You are on page 1of 2

PVC-JZ/OZ-CY

Anwendung
als Energie-, Steuer-, Anschluss- und Verbindungsleitung in elektrischen Anlagen, fr strfreie Daten- und Signalbertragung, fr feste Verlegung und flexible Anwendungen bei freier Bewegung ohne Zugbeanspruchung und ohne zwangsweise Fhrung. Geeignet fr Verlegung in trockenen und feuchten Rumen, jedoch nicht im Freien ohne UV-Schutz und nicht im Erdreich.

Application
power, control and connecting cable in electrical facilities for lossless data and signal transmission, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Besonderheiten
4 kV Prfspannung weitgehend bestndig gegen Suren, Laugen und bestimmte le. LBS-frei/silikonfrei (bei Produktion) platzsparende Alternative zu PVC-JZ/OZ-YCY empfohlen fr EMV gerechte Anwendung

Special features
4 kV testing voltage largely resistant to acids, bases and usual oils free from lacquer damaging substances and silicone (during production) space-saving alternative to PVC-JZ/OZ-YCY recommended for EMC-applications

Hinweise
RoHS-konform konform zur 73/23/EWG-Richtlinie ("Niederspannungsrichtlinie") CE. Sonderausfhrungen, andere Abmessungen, Querschnitte, Ader- und Mantelfarben fertigen wir auf Anfrage.

Remarks
conform to RoHS conform to 73/23/EWG-Guideline CE. We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Aufbau & Technische Daten


Leiter Werkstoff Leiterklasse Aderisolationswerkstoff Aderkennung Verseilung Gesamtschirm Auenmantelwerkstoff Mantelfarbe Nennspannung Prfspannung Leiterwiderstand Isolationswiderstand Strombelastbarkeit Kapazitt Induktivitt kleinster Biegeradius fest kleinster Biegeradius bewegt Betriebstemp. fest min/max Betriebstemp. bew. min/max Temperatur am Leiter max. Brandverhalten Standard Cu-Litze blank nach DIN VDE 0295 Klasse 5 bzw. IEC 228 class 5 PVC nach DIN VDE 0293 schwarze Adern mit weissen Ziffern mit oder ohne gn/ge Adern in Lagen verseilt Cu-Geflecht verzinnt; opt. Bedeckung ca. 85 % PVC grau, RAL 7001 Uo/U: 300/500 V Ader/Ader: 4 kV Ader/Schirm: 2 kV nach DIN VDE 0295 Klasse 5 bzw. IEC 228 class 5 min. 20 M x km gem. DIN VDE, siehe Technischer Anhang Ader/Ader ca. 120 nF/km; Ader/Schirm ca. 155 nF/km ca. 0,67 mH/km 6xd 15 x d -30 C / +80 C - 5 C / +70 C + 70 C im Betrieb; +150 C im Kurzschlufall selbstverlschend und flammwidrig nach IEC 332-1 in Anlehnung an DIN VDE 0245, 0250 und 0281

Structure & Specifications


conductor material conductor class core insulation core identification stranding overall shield outer sheath sheath colour rated voltage testing voltage conductor resistance insulation resistance current carrying capacity capacity inductivity min. bending radius fixed min. bending radius moved operat. temp. fixed min/max temp. at conductor burning behavior standard bare copper strand acc. to DIN VDE 0295 class 5 resp. IEC 228 class 5 PVC acc. to DIN VDE 0293 black cores with white numerals with or without gn/ye stranded in layers copper braid tinned; coverage approx. 85 % PVC grey, RAL 7001 Uo/U: 300/500 V core/core: 4 kV core/shield: 2 kV acc. to DIN VDE 0295 class 5 resp. IEC 228 class 5 min. 20 M x km acc. to DIN VDE, see Technical Guidelines core/core ca. 120 nF/km; core/shield ca. 155 nF/km ca. 0,67 mH/km 6xd 15 x d -30 C / +80 C + 70 C in operation; +150 C in case of short-circuit self-extinguishing and flame-retardant acc. to IEC 332-1 acc. to DIN VDE 0245, 0250 and 0281

operat. temp. moved min/max - 5 C / +70 C

01.01.06

PVC-JZ/OZ-CY

Abmessung dimension n x mm 2 X 0,5 3 G 0,5 4 G 0,5 5 G 0,5 7 G 0,5 12 G 0,5 18 G 0,5 25 G 0,5 2 X 0,75 3 G 0,75 4 G 0,75 5 G 0,75 7 G 0,75 12 G 0,75 18 G 0,75 25 G 0,75 2 X 1,0 3 G 1,0 4 G 1,0 5 G 1,0 7 G 1,0 12 G 1,0 18 G 1,0 25 G 1,0 2 X 1,5 3 G 1,5 4 G 1,5 5 G 1,5 7 G 1,5 12 G 1,5 18 G 1,5 25 G 1,5 34 G 1,5 3 G 2,5 4 G 2,5 5 G 2,5 7 G 2,5 12 G 2,5 18 G 2,5 25 G 2,5

Auen- outer mm 5,8 6,1 6,5 7,0 7,5 9,9 11,5 13,4 6,2 6,5 7,0 7,7 8,3 10,9 12,7 14,8 6,5 6,5 7,3 8,1 8,8 11,5 13,9 15,9 7,1 7,5 8,2 8,9 9,9 13,0 15,6 17,9 20,8 8,9 9,9 11,0 11,9 16,0 19,0 22,2

Cu-Zahl copper weight kg/km 36,0 43,0 49,0 57,0 69,0 104,0 141,0 211,0 43,0 52,0 61,0 72,0 89,0 138,0 211,0 280,0 51,0 62,0 74,0 88,0 112,0 185,0 268,0 354,0 65,0 82,0 100,0 119,0 154,0 268,0 373,0 530,0 683,0 118,0 147,0 176,0 253,0 355,0 569,0 827,0

Gewicht weight kg/km 45,0 59,0 83,0 96,0 136,0 200,0 275,0 350,0 56,0 70,0 95,0 130,0 168,0 232,0 315,0 435,0 84,0 110,0 130,0 156,0 192,0 285,0 395,0 656,0 97,0 125,0 165,0 193,0 245,0 365,0 553,0 734,0 944,0 188,0 236,0 270,0 340,0 589,0 978,0 1.358,0

Abmessung dimension n x mm 4G4 7G4 4G6 7G6 4 G 10 7 G 10 4 G 16 7 G 16 4 G 25 4 G 35

Auen- outer mm 11,6 14,4 14,2 17,0 17,2 21,4 20,2 24,8 25,1 30,4

Cu-Zahl copper weight kg/km 248,0 355,0 343,0 505,0 535,0 820,0 800,0 1.470,0 1.075,0 1.576,0

Gewicht weight kg/km 305,0 500,0 440,0 672,0 710,0 1.305,0 1.050,0 1.813,0 1.570,0 2.070,0

01.01.06

You might also like