A range of low cost thermistor sensors comprising insertion, clamp-on, and outside air versions. A quick-release lid makes the TB/T.. range easy to install. The insertion sensor may be used for duct or immersion purposes. It has a 6 mm diameter brass probe which is suitable for retrofit immersion applications and will fit most existing pockets (universal fitting kit option). Brass and 316 stainless steel pockets are available. A foam gasket is fitted, and an adjustable depth flange option is available for its use as a duct sensor, enabling the insertion depth to be adjusted.
Features
Low cost High quality thermistors Brass probes M20 conduit entry with cable gland IP67 housing Quarter turn quick release lid Easy to wire Universal fitting kit option for retrofit of immersion sensors Adjustable insertion depth flange option for duct sensors
Physical
Insertion sensors (duct/immersion) (TB/TI) 400 mm (15.75) (TB/TI/L) 150 mm (5.91) (TB/TI/S)
6 mm (0.24)
109 mm (4.29)
M20 gland
50 mm (1.97)
2 mm grub screw
97 mm (3.82)
spring
57 mm (2.24)
1
TB/TC, /TI, /TO Thermistor Room Temperature Sensors Data Sheet TA200724 Issue 1/B 16/02/04
9.5 mm (0.37)
Adjustable Depth Flange Universal Fitting Kit (ACC/DF/6) (ACC/UF) adjustable insertion depth for immersion sensor use for duct sensor use in existing pockets
102 mm (4.02)
Data Sheet
Choose an accessible location for the sensor head, where the element will make good contact with the surface that is to be measured. The probe temperature range is -40 C to +100 C (-40 F to +212 F). However the sensors measurement range is -30 C to +100 C (-22 F to +212 F). Strap the sensor head to the pipe using the jubilee clip provided. Wrap the clip around the pipe, pass the sensor head under the strap, and tighten the screw (as shown). Ensure that good contact is made between the sensor head and the surface. Where possible use a thermally conductive paste to ensure a good thermal contact and apply any insulation over both sensing element and pipe.
tighten screw
Junction Box
The junction box should be mounted on a flat surface. Choose a position which is a maximum of 2 m (6) away from the sensor head. The permitted ambient temperature range is -40 C to +50 C (-40 F to +122 F). Avoid direct contact with steam. Screw the junction box in position using 2 No. 6 screws, (85 mm, 3.35 fixing centres).
2 off No 6 screws
85 mm (3.35) centres
TB/TI Mechanical
The probe temperature range is -40 C to +110 C (-40 F to +230 F); the box range is -40 C to +50 C (-40 F to 122 F). However the sensors measurement range is -30 C to +110 C (-22 F to +230 F).
duct
2 mm Allen key
TB/TC, /TI, /TO Thermistor Room Temperature Sensors Data Sheet TA200724 Issue 1/B 16/02/04
Data Sheet
Retrofit to existing pocket
The Universal Fitting Kit enables sensor to be fixed to a number of different pocket types. Adjust position of brass bush on probe so that probe inserts fully into pocket using 2 mm hexagonal socket key to adjust grub screw.
For pockets with a clip retaining groove simply insert probe into pocket and pull the metal clip over the over the top of the pocket to engage in the groove.
For pockets which fix sensor by a grub screw, tighten pocket grub screw onto brass bush. If necessary, spring and clip can be removed.
TB/TO Mechanical
Choose an accessible location on a north facing wall (unless in the southern hemisphere), ensuring that the sensor is sited away from direct sunlight, and any heat sources which may come from the building - e.g. heating flues, open windows etc. Do not install the sensor in a location where it will be exposed to temperatures outside the boxs temperature range (-40 C to +50 C, -40 F to 122 F). However the sensors measurement range is -30 C to +50 C (-22 F to +122 F). Mark the position of the 2 fixing holes with 85 mm (3.35) fixing centres. Drill holes in the positions marked. Fix the sensor to the wall with 2 No 6 screws.
2 off No 6 screws
Full installation details are given in the individual installation instructions numbered as follows: TB/TO TB/TC TB/TI Outside Air Thermistor Temperature Sensor Installation Instructions Clamp-on Thermistor Temperature Sensor Installation Instructions Insertion Thermistor Temperature Sensor Installation Instructions TG200725 TG200726 TG200727
PRODUCT CODES
TB/TO TB/TI/S TB/TI/L TB/TC POC/SS/6 POC/B/6 ACC/UF ACC/DF/6 Outside Air Thermistor Temperature Sensor Insertion Thermistor Temperature Sensor (for duct or immersion use) with foam gasket fitted (short - 150 mm, 5.91) Insertion Thermistor Temperature Sensor (for duct or immersion use) with foam gasket fitted (long - 400 mm, 15.75) Clamp-on Thermistor Temperature Sensor supplied with jubilee clip 6 mm stainless steel pocket for TB/TI (immersion use) 6 mm brass pocket for TB/TI (immersion use) Universal fitting kit (retrofit to existing pockets) for TB/TI (immersion use) Adjustable depth flange for TB/TI (duct use)
TB/TC, /TI, /TO Thermistor Room Temperature Sensors Data Sheet TA200724 Issue 1/B 16/02/04
Data Sheet
:-40 C to +50 C (-40 F to +122 F) :-40 C to +100 C (-40 F to +212 F) :-40 C to +110 C (-40 F to +230 F) :0 to 95 %RH :-30 C to +50 C (-22 F to +122 F) :-30 C to +100 C (-22 F to +212 F) :-30 C to +110 C (-22 F to +230 F) :M20 cable gland :1 part screw terminals for 0.5 to 2.5 mm2 cross section (14 to 20 AWG) cable :57 mm (2.24) x 109 mm (4.29) max diameter, cable 2 m (66) :57 mm (2.24) x 102 mm (4.02) max diameter :(box)57 mm (2.24) x 102 mm (4.02), /S probe 150 mm (5.91) x 6 mm /L probe 400 mm (15.75) x 6 mm
Input channels and sensor scaling For IQ controllers link input channel for thermistor, T and set up the sensor type scaling; the recommended method of setting the sensor type scaling is to use SET. For all IQ2 series controllers with firmware of version 2.1 or greater, or IQ3 series controllers, one of the following SET Part Numbers should be used: Trend Thermistor TB (C) Novar Thermistor TB (F) If not using the full range (-30 C to +110 C, -22 F to +230 F), the values for U and L should be changed to suit the range as shown in the following tables. If not using SET, use sensor type scaling mode 5, characterise, and the following tables for all IQ2 series controllers with firmware of version 2.1 or greater, or IQ3 controllers; for all other IQ controllers see the Sensor Scaling Reference Card, TB100521A. Using SET or these tables on IQ2 (firmware >v2.1) or IQ3 gives the following system accuracies: -10 C to +40 C :1 C (14 F to +104 F, 1.6 F) -30 C to +50 C :2 C (-22 F to +122 F, 3.5 F) -30 C to +100 C :3.2 C (-22 F to +212 F, 5.7 F) -30 C to +110 C :3.7 C (-22 F to +230 F, 6.6 F)
Material Enclosure :Impact resistant ABS /TI, /TO probes :Brass /TC probe :Plated copper POC/SS/6 :pocket, 316 stainless steel/silver solder POC/B/6 :pocket, brass/silver solder Environmental Protection:IP67 -30 C to +110 C (-22 F to 230 F)
Units: Y E U L P x 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Input type Exponent Upper Lower Points
C 3 115 -35 20 Ox 110 105 100 95 90 85 80 70 60 50 40 30 10 0 -5 -10 -15 -20 -25 -30
Units: Y E
Input type Exponent Upper Lower Points
Units: Y E
Input type Exponent Upper Lower Points
C 3 45 -15 6 Ox 40 30 10 0 -5 -10
1 (therm V)
1 (therm V)
1 (therm V)
1 (therm V)
239 -31
U L P x
221 -31
U L P x
131 -31
U L P x
113 -5
Ix 0.480 0.549 0.630 0.724 0.833 0.961 1.110 1.484 1.985 2.641 3.470 4.460 6.663 7.668 8.102 8.482 8.807 9.078 9.299 9.476
Ix 0.630 0.724 0.833 0.961 1.110 1.484 1.985 2.641 3.470 4.460 6.663 7.668 8.102 8.482 8.807 9.078 9.299 9.476
Ix 2.641 3.470 4.460 6.663 7.668 8.102 8.482 8.807 9.078 9.299 9.476
230 220 212 203 194 185 176 158 140 122 104 86 50 32 23 14 5 -4 -13 -22
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
212 203 194 185 176 158 140 122 104 86 50 32 23 14 5 -4 -13 -22
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6
104 86 50 32 23 14
Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
P.O. Box 34, Horsham, West Sussex, RH12 2YF United Kingdom Telephone +44 (0)1403 211 888 E-mail trendinfo@novar.com Fax (International) +44 (0)1403 210982
Registered office. Novar House 24 Queens Road Weybridge Surrey KT13 9UX Registered in England No 1664519
TB/TC, /TI, /TO Thermistor Room Temperature Sensors Data Sheet TA200724 Issue 1/B 16/02/04