, the contractor shall engage more manpower during those times without any additional cost. Apart from the regular O&M contract fee, no seperate labour charges or service charges will be paid for any of the maintenance / servicing of the ACMV system installations / Euipments / Components during the contract period.

Station :

Date :

Signature of Tenderer

ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

ACMV WORKS

ANNEXURE B - NON DEFFECTS LIABILITY PERIOD ITEMS EXISTING TICEL BIO PARK - I EQUIPEMENTS LIST
SI No A 1 2 3 4 5 6 7 8 a b c d e f g h i j k l m n o ACMV WORKS 200 TR Air Cooled Water Chiller 200 TR Air Cooled Brine Chiller Primary / Secondary chilled water / Chilled brine Pumps Primary and secondary chiller water / brine piping system with insulation Duct and duct insulation works Toilet Exhaust System Terrace Exhaust Blower Air Handling Units - 3 TR to 100 TR 1.5 TR 3 TR 5.5 TR 8.3 TR 10 TR 15 TR 16.5 TR 18 TR 31 TR 34 TR 38 TR 65 TR 67 TR 92 TR 100 TR 6 3 1 27 7 1 1 1 1 2 2 2 2 1 1 2 2 2 2 11 Description QTY REMARKS

ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM