Control and Instrumentation Cables

4
Control and Instrumentation Cables
BS5308 Part 1 Type 1 Multipair: Collective Screen, Unarmoured . . . . . . . . . . . . . . . . . . .4:2 Individual & Collective Screen, Unarmoured . . . . . . . . .4:4 BS5308 Part 1 Type 2 Multipair: Collective Screen, Armoured . . . . . . . . . . . . . . . . . . . . .4:6 Individual & Collective Screen, Armoured . . . . . . . . . . .4:8 BS5308 Part 1 Type 1 LSF Multipair: Collective Screen, Unarmoured . . . . . . . . . . . . . . . . . .4:10 Individual & Collective Screen, Unarmoured . . . . . . . .4:12 BS5308 Part 1 Type 2 LSF Multipair: Collective Screen, Armoured . . . . . . . . . . . . . . . . . . . 4:14 Individual & Collective Screen, Armoured . . . . . . . . . .4:16 BS5308 Part 1 Type 1 LSF Multicore: Collective Screen, Unarmoured . . . . . . . . . . . . . . . . . .4:18 BS5308 Part 1 Type 2 LSF Multicore: Collective Screen, Armoured . . . . . . . . . . . . . . . . . . . 4:20 Technical Information for BS5308 Part 1 . . . . . . .4:22 BS5308 Part 2 Type 1 Multipair: Collective Screen, Unarmoured . . . . . . . . . . . . . . . . . .4:24 BS5308 Part 2 Type 2 Multipair: Collective Screen, Armoured . . . . . . . . . . . . . . . . . . . .4:26 Individual & Collective Screen, Armoured . . . . . . . . . .4:28 BS5308 Part 1 Type 2 LSF Fire Resistant: Collective Screen, Armoured . . . . . . . . . . . . . . . . . . . .4:30 Technical Information for BS5308 Part 2 . . . . . . .4:32 CES20 Part 4 Type 143 . . . . . . . . . . . . . . . . . . . . . . . . 4:34 Technical Information for CES20 Part 4 Type 143 . .4:36 ESI* 09-6 Issue 5: Multipair PVC Insulated & Sheathed Armoured, Un-screened/Screened . . . . . . . . . . . . . . . . . . . . . . . . .4:38 Technical Information for ESI* 09-6 Issue 5 . . . . .4:40 ENATS* 09-6 Issue 7: Multipair PVC Insulated & Sheathed Armoured, Un-screened . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4:42 Collective Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . .4:44 ENATS 09-6 Issue 7: Multipair PE Insulated & LSF Sheathed Armoured, Un-screened . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4:46 Collective screen . . . . . . . . . . . . . . . . . . . . . . . . . . . .4:48 For Multicore Control Cables see Section 1 Technical Information for ENATS* 09-6 Issue 7 . .4:50 Multipair PVC Insulated KCB (VX) Thermocouple Compensating Cables . . . . . . . . . . . . . . . . . . . . . . .4:52 Traffic Control System Cables Single-Core Loop Detector Cables . . . . . . . . . . . . . . . .4:54 Single & Multipair Unarmoured Feeder Cables . . . . . . .4:56 Single & Multipair Armoured Feeder Cables . . . . . . . . .4:58 Armoured Multicore Junction High Voltage Cable . . . . .4:60 TRAFFIC CONTROL SYSTEM CABLES (4:54) These cables are used in the monitoring of traffic movement and implementing selective use of traffic lights to improve traffic flow. The system uses loop detector cables for traffic monitoring with multipair/core cables used for signal control and signal power.

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Not suitable for direct buried applications (see cables types 2 and 3).

Multipair PE Insulated Instrumentation Cable

BS5308 Part 1 Type 1


Collective Screen, Unarmoured 300/500 V

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 1 Conductors: Solid (Class 1), stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 1 on page 4:22 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

Outer Sheath: PVC outer sheath Type TM.1 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

042

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated Instrumentation Cable

BS5308 Part 1 Type 1


Collective Screen, Unarmoured 300/500 V
Anixter Number Number of Pairs/Triple Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7-M21-0001LF A7-M21-0002LF A7-M21-0005LF A7-M21-0010LF A7-M21-0020LF A7-M21-0001TLF 1P 2P(Quad) 5P 10P 20P 1T 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 mm 0.60 0.60 0.60 0.60 0.60 0.60 Nominal O/D mm 7.00 7.90 13.10 17.20 22.30 7.30 Approx. Cable Weight kg/km 60 80 200 340 570 68 Min Bending Radius (fixed bend) mm 60 70 110 140 180 60

2 3 4 5 6 7 8 9 10 11 12 13 14 15

A7-M31-0001LF A7-M31-0002LF A7-M31-0005LF A7-M31-0010LF A7-M31-0020LF A7-M31-0001TLF

1P 2P(Quad) 5P 10P 20P 1T

0.75 0.75 0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60 0.60 0.60

7.40 8.40 13.80 18.90 24.60 7.80

75 100 250 450 920 80

60 70 120 150 200 70

A7-L11-0001LF A7-L11-0002LF A7-L11-0005LF A7-L11-0010LF A7-L11-0020LF A7-L11-0001TLF

1P 2P(Quad) 5P 10P 20P 1T

1.00 1.00 1.00 1.00 1.00 1.00

1/1.13 1/1.13 1/1.13 1/1.13 1/1.13 1/1.13

0.60 0.60 0.60 0.60 0.60 0.60

7.40 8.40 14.20 18.40 24.40 7.70

85 115 290 500 950 105

60 70 120 150 200 70

A7-L31-0001LF A7-L31-0002LF A7-L31-0005LF A7-L31-0010LF A7-L31-0020LF A7-L31-0001TLF

1P 2P(Quad) 5P 10P 20P 1T

1.50 1.50 1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60

8.30 9.70 16.40 21.60 28.50 8.70

100 150 360 670 1230 120

70 80 140 180 230 80

16 17 18 19 20

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 1 and details are available upon request. 0.5mm2 cables are also available with solid conductors (1/0.8mm). Details available upon request. For low smoke zero halogen alternative see page 4:10. For further technical information refer to page 4:22.
Products. Technology. Services. Delivered Globally.

www.anixter.com

043

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications

Multipair PE Insulated Instrumentation Cable

BS5308 Part 1 Type 1


Individual and Collective Screen, Unarmoured 300/500 V

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Not suitable for direct buried applications (see cables types 2 and 3).

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 1 Conductors: Solid (Class 1), stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: Pairs will be numbered, each pair containing 1 black and 1 blue core 100mm maximum pair lay length (minimum 10 twists per metre) Individual Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Screen Isolation Tape: numbered p.e.t.p. tape applied over each individually screened pair Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

Outer Sheath: PVC outer sheath Type TM.1 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

044

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated Instrumentation Cable

2 3 4 5 6 7 8 9 10

BS5308 Part 1 Type 1


Individual and Collective Screen, Unarmoured 300/500 V
Anixter Number Number of Pairs/Triple Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7-P51-0002LF A7-P51-0005LF A7-P51-0010LF A7-P51-0020LF 2P 5P 10P 20P 0.50 0.50 0.50 0.50 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 mm 0.60 0.60 0.60 0.60 Nominal O/D mm 10.70 13.60 19.00 24.60 Approx. Cable Weight kg/km 160 250 480 780 Min Bending Radius (fixed bend) mm 100 130 170 220

A7-W71-0002LF A7-W71-0005LF A7-W71-0010LF A7-W71-0020LF

2P 5P 10P 20P

0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60

11.40 14.50 20.40 26.80

190 270 550 960

110 140 190 240

A7-N41-0002LF A7-N41-0005LF A7-N41-0010LF A7-N41-0020LF

2P 5P 10P 20P

1.00 1.00 1.00 1.00

1/1.13 1/1.13 1/1.13 1/1.13

0.60 0.60 0.60 0.60

11.30 14.50 20.40 26.70

200 290 580 1010

110 130 190 240

11 12 13

A7-V61-0002LF A7-V61-0005LF A7-V61-0010LF A7-V61-0020LF

2P 5P 10P 20P

1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60

13.10 16.80 23.90 27.60

250 400 800 1400

120 160 220 280

14 15 16 17 18 19 20

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 1 and details are available upon request. 0.5mm2 cables are also available with solid conductors (1/0.8mm). Details available upon request. For low smoke zero halogen alternative see page 4:12. For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

045

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Suitable for direct buried applications.

Multipair PE Insulated Instrumentation Cable

BS5308 Part 1 Type 2


Collective Screen, Armoured 300/500 V

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 1 Conductors: Solid (Class 1), stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 1 page 4:22 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Polythene bedding Type 2C or 03 to BS6234

Mild galvanised steel wires to BS EN10257-1 Outer Sheath: PVC outer sheath Type TM.1 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

046

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated Instrumentation Cable

2 3 4 5

BS5308 Part 1 Type 2


Collective Screen, Armoured 300/500 V
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7-M22-0001LF A7-M22-0002LF A7-M22-0005LF A7-M22-0010LF A7-M22-0020LF A7-M22-0001TLF A7-M32-0001LF A7-M32-0002LF A7-M32-0005LF A7-M32-0010LF A7-M32-0020LF A7-M32-0001TLF A7-L12-0001LF A7-L12-0002LF A7-L12-0005LF A7-L12-0010LF A7-L12-0020LF A7-L12-0001TLF A7-L32-0001LF A7-L32-0002LF A7-L32-0005LF A7-L32-0010LF A7-L32-0020LF A7-L32-0001TLF 1P 2P(Q) 5P 10P 20P 1TR 1P 2P(Q) 5P 10P 20P 1TR 1P 2P(Q) 5P 10P 20P 1TR 1P 2P(Q) 5P 10P 20P 1TR 0.5 0.5 0.5 0.5 0.5 0.5 0.75 0.75 0.75 0.75 0.75 0.75 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 1/1.13 1/1.13 1/1.13 1/1.13 1/1.13 1/1.13 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 Insulation Thickness Nominal Diameter Under Armour mm 7.00 7.90 13.10 17.20 22.30 7.30 7.40 8.40 13.80 18.90 24.60 7.80 7.40 8.40 14.20 18.40 24.40 7.70 8.30 9.70 16.40 21.60 28.50 8.70 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 250 300 560 970 1640 270 280 330 750 1260 1890 300 290 345 790 1310 2040 310 330 420 940 1500 2400 350 Min Bending Radius (fixed bend) mm 100 100 150 190 240 100 100 110 160 210 260 100

mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 0.90 0.90 1.25 1.60 0.90 0.90 0.90 1.25 1.60 1.60 0.90 0.90 0.90 1.25 1.25 1.60 0.90 0.90 0.90 1.25 1.60 1.60 0.90

mm 11.40 12.30 17.90 22.90 29.10 11.70 11.80 13.00 19.30 25.50 31.60 12.20 11.80 13.00 19.70 24.30 31.20 12.30 12.90 14.30 22.10 28.40 35.70 13.30

6 7 8 9 10 11 12

100 110 160 200 250 100

13 14 15

110 120 180 230 290 110

16 17 18 19 20

(Q) = Quad N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 1 and details are available upon request. 0.5mm2 cables are also available with solid conductors (1/0.8mm). Details available upon request. For low smoke zero halogen alternative see page 4:14. For further technical information refer to page 4:22.
Products. Technology. Services. Delivered Globally.

www.anixter.com

047

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Suitable for direct buried applications.

Multipair PE Insulated Instrumentation Cable

BS5308 Part 1 Type 2


Individual and Collective Screen, Armoured 300/500 V

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 1 Conductors: Solid (Class 1), stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: Pairs will be numbered, each pair containing 1 black and 1 blue core 100mm maximum pair lay length (minimum 10 twists per metre) Individual Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Screen Isolation Tape: numbered p.e.t.p. tape applied over each individually screened pair Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

Polythene bedding Type 2C or 03 to BS6234 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: PVC outer sheath Type TM.1 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

048

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated Instrumentation Cable

2 3 4 5

BS5308 Part 1 Type 2


Individual and Collective Screen, Armoured 300/500 V
Anixter Number Number Nom. of Cond. Pairs/ Area Triple mm2 A7-P52-0002LF A7-P52-0005LF A7-P52-0010LF A7-P52-0020LF 2P 5P 10P 20P 0.5 0.5 0.5 0.5 Nominal Cond. Stranding #/mm 16/0.20 16/0.20 16/0.20 16/0.20 Insulation Thickness Nominal Diameter Under Armour mm 10.70 13.60 19.00 24.60 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 460 760 1300 1870 Min Bending Radius (fixed bend) mm 140 170 230 280

mm 0.60 0.60 0.60 0.60

mm 0.90 1.25 1.60 1.60

mm 15.30 19.10 25.60 31.60

6 7 8

A7-W72-0002LF A7-W72-0005LF A7-W72-0010LF A7-W72-0020LF

2P 5P 10P 20P

0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60

11.40 14.60 20.40 26.80

0.90 1.25 1.60 2.00

16.00 20.00 27.00 33.80

500 920 1610 2420

150 180 240 310

9 10 11 12 13 14 15 16 17 18 19 20

A7-N42-0002LF A7-N42-0005LF A7-N42-0010LF A7-N42-0020LF

2P 5P 10P 20P

1.0 1.0 1.0 1.0

1/1.13 1/1.13 1/1.13 1/1.13

0.60 0.60 0.60 0.60

11.30 14.50 20.40 26.70

0.90 1.25 1.60 2.00

15.90 20.00 27.00 33.70

515 950 1670 2540

150 180 240 310

A7-V62-0002LF A7-V62-0005LF A7-V62-0010LF A7-V62-0020LF

2P 5P 10P 20P

1.5 1.5 1.5 1.5

7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60

13.10 16.80 23.90 31.10

1.25 1.60 1.60 2.00

18.60 22.50 30.70 39.30

730 1180 1820 3030

170 210 270 350

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 1 and details are available upon request. 0.5mm2 cables are also available with solid conductors (1/0.8mm). Details available upon request. For low smoke zero halogen alternative see page 4:16. For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

049

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 1 on page 4:22 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Outer Sheath: Black LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multipair PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 1 LSF


Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Not suitable for direct buried applications (see cable type 2).

Products. Technology. Services. Delivered Globally.

0410

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated LSF Instrumentation Cable

2 3 4 5 6 7 8 9

BS5308 Part 1 Type 1 LSF


Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number of Pairs/Triple Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7W1-P001L-02 A7W1-P002L-02 A7W1-P005L-02 A7W1-P010L-02 A7W1-P020L-02 A7W1-P030L-02 A7W1-P050L-02 1P 2P(Quad) 5P 10P 20P 30P 50P 0.50 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60 Nominal O/D mm 7.00 7.90 13.10 17.20 22.30 26.90 33.90 Approx. Cable Weight kg/km 60 80 200 340 570 790 1270 Min Bending Radius (fixed bend) mm 60 70 110 140 180 220 280

A7DF1-P001L-02 A7DF1-P002L-02 A7DF1-P005L-02 A7DF1-P010L-02 A7DF1-P020L-02 A7DF1-P030L-02 A7DF1-P050L-02

1P 2P(Quad) 5P 10P 20P 30P 50P

0.75 0.75 0.75 0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60 0.60 0.60 0.60

7.40 8.40 13.80 18.90 24.60 28.90 36.90

75 100 250 450 920 1200 1920

60 70 120 150 200 240 300

10 11 12 13 14 15 16 17 18 19 20

A7BT1-P001L-02 A7BT1-P002L-02 A7BT1-P005L-02 A7BT1-P010L-02 A7BT1-P020L-02 A7BT1-P030L-02 A7BT1-P050L-02

1P 2P(Quad) 5P 10P 20P 30P 50P

1.50 1.50 1.50 1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60 0.60

8.30 9.70 16.40 21.60 28.50 34.30 43.60

100 150 360 670 1230 1730 2700

70 80 140 180 230 280 350

For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0411

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: Pairs will be numbered, each pair containing 1 black and 1 blue core 100mm maximum pair lay length (minimum 10 twists per metre) Individual Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Screen Isolation Tape: numbered p.e.t.p. tape applied over each individually screened pair Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Outer Sheath: Black or Blue LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multipair PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 1 LSF


Individual and Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Not suitable for direct buried applications (see cable type 2).

Products. Technology. Services. Delivered Globally.

0412

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated LSF Instrumentation Cable

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

BS5308 Part 1 Type 1 LSF


Individual and Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number of Pairs/Triple Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7Z1-P002L A7Z1-P005L A7Z1-P010L A7Z1-P020L A7Z1-P030L A7Z1-P050L 2P 5P 10P 20P 30P 50P 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 mm 0.60 0.60 0.60 0.60 0.60 0.60 Nominal O/D mm 10.70 13.60 19.00 24.60 29.20 37.10 Approx. Cable Weight kg/km 160 250 480 780 1100 1590 Min Bending Radius (fixed bend) mm 100 130 170 220 260 340

A7DG1-P002L A7DG1-P005L A7DG1-P010L A7DG1-P020L A7DG1-P030L A7DG1-P050L

2P 5P 10P 20P 30P 50P

0.75 0.75 0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60 0.60 0.60

11.40 14.50 20.40 26.80 31.50 40.30

190 270 550 960 1320 2120

110 140 190 240 290 360

A7CS1-P002L A7CS1-P005L A7CS1-P010L A7CS1-P020L A7CS1-P030L A7CS1-P050L

2P 5P 10P 20P 30P 50P

1.50 1.50 1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60

13.10 16.80 23.90 31.10 36.80 47.20

250 400 800 1400 2040 3250

120 160 220 280 330 420

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02. Eg. A7Z1-P002L-02 For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0413

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 1 page 4:22 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down LSF inner sheath to BS6724 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black or Blue LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multipair PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 2 LSF


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Suitable for direct buried applications.

Products. Technology. Services. Delivered Globally.

0414

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated LSF Instrumentation Cable

2 3 4 5

BS5308 Part 1 Type 2 LSF


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7W2-P001L A7W2-P002L A7W2-P005L A7W2-P010L A7W2-P020L A7W2-P030L A7W2-P050L 1P 2P(Q) 5P 10P 20P 30P 50P 0.5 0.5 0.5 0.5 0.5 0.5 0.5 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 Insulation Thickness Nominal Diameter Under Armour mm 7.0 7.9 12.9 17.4 22.5 26.7 33.9 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 265 315 620 1075 1820 2345 3680 Min Bending Radius (fixed bend) mm 100 100 150 190 240 330 420

mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 0.90 0.90 1.25 1.60 1.60 2.00

mm 11.40 12.30 17.70 23.10 29.30 33.70 42.10

6 7 8 9 10 11 12 13 14

A7DF2-P001L A7DF2-P002L A7DF2-P005L A7DF2-P010L A7DF2-P020L A7DF2-P030L A7DF2-P050L

1P 2P(Q) 5P 10P 20P 30P 50P

0.75 0.75 0.75 0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60 0.60 0.60 0.60

7.4 8.4 13.8 18.9 24.6 28.9 36.9

0.90 0.90 1.25 1.60 1.60 2.00 2.00

11.80 13.00 19.30 25.50 31.60 36.10 45.30

310 370 830 1400 2095 2680 4220

100 110 160 210 260 360 440

A7BT2-P001L A7BT2-P002L A7BT2-P005L A7BT2-P010L A7BT2-P020L A7BT2-P030L A7BT2-P050L

1P 2P(Q) 5P 10P 20P 30P 50P

1.5 1.5 1.5 1.5 1.5 1.5 1.5

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60 0.60

8.30 9.70 16.40 21.60 28.50 34.30 43.60

0.9 0.9 1.25 1.60 1.60 2.0 2.5

12.90 14.30 22.10 28.40 35.70 42.50 53.40

370 470 1060 1180 2650 3450 5500

110 120 180 230 290 410 510

15 16 17 18 19 20

(Q) = Quad N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02. Eg. A7W2-P001L-02 For further technical information refer to page 4:22.
Products. Technology. Services. Delivered Globally.

www.anixter.com

0415

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: Pairs will be numbered, each pair containing 1 black and 1 blue core 100mm maximum pair lay length (minimum 10 twists per metre) Individual Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Screen Isolation Tape: numbered p.e.t.p. tape applied over each individually screened pair Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down LSF inner sheath to BS6724 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black or Blue LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multipair PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 2 LSF


Individual and Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Suitable for direct buried applications.

Products. Technology. Services. Delivered Globally.

0416

www.anixter.com

1 Control and Instrumentation Cables

Multipair PE Insulated LSF Instrumentation Cable

2 3 4 5

BS5308 Part 1 Type 2 LSF


Individual and Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7Z2-P002L A7Z2-P005L A7Z2-P010L A7Z2-P020L A7Z2-P030L A7Z2-P050L 2P 5P 10P 20P 30P 50P 0.5 0.5 0.5 0.5 0.5 0.5 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 16/0.20 Insulation Thickness Nominal Diameter Under Armour mm 10.70 13.60 19.00 24.60 29.20 37.10 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 480 790 1350 1950 2720 4700 Min Bending Radius (fixed bend) mm 140 170 230 280 330 420

mm 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 1.25 1.60 1.60 2.00 2.50

mm 15.30 19.10 25.60 31.60 36.40 45.50

6 7 8 9

A7DG2-P002L A7DG2-P005L A7DG2-P010L A7DG2-P020L A7DG2-P030L A7DG2-P050L

2P 5P 10P 20P 30P 50P

0.75 0.75 0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60 0.60 0.60

11.40 14.50 20.40 26.80 31.50 40.30

0.90 1.25 1.60 2.00 2.00 2.50

16.00 20.00 27.00 33.80 39.70 49.90

530 830 1500 2470 3130 4920

150 180 240 310 360 440

10 11 12 13

A7CS2-P002L A7CS2-P005L A7CS2-P010L A7CS2-P020L A7CS2-P030L A7CS2-P050L

2P 5P 10P 20P 30P 50P

1.5 1.5 1.5 1.5 1.5 1.5

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60

13.10 16.80 23.90 31.10 36.80 47.20

1.25 1.60 1.60 2.00 2.50 2.50

18.60 22.50 30.70 39.30 45.20 57.20

760 1190 1910 3140 4590 6190

170 210 270 350 410 510

14 15 16 17 18 19 20

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02. Eg. A7Z2-P002L-02 For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0417

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Core Identification: Up to forty cores - cores will be numbered in black ink on yellow cores Up to eighty cores - First forty cores will be numbered 1-40 in black ink on yellow cores. Remaining will be numbered 1-40 in yellow ink on black cores Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Outer Sheath: Black LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multicore PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 1


Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Not suitable for direct buried applications (see cable type 2).

Products. Technology. Services. Delivered Globally.

0418

www.anixter.com

1 Control and Instrumentation Cables

Multicore PE Insulated LSF Instrumentation Cable

2 3 4 5 6 7 8 9 10

BS5308 Part 1 Type 1


Collective Screen, Unarmoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number of Cores Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7BQ10002L-02 0003L-02 0004L-02 0006L-02 0010L-02 0020L-02 0040L-02 0080L-02 A7BS10002L-02 0003L-02 0004L-02 0006L-02 0010L-02 0020L-02 0040L-02 0080L-02 2C 3C 4C 6C 10C 20C 40C 80C 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 8.30 8.70 9.70 11.30 14.30 18.40 24.40 33.60 100 130 150 190 310 530 965 1825 70 80 80 100 120 150 200 270 2C 3C 4C 6C 10C 20C 40C 80C 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 7.00 7.30 7.90 9.10 11.40 14.50 19.20 26.10 60 65 80 115 180 320 580 950 60 60 70 80 100 120 170 220 #/mm mm Nominal O/D mm Approx. Cable Weight kg/km Min Bending Radius (fixed bend) mm

11 12 13 14 15 16 17 18 19 20

For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0419

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Specifications
Generally in accordance with BS 5308 Part 1 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Core Identification: Up to forty cores - cores will be numbered in black ink on yellow cores Up to eighty cores - First forty cores will be numbered 1-40 in black ink on yellow cores. Remaining will be numbered 1-40 in yellow ink on black cores Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down LSF inner sheath to BS6724 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black LSF outer sheath to BS6724 Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Multicore PE Insulated LSF Instrumentation Cable

BS5308 Part 1 Type 2


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Especially for use in areas where fire would create dense smoke and toxic fumes causing a major threat to life and equipment. Suitable for direct buried applications.

Products. Technology. Services. Delivered Globally.

0420

www.anixter.com

1 Control and Instrumentation Cables

Multicore PE Insulated LSF Instrumentation Cable

2 3 4 5

BS5308 Part 1 Type 2


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number Nominal Nominal of Cond. Cond. Cores Area Stranding mm2 A7BQ20002L-02 0003L-02 0004L-02 0006L-02 0010L-02 0020L-02 0040L-02 0080L-02 A7BS20002L-02 0003L-02 0004L-02 0006L-02 0010L-02 0020L-02 0040L-02 0080L-02 2C 3C 4C 6C 10C 20C 40C 80C 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 8.30 8.90 9.70 11.70 14.70 18.70 24.60 33.60 0.90 0.90 0.90 0.90 1.25 1.60 1.60 2.00 12.9 13.30 14.30 16.80 19.80 25.00 31.20 41.80 370 385 470 520 710 1210 2040 3120 100 110 120 140 170 210 260 340 2C 3C 4C 6C 10C 20C 40C 80C 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 7.00 7.30 7.90 9.10 11.40 14.50 19.20 26.10 0.90 0.90 0.90 0.90 0.90 1.25 1.60 1.60 11.40 11.70 12.30 13.70 16.90 20.00 25.80 33.90 265 295 325 380 525 880 1450 2070 100 100 100 120 140 170 220 270 #/mm Insulation Thickness Nominal Diameter Under Armour mm Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km Min Bending Radius (fixed bend) mm

mm

mm

mm

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

For further technical information refer to page 4:22.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0421

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Technical Information for BS5308 Part 1


IDENTIFICATION OF PAIRS Two-pair un-screened and collectively screened cables shall be laid up in quad formation and colour coded in clockwise order of rotation: black, blue, green, brown. All other un-screened or collectively screened cables up to 50 pair shall be colour coded as given in colour code chart 1 below:

COLOUR CODE CHART 1


Pair Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 a-Wire Black Black Blue Black Blue Green Black Blue Green Brown Black Blue Green Brown White Black Blue Green Brown White Red Black Blue Green Brown b-Wire Blue Green Green Brown Brown Brown White White White White Red Red Red Red Red Orange Orange Orange Orange Orange Orange Yellow Yellow Yellow Yellow Pair Number 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 a-Wire White Red Orange Black Blue Green Brown White Red Orange Yellow Black Blue Green Brown White Red Orange Yellow Grey Black Blue Green Brown White b-Wire Yellow Yellow Yellow Grey Grey Grey Grey Grey Grey Grey Grey Violet Violet Violet Violet Violet Violet Violet Violet Violet Turquoise Turquoise Turquoise Turquoise Turquoise

Single triple cables will be identified black, blue, green. N.B. The cables are suitable for operation at voltage up to and including 300 Vrms core-earth and 500 Vrms core-core, but are not intended for direct connection to a low impedance source, e.g. public mains electricity supply.

Products. Technology. Services. Delivered Globally.

0422

www.anixter.com

1 Control and Instrumentation Cables

Technical Information for BS5308 Part 1


ELECTRICAL CHARACTERISTICS

2 3

MAXIMUM MUTUAL CAPACITANCE VALUES


Conductor Size 0.5mm2 pF/m Cables without Screens Cables with Collective Screen only except 1 pair, 2 pair and 1 triple) One Pair, One Triple and Two Pair Collectively Screened and all cables with individually Screened Pairs 75 75 115 0.75mm2 pF/m 75 75 115 1.0mm2 pF/m 75 75 115 1.5mm2 pF/m 85 85 120 2.5mm2 pF/m 85 85

4 5 6
120

7 8
Resistance @ 20C Maximum /km 36.8 39.7 26.5 18.4 12.3 7.56

MAXIMUM D.C. CONDUCTOR RESISTANCE @ 20C


Conductor Size mm2 0.5 0.5 0.75 1.0 1.5 2.5 Conductor Stranding #/mm 1/0.8 16/0.2 24/0.2 1/1.13 7/0.53 7/0.67

9
pF/m = pico Farads per metre
/km = ohms per km H/ = micro Henrys per ohm

10 11 12 13

MAXIMUM L/R RATIO


Conductor Size mm2 0.5 0.75 1.0 1.5 2.5 25H/ 25H/ 25H/ 40H/ 65H/ Conductor L/R Ratio (for adjacent cores)

14 15 16 17 18 19 20

INFORMATION ON HANDLING AND USAGE AT LOW TEMPERATURES Attention is drawn to the fact that as the temperature decreases PVC compounds become increasingly stiff and brittle, with the result that if the cable is bent quickly into a small radius, or is struck sharply at temperatures in the region of 0C or lower, there is a risk of shattering the PVC components. To avoid the risk of damage during handling, therefore, it is desirable that the cables specified in this standard should be installed only when both the cable and the ambient temperatures are above 0C and have been so for the previous 24 hrs, or where special precautions have been taken to maintain the cable above this temperature. However, after installation, they will operate satisfactorily at temperatures between -40C and +65C providing that at temperatures below 0C they are not subject to movement or impact. The manufacturer should be consulted for precise instructions if the cable is to be stored and/or used outside these temperature limits.
Products. Technology. Services. Delivered Globally.

www.anixter.com

0423

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications

Multipair PVC Insulated Instrumentation Cable

BS5308 Part 2 Type 1


Collective Screen, Unarmoured 300/500 V

Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc). Not suitable for direct buried applications (see cable type 2).

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 2 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: PVC insulation Type TI.1 to BS EN 50363-3 Pair Identification: See colour code chart 2 on page 4:32 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

Outer Sheath: PVC outer sheath Type TM.1 or 6 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0424

www.anixter.com

1 Control and Instrumentation Cables

Multipair PVC Insulated Instrumentation Cable

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

BS5308 Part 2 Type 1


Collective Screen, Unarmoured 300/500 V
Anixter Number Number of Pairs/Triple Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 A7-S31-0001LF A7-S31-0002LF A7-S31-0005LF A7-S31-0010LF A7-S31-0020LF A7-S31-0001TLF 1P 2P(Quad) 5P 10P 20P 1T 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 mm 0.60 0.60 0.60 0.60 0.60 0.60 Nominal O/D mm 7.00 7.90 12.90 17.40 22.50 7.30 Approx. Cable Weight kg/km 60 80 200 340 570 72 Min Bending Radius (fixed bend) mm 60 70 110 140 180 60

A7-S41-0001LF A7-S41-0002LF A7-S41-0005LF A7-S41-0010LF A7-S41-0020LF A7-S41-0001TLF

1P 2P(Quad) 5P 10P 20P 1T

0.75 0.75 0.75 0.75 0.75 0.75

24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2

0.60 0.60 0.60 0.60 0.60 0.60

7.40 8.40 13.80 18.90 24.60 7.80

75 100 250 450 800 90

60 70 120 150 200 70

A7-S21-0001LF A7-S21-0002LF A7-S21-0005LF A7-S21-0010LF A7-S21-0020LF A7-S21-0001TLF

1P 2P(Quad) 5P 10P 20P 1T

1.50 1.50 1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60

8.30 9.70 16.10 22.10 28.70 8.70

100 150 360 670 1230 135

70 80 140 180 230 80

N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 2 and details are available upon request. Cables having individual pair screens as well as collective screens are also available, Details upon request. For further technical information refer to page 4:32.

17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0425

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc). Suitable for direct buried applications.

Multipair PVC Insulated Instrumentation Cable

BS5308 Part 2 Type 2


Collective Screen, Armoured 300/500 V

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 2 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: PVC insulation Type TI.1 to BS EN 50363-3 Pair Identification: See colour code chart 2 page 4:32 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down PVC bedding Type TM.1 to BS EN 50363-4-1

Mild galvanised steel wires to BS EN10257-1 Outer Sheath: PVC outer sheath Type TM.1 to BS EN 50363-4-1 In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0426

www.anixter.com

1 Control and Instrumentation Cables

Multipair PVC Insulated Instrumentation Cable

2 3 4 5

BS5308 Part 2 Type 2


Collective Screen, Armoured 300/500 V
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7-S32-0001LF A7-S32-0002LF A7-S32-0005LF A7-S32-0010LF A7-S32-0020LF A7-S32-0001TLF 1P 2P(Q) 5P 10P 20P 1TR 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 Insulation Thickness Nominal Diameter Under Armour mm 7.00 7.90 12.90 17.40 22.50 7.30 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 255 305 610 1060 1800 280 Min Bending Radius (fixed bend) mm 100 100 150 190 240 100

mm 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 0.90 0.90 1.25 1.60 0.90

mm 11.40 12.30 17.70 23.10 29.30 11.70

6 7 8 9

A7-S42-0001LF A7-S42-0002LF A7-S42-0005LF A7-S42-0010LF A7-S42-0020LF A7-S42-0001TLF

1P 2P(Q) 5P 10P 20P 1TR

0.75 0.75 0.75 0.75 0.75 0.75

24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2

0.60 0.60 0.60 0.60 0.60 0.60

7.40 8.40 13.80 18.90 24.60 7.80

0.90 0.90 1.25 1.60 1.60 0.90

11.80 13.00 19.30 25.50 31.60 12.20

305 360 820 1380 2080 330

100 110 160 210 260 100

10 11 12 13

A7-S22-0001LF A7-S22-0002LF A7-S22-0005LF A7-S22-0010LF A7-S22-0020LF A7-S22-0001TLF

1P 2P(Q) 5P 10P 20P 1TR

1.50 1.50 1.50 1.50 1.50 1.50

7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60 0.60 0.60

8.30 9.70 16.10 22.10 28.70 8.70

0.90 0.90 1.25 1.60 1.60 0.90

12.90 14.30 21.80 28.90 35.90 13.30

360 460 1040 1610 2630 380

110 120 180 230 290 110

14 15 16 17 18 19 20

(Q) = Quad N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04. 15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 2 and details are available upon request. For further technical information refer to page 4:32.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0427

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Suitable for direct buried applications.

Multipair PVC Insulated Instrumentation Cable

BS5308 Part 2 Type 2


Individual and Collective Screen, Armoured 300/500 V

10 11 12 13 14 15 16 17 18 19 20

In accordance with BS 5308 Part 2 Conductors: Stranded (Class 2) or flexible (Class 5) copper conductors to BS EN 60228 Insulation: PVC insulation Type TI.1 to BS EN 50363-3 Pair Identification: Pairs will be numbered, each pair containing 1 white and 1 blue core 100mm maximum pair lay length (minimum 10 twists per metre) Individual Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Screen Isolation Tape: numbered p.e.t.p. tape applied over each individually screened pair Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

PVC bedding Type TM.1 to BS EN 50363-4-1 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black or Blue PVC outer sheath Type TM.1 to BS EN 50363-4-1. In addition, outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 300/500 V Temperature Rating: 65C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0428

www.anixter.com

1 Control and Instrumentation Cables

Multipair PVC Insulated Instrumentation Cable

2 3 4 5

BS5308 Part 2 Type 2


Individual and Collective Screen, Armoured 300/500 V
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7DB2-P002LF-02 A7DB2-P005LF-02 A7DB2-P010LF-02 A7DB2-P020LF-02 2P 5P 10P 20P 0.5 0.5 0.5 0.5 #/mm 16/0.20 16/0.20 16/0.20 16/0.20 Insulation Thickness Nominal Diameter Under Armour mm 10.70 13.60 19.00 24.60 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 505 830 1420 2040 Min Bending Radius (fixed bend) mm 140 170 230 280

mm 0.60 0.60 0.60 0.60

mm 0.90 1.25 1.60 1.60

mm 15.30 19.10 25.60 31.60

6 7 8

A7DD2-P002LF-02 A7DD2-P005LF-02 A7DD2-P010LF-02 A7DD2-P020LF-02

2P 5P 10P 20P

0.75 0.75 0.75 0.75

24/0.20 24/0.20 24/0.20 24/0.20

0.60 0.60 0.60 0.60

11.40 14.50 20.40 26.80

0.90 1.25 1.60 1.60

16.00 20.00 27.00 33.80

545 1005 1760 2640

150 180 240 310

9 10 11 12 13 14 15 16 17 18 19 20

A7DA2-P002LF-02 A7DA2-P005LF-02 A7DA2-P010LF-02 A7DA2-P020LF-02

2P 5P 10P 20P

1.5 1.5 1.5 1.5

7/0.53 7/0.53 7/0.53 7/0.53

0.60 0.60 0.60 0.60

13.10 16.80 23.90 31.10

1.25 1.25 1.60 2.00

18.60 22.50 30.70 39.30

800 1290 1990 3310

170 210 270 350

N.B. The above part numbers apply to cables with black outer sheaths. For blue outer remove -02. E.g. A7DB2-P002LF-02 For further technical information refer to page 4:32.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0429

1 Control and Instrumentation Cables 2 3 4 5 6


Specifications

Multipair/Triple XLPE Insulated LSF Instrumentation Cable Fire Resistant

BS5308 Part 1 Type 2 LSF and Fire Resistant


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry, etc). For use when fire resistance and circuit integrity is essential and where life may be endangered by smoke and noxious fumes, and where sensitive equipment may be damaged by acid forming gases.

7 8 9 10 11 12 13 14 15 16 17 18 19 20

Generally in accordance with BS 5308, but with the addition of fire properties relevant to IEC60331. Also meets relevant Cooper Energy Services specifications Conductors: Stranded (Class 2) copper conductors to BS EN 60228 Insulation: Mica Glass Tape, XLPE Type GP8 to BS7655 Pairs/Triples Identification: See colour code chart 2 on page 4:32. These cables are colour coded in accordance with BS5308 Part 2 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape 50% overlap Collective Screen: tinned copper drain wire(s) under and in contact with aluminium/p.e.t.p. tape applied metallic side down

Black LSF inner sheath Type LTS1 to BS7655 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black or blue LSF outer sheath Type LTS1 to BS7655 Flame retardant to BS EN 60332-3-22 & IEC60332-3-22 Category A (NMV7) Fire resistant to IEC60331 (750C for 3 hours) Voltage Rating: 300/500 V Temperature Rating: 90C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0430

www.anixter.com

1 Control and Instrumentation Cables

Multipair/Triple XLPE Insulated LSF Instrumentation Cable - Fire Resistant

2 3 4 5 6 7 8 9 10 11

BS5308 Part 1 Type 2 LSF and Fire Resistant


Collective Screen, Armoured 300/500 V Low Smoke Zero Halogen
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A12AG1-0001L-02 A12AG1-0001L-06 A12AG1-0002L-02 A12AG1-0002L-06 A12AG1-0005L-02 A12AG1-0005L-06 A12AG1-0010L-02 A12AG1-0010L-06 A12AG1-0001TL-02 A12AG1-0001TL-06 1P 1P 2P(Q) 2P(Q) 5P 5P 10P 10P 1T 1T 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 #/mm 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 Insulation Thickness Nominal Diameter Under Armour mm 8.70 8.70 10.10 10.10 17.70 17.70 24.00 24.00 9.20 9.20 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 334 334 418 418 1127 1127 1694 1694 373 373 Minimum Bending Radius (fixed bend) mm 160 160 177 177 291 291 372 372 166 166

mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 0.90 0.90 0.90 1.60 1.60 1.60 1.60 0.90 0.90

mm 13.30 13.30 14.70 14.70 20.90 20.90 31.00 31.00 13.80 13.80

A12AG2-0001L-02 A12AG2-0001L-06 A12AG2-0002L-02 A12AG2-0002L-06 A12AG2-0005L-02 A12AG2-0005L-06

1 1 2(Q) 2(Q) 5 5

2.5 2.5 2.5 2.5 2.5 2.5

7/0.67 7/0.67 7/0.67 7/0.67 7/0.67 7/0.67

0.70 0.70 0.70 0.70 0.70 0.70

10.00 10.00 11.80 11.80 20.90 20.90

0.90 0.90 0.90 0.90 1.60 1.60

14.60 14.60 16.60 16.60 27.70 27.70

398 398 533 533 1427 1427

175 175 199 199 333 333

12 13 14 15 16 17 18 19 20

(Q) = Quad N.B: -02 denotes Black outer sheath colour -06 denotes Blue outer sheath colour Also available in individually and collectively screened versions. Details upon request. For further technical information for BS5308 Part 1 electrical characteristics refer to page 4:22. For BS5308 Part 2 colour coding refer to page 4:32.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0431

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Technical Information for BS5308 Part 2


IDENTIFICATION OF PAIRS Two-pair un-screened and collectively screened cables shall be laid up in quad formation and colour coded in clockwise order of rotation: blue, green, orange, brown. All other un-screened or collectively screened cables up to 50 pair shall be colour coded as given in colour code chart 2 below:

COLOUR CODE CHART 2


Pair Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 a-Wire White White White White White Red Red Red Red Red Black Black Black Black Black Yellow Yellow Yellow Yellow Yellow WHITE-Blue WHITE-Blue WHITE-Blue WHITE-Blue WHITE-Blue b-Wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Pair Number 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 a-Wire RED-Blue RED-Blue RED-Blue RED-Blue RED-Blue BLUE-Black BLUE-Black BLUE-Black BLUE-Black BLUE-Black YELLOW-Blue YELLOW-Blue YELLOW-Blue YELLOW-Blue YELLOW-Blue WHITE-Orange WHITE-Orange WHITE-Orange WHITE-Orange WHITE-Orange ORANGE-Red ORANGE-Red ORANGE-Red ORANGE-Red ORANGE-Red b-Wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey

Single triple cables will be identified white, blue, orange.

Products. Technology. Services. Delivered Globally.

0432

www.anixter.com

1 Control and Instrumentation Cables

Technical Information for BS5308 Part 2


ELECTRICAL CHARACTERISTICS Maximum mutual capacitance values: Maximum mutual capacitance of the pairs or adjacent cores - 250pF/m Maximum capacitance between any core and screen - 450pF/m

2 3 4 5

MAXIMUM D.C. CONDUCTOR RESISTANCE @ 20C


Conductor Size mm
2

Conductor Stranding #/mm

Resistance @ 20C Maximum /km Multicore Multipair 39.7 26.5 12.3

6 7 8 9

0.5 0.75 1.5

16/0.2 24/0.2 7/0.53

39.0 26.0 12.1

MAXIMUM L/R RATIO


Conductor Size mm2 0.5 0.75 1.5 25H/ 25H/ 40H/ Conductor L/R Ratio (for adjacent cores)

10
pF/m = pico Farads per metre
/km = ohms per km H/ = micro Henrys per ohm

11 12 13

INFORMATION ON HANDLING AND USAGE AT LOW TEMPERATURES Attention is drawn to the fact that as the temperature decreases PVC compounds become increasingly stiff and brittle, with the result that if the cable is bent quickly into a small radius, or is struck sharply at temperatures in the region of 0C or lower, there is a risk of shattering the PVC components. To avoid the risk of damage during handling, therefore, it is desirable that the cables specified in this standard should be installed only when both the cable and the ambient temperatures are above 0C and have been so for the previous 24 hrs, or where special precautions have been taken to maintain the cable above this temperature. However, after installation, they will operate satisfactorily at temperatures between -40C and +65C providing that at temperatures below 0C they are not subject to movement or impact. The manufacturer should be consulted for precise instructions if the cable is to be stored and/or used outside these temperature limits.

14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0433

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are designed to connect electrical instrument circuits and provide communication services in and around processing plants (specifically steel industry). Suitable for direct buried applications.

Multipair PVC Insulated Instrumentation Cable

CES20 Part 4 Type 143

10 11 12 13 14 15 16 17 18 19 20

In accordance with British Steel specification CES20 Part 4 Type 143 Conductors: Flexible Class 5 tinned copper conductors to BS EN 60228 Insulation: PVC insulation Type 2 to BS7655 Pair Identification: See colour code chart 5 on page 4:40 100mm maximum pair lay length (minimum 10 twists per metre) Binder Tape: p.e.t.p. tape suitable overlap PVC tape Collective Screen: Solid 1/0.8mm tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down

p.e.t.p. tape suitable overlap PVC bedding to BS7655 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Orange PVC sheath Type TM.1 to BS EN 50363-4-1 Flame retardant to BS EN 60332-1-2 Voltage Rating: 300/500 V Temperature Rating: 70C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0434

www.anixter.com

1 Control and Instrumentation Cables

Multipair PVC Insulated Instrumentation Cable

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CES20 Part 4 Type 143


Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 A7CT-2402 A7CT-2405 A7CT-2410 A7CT-2420 A7CT-2430 A7CT-2450 2(Q) 5 10 20 30 50 0.75 0.75 0.75 0.75 0.75 0.75 #/mm 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 Insulation Thickness Nominal Diameter Under Armour mm 10.40 13.20 17.70 22.90 28.50 36.10 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 485 720 1230 1805 2575 4250 Min Bending Radius (fixed bend) mm 130 160 200 260 300 380

mm 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 1.25 1.60 1.60 2.00 2.50

mm 15.20 18.90 24.60 31.30 37.00 47.00

(Q) = Quad For further technical information refer to page 4:36.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0435

1 Control and Instrumentation Cables 2 3 4


COLOUR CODE CHART 5

Technical Information for CES20 Part 4 Type 143


IDENTIFICATION OF PAIRS Two pair cables shall be laid up in quad formation in clockwise order of rotation: blue, orange, green, brown. All other cables up to 50 pair shall be colour coded as given in colour code chart 5 below:

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Pair Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

a-Wire Black Black Black Black Black Blue Blue Blue Blue Blue Orange Orange Orange Orange Green Green Green Brown Brown Grey Black Black Black Black White

b-Wire Blue Orange Green Brown Grey White Orange Green Brown Grey White Green Brown Grey White Brown Grey White Grey White White Red Yellow Violet Red

Pair Number 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

a-Wire White White Blue Blue Blue Green Green Green Red Red Red Red Red Grey Grey Orange Orange Yellow Yellow Brown Turquoise Turquoise Turquoise Turquoise Turquoise

b-Wire Yellow Violet Red Yellow Violet Red Yellow Violet Grey Orange Yellow Brown Violet Yellow Violet Yellow Violet Brown Violet Violet Black Blue Red Orange Yellow

Products. Technology. Services. Delivered Globally.

0436

www.anixter.com

1 Control and Instrumentation Cables

Technical Information for CES20 Part 4 Type 143


N.B: The cables are suitable for operation at voltages up to and including 300 Vrms core-earth and 500 Vrms core-core, but are not intended for direct connection to low impedance source e.g. public mains electricity supply. ELECTRICAL CHARACTERISTICS Maximum d.c. conductor resistance @ 20C - 27.2/km Maximum mutual capacitance of the pairs or adjacent cores - 250pF/m Maximum capacitance between any core and screen - 450pF/m Maximum L/R ratio - 25H/ pF/m = pico Farads per metre /km = ohms per km H/ = micro Henrys per ohm

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0437

1 Control and Instrumentation Cables 2 3 4 5 6


Application

ESI* 09-6 Issue 5


Multipair PVC Insulated and Sheathed Armoured

7 8 9 10 11 12 13 14 15 16 17 18 19 20

These light current control cables are intended primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150 V d.c. or 110 V a.c. Suitable for direct buried applications. May be provided with optional collective screen.

Specifications
In accordance with ESI 09-6 Issue 5 Conductors: Solid (Class 1) tinned copper conductors to BS EN 60228 Insulation: PVC insulation Type 2 to BS7655 Pair Identification: See colour code chart 3 on page 4:40 Binder Tape: p.e.t.p. tape of suitable overlap OPTIONAL Collective Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Inner Sheath: PVC inner sheath Type TM.1 or 6 to BS EN 50363-4-1 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black PVC outer sheath Type TM.1 or 6 to BS EN 50363-4-1. In addition, the PVC outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 150 V d.c./110 V a.c Temperature Rating: 70C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0438

www.anixter.com

1 Control and Instrumentation Cables

ESI* 09-6 Issue 5


Multipair PVC Insulated and Sheathed Armoured
Anixter Number Number Nominal Nominal of Cond. Cond. Pairs/ Area Stranding Triple mm2 UN-SCREENED CABLES A11EE-P002F A11EE-P005F A11EE-P010F A11EE-P020F A11EE-P030F A11EE-P050F A11EE-P100F SCREENED CABLES A11FF-P002F A11FF-P005F A11FF-P010F A11FF-P020F A11FF-P030F A11FF-P050F A11FF-P100F 2P(Q) 5P 10P 20P 30P 50P 100P 0.64 0.64 0.64 0.64 0.64 0.64 0.64 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 0.30 0.30 0.30 0.30 0.30 0.30 0.30 6.20 9.90 13.50 17.30 20.40 25.90 36.00 0.90 0.90 1.25 1.25 1.60 1.60 2.00 10.60 14.60 19.10 23.20 27.20 33.10 44.60 220.00 380.00 630.00 955.00 1415.00 2000.00 3750.00 90.00 120.00 160.00 190.00 220.00 270.00 360.00 2P(Q) 5P 10P 20P 30P 50P 100P 0.64 0.64 0.64 0.64 0.64 0.64 0.64 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 1/0.9 0.30 0.30 0.30 0.30 0.30 0.30 0.30 5.70 9.40 13.00 16.80 19.90 25.40 35.50 0.90 0.90 1.25 1.25 1.60 1.60 2.00 10.10 14.10 18.60 22.70 26.70 32.60 44.10 200.00 370.00 610.00 930.00 1390.00 1940.00 3700.00 70.00 90.00 120.00 140.00 170.00 200.00 270.00 #/mm Insulation Thickness Nominal Diameter Under Armour mm Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km Minimum Bending Radius (fixed bend) mm

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

mm

mm

mm

(Q) = Quad 15, 25, 40 and 75 pair cables of the above type are also covered in ESI 09-6 Issue 5. Details are available upon request. For further technical information refer to page 4:40

* ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.

20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0439

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


COLOUR CODE CHART 3

Technical Information for ESI* 09-6 Issue 5


PAIR IDENTIFICATION Pairs will be identified as follows: 2 pair (quad) cables - Blue, Orange, Green, Brown (in order of rotation) 5 pair cables - Pairs 1 to 5 inclusive 10 pair cables - Pairs 1 to 10 inclusive 15 pair cables - Pairs 1 to 15 inclusive 20 pair cables - Pairs 1 to 20 inclusive 25 pair cables - Pairs 1 to 25 inclusive 30 pair cables - Pairs 1 to 30 inclusive 40 pair cables - Pairs 1 to 40 inclusive 50 pair cables - Pairs 1 to 50 inclusive *75 pair cables - Pairs 1 to 50 plus 1 to 25 inclusive *100 pair cables - Pairs 1 to 50 plus 1 to 50 inclusive *Alternative colour schemes are acceptable for the 75 and 100 pair.

10 11 12 13 14 15 16 17 18 19 20

Pair Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Wire Black/Blue Black/Orange Black/Green Black/Brown Black/Grey Blue/White Blue/Orange Blue/Green Blue/Brown Blue/Grey Orange/White Orange/Green Orange/Brown Orange/Grey Green/White Green/Brown Green/Grey

Pair Number 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

Wire Brown/White Brown/Grey Grey/White Black/White Black/Red Black/Yellow Black/Violet White/Red White/Yellow White/Violet Blue/Red Blue/Yellow Blue/Violet Green/Red Green/Yellow Green/Violet Red/Grey

Pair Number 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

Wire Red/Orange Red/Yellow Red/Brown Red/Violet Grey/Yellow Grey/Violet Orange/Yellow Orange/Violet Yellow/Brown Yellow/Violet Brown/Violet Turquoise/Black Turquoise/Blue Turquoise/Red Turquoise/Orange Turquoise/Yellow

Products. Technology. Services. Delivered Globally.

0440

www.anixter.com

1 Control and Instrumentation Cables

Technical Information for ESI* 09-6 Issue 5


ELECTRICAL CHARACTERISTICS Conductor Resistance Maximum d.c. conductor resistance @ 20C (LOOP) 59.34 ohms/km. Insulation Resistance Minimum insulation resistance 80 Mohms/km. * ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0441

1 Control and Instrumentation Cables 2 3 4 5 6


Application

ENATS* 09-6 Issue 7


Multipair PVC Insulated and Sheathed Armoured, Un-screened

7 8 9 10 11 12 13 14 15 16 17 18 19 20

These light current control cables are primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150 V d.c. or 110 V a.c.

Specification
In accordance with ENATS 09-6 Issue 7 Table E.3B Conductors: Solid (Class 1) plain copper conductors to BS EN 60228 Insulation: PVC insulation Type 2 to BS7655 Pair Identification: See colour code chart 4 on page 4:50 Binder Tape: p.e.t.p. tape of suitable overlap Inner Sheath: PVC inner sheath Type TM.1 or 6 to BS EN 50363-4-1 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black PVC outer sheath Type TM.1 or 6 to BS EN 50363-4-1. In addition, the PVC outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 150 V d.c./110 V a.c. Temperature Rating: 70C maximum conductor operating temperature

* ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.
Products. Technology. Services. Delivered Globally.

0442

www.anixter.com

1 Control and Instrumentation Cables

ENATS* 09-6 Issue 7


Multipair PVC Insulated and Sheathed Armoured, Un-screened
Anixter Number Number Nominal Nominal of Pairs Cond. Cond. Area Stranding mm2 A11BP-P002F A11BP-P005F A11BP-P010F A11BP-P020F A11BP-P040F A11BP-P060F A11BP-P100F A11BP-P200F 2P(Q) 5P 10P 20P 40P 60P 100P 200P 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 Insulation Thickness Nominal Diameter Under Armour mm 5.10 8.50 10.90 14.40 22.90 25.90 32.60 46.00 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 200 290 540 770 1430 1900 3010 5660 Minimum Bending Radius (fixed bend) mm 60 80 100 130 180 200 250 340

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

mm 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

mm 0.90 0.90 1.25 1.25 1.60 1.60 2.00 2.00

mm 9.50 13.10 16.40 20.10 29.70 33.10 41.00 56.00

(Q) = Quad For further technical information refer to page 4:50. Non-armoured versions also available. Details upon request.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0443

1 Control and Instrumentation Cables 2 3 4 5 6


Application

ENATS* 09-6 Issue 7


Multipair PVC Insulated and Sheathed Collective Screen, Armoured

7 8 9 10 11 12 13 14 15 16 17 18 19 20

These light current control cables are intended primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150 V d.c. or 110 V a.c. All armoured cables (generation) must be provided with a collective screen.

Specification
In accordance with ENATS 09-6 Issue 7 Table E.3C (These cables were formerly covered by GDCD200) Conductors: Solid (Class 1) plain copper conductors to BS EN 60228 Insulation: PVC insulation Type 2 to BS7655 Pair Identification: See colour code chart 4 on page 4:50 Binder Tape: p.e.t.p. tape of suitable overlap Collective Screen: 2 pair cables - tinned copper drain wire under and in contact with aluminium tape. 5 pair cables and above - tinned copper drain wire under and in contact with laminate backed aluminium tape (metallic side down), the backing ensuring adhesion to the PVC inner sheath Inner Sheath: PVC inner sheath Type TM.1 or 6 to BS EN 50363-4-1 Mild galvanised steel wires to BS EN10257-1 (Cables up to 10PR only) Outer Sheath: Grey PVC outer sheath Type TM.1 or 6 to BS EN 50363-4-1. In addition, the PVC outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 15% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 150 V d.c./110 V a.c. Temperature Rating: 70C maximum conductor operating temperature N.B. Cables of 20 pair and above have DSTA (Double Steel Tape Armour).

Products. Technology. Services. Delivered Globally.

0444

www.anixter.com

1 Control and Instrumentation Cables

ENATS* 09-6 Issue 7


Multipair PVC Insulated and Sheathed Collective Screen, Armoured
Anixter Number Number Nominal Nominal of Pairs Cond. Cond. Area Stranding mm2 A11CY-P002F-09 A11CY-P005F-09 A11CY-P010F-09 A11CY-P020F-09 A11CY-P040F-09 A11CY-P060F-09 A11CY-P100F-09 A11CY-P200F-09 2P(Q) 5P 10P 20P 40P 60P 100P 200P 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 Insulation Thickness Nominal Diameter Under Armour mm 6.50 9.50 11.70 15.00 24.10 27.90 34.00 47.60 Armour Wire Nominal Diameter/ O/D Tape Thickness mm 0.90 0.90 1.25 0.50* 0.50* 0.50* 0.50* 0.50* mm 12.10 15.30 18.60 21.80 31.70 36.10 42.20 57.20 Approx. Cable Weight kg/km 300.00 450.00 730.00 930.00 1570.00 2120.00 2850.00 4860.00 Minimum Bending Radius (fixed bend) mm 100.00 130.00 150.00 180.00 260.00 290.00 340.00 460.00

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

mm 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

(Q) = Quad * Refers to thickness of steel tape on DSTA cables. For SWA version of DSTA armoured cables please use suffix -SWA e.g. A11CY-P020F-SWA For further technical information refer to page 4:50.

* ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.
Products. Technology. Services. Delivered Globally.

20

www.anixter.com

0445

1 Control and Instrumentation Cables 2 3 4 5 6


Application

ENATS* 09-6 Issue 7


Multipair LSZH Insulated and Sheathed Armoured, Un-screened

7 8 9 10 11 12 13 14 15 16 17 18 19 20

These light current control cables are primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150 V d.c. or 110 V a.c.

Specification
Generally in accordance with ENATS 09-6 Issue 7 Table E.3B Conductors: Solid (Class 1) plain copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 4 on page 4:50 Binder Tape: p.e.t.p. tape of suitable overlap Inner Sheath: LSF inner sheath Type LTS1 or LTS3 to BS7655 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black LSF outer sheath Type LTS1 or LTS3 to BS7655. In addition, the LSF outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 0.5% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 150 V d.c./110 V a.c. Temperature Rating: 70C maximum conductor operating temperature

* ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.
Products. Technology. Services. Delivered Globally.

0446

www.anixter.com

1 Control and Instrumentation Cables

ENATS* 09-6 Issue 7


Multipair LSZH Insulated and Sheathed Armoured, Un-screened
Anixter Number Number Nominal Nominal of Pairs Cond. Cond. Area Stranding mm2 A11BP-P002LSF A11BP-P005LSF A11BP-P010LSF A11BP-P020LSF A11BP-P030LSF A11BP-P040LSF A11BP-P050LSF A11BP-P060LSF 2P(Q) 5P 10P 20P 30P 40P 50P 60P 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 Insulation Thickness Nominal Diameter Under Armour mm 5.10 8.50 10.90 14.40 18.60 22.90 23.80 25.90 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 197 279 526 740 880 1345 1700 1810 Minimum Bending Radius (fixed bend) mm 60 80 100 130 160 180 200 200

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

mm 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

mm 0.90 0.90 1.25 1.25 1.60 1.60 1.60 1.60

mm 9.50 13.10 16.40 20.10 25.20 29.70 31.80 33.10

(Q) = Quad For further technical information refer to page 4:50. Non-armoured versions also available. Details upon request.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0447

1 Control and Instrumentation Cables 2 3 4 5 6


Application

ENATS* 09-6 Issue 7


Multipair LSZH Insulated and Sheathed Collective Screen, Armoured

7 8 9 10 11 12 13 14 15 16 17 18 19 20

These light current control cables are intended primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150 V d.c. or 110 V a.c.

Specification
Generally in accordance with ENATS 09-6 Issue 7 Table E.3B but with the addition of a collective screen Conductors: Solid (Class 1) plain copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Pair Identification: See colour code chart 4 on page 4:50 Binder Tape: p.e.t.p. tape of suitable overlap Collective Screen: tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down Inner Sheath: LSF inner sheath Type LTS1 or LTS3 to BS7655 Mild galvanised steel wires to BS EN10257-1 Outer Sheath: Black LSF outer sheath Type LTS1 or LTS3 to BS7655. In addition, the LSF outer sheath displays following characteristics: Minimum oxygen index: 30% Maximum HCL Emission @ 800C: 0.5% Flame retardant to BS EN 60332-3-24 & IEC60332-3-24 Category C (NMV1.5) Voltage Rating: 150 V d.c./110 V a.c. Temperature Rating: 70C maximum conductor operating temperature

Products. Technology. Services. Delivered Globally.

0448

www.anixter.com

1 Control and Instrumentation Cables

ENATS* 09-6 Issue 7


Multipair LSZH Insulated and Sheathed Collective Screen, Armoured
Anixter Number Number Nominal Nominal of Pairs Cond. Cond. Area Stranding mm2 A11BQ-P002LSF A11BQ-P005LSF A11BQ-P010LSF A11BQ-P020LSF A11BQ-P030LSF A11BQ-P040LSF A11BQ-P050LSF A11BQ-P060LSF 2P(Q) 5P 10P 20P 30P 40P 50P 60P 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 #/mm 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 1/0.8 Insulation Thickness Nominal Diameter Under Armour mm 5.60 9.00 11.40 14.90 19.10 23.40 24.30 26.90 Armour Wire Nominal Diameter O/D Approx. Cable Weight kg/km 220 310 550 780 1115 1345 1780 2010 Minimum Bending Radius (fixed bend) mm 80 110 140 170 210 250 260 280

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

mm 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

mm 0.90 0.90 1.25 1.25 1.60 1.60 1.60 1.60

mm 10.00 13.60 16.90 20.60 25.70 30.20 32.30 34.10

(Q) = Quad For further technical information refer to page 4:50. Non-armoured versions also available. Details upon request.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0449

1 Control and Instrumentation Cables 2 3 4 5


1

Technical Information for ENATS* 09-6 Issue 7


PAIR IDENTIFICATION Pairs will be identified as given in colour code chart 4 below:
COLOUR CODE CHART 4
Pair Number Wire a White White White White White Red Red Red Red Red Black Black Black Black Black Yellow Yellow Yellow Yellow Yellow Colour Wire b Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

2 pair cables are laid up in quad formation in order of rotation: white, red, blue, orange. Cables having 40 pairs and above are laid up in 20 pair units, each individual 20 pair unit having pair identification as per colour code chart 4. Each unit shall be identified by a numbered tape applied directly on to the unit binder tapes or by a separate longitudinal tape applied under a clear unit binder tape. The numbers shall run from 1 upwards in units of 1.

Products. Technology. Services. Delivered Globally.

0450

www.anixter.com

1 Control and Instrumentation Cables

Technical Information for ENATS* 09-6 Issue 7


ELECTRICAL CHARACTERISTICS Conductor Resistance Maximum d.c. conductor resistance @ 20C (LOOP) 73.6 ohms/km. Insulation Resistance Minimum insulation resistance @ 20C 80 Mohms/km (PVC), 1500 Mohms/km (PE). Mutual Capacitance Maximum mutual capacitance 150nF/km (@ 1kHz) PVC insulation, 75nF/km (@ 1kHz) PE insulation. Capacitance Unbalance Maximum capacitance unbalance: 2 pair 800pF for 500m of cable @ 1kHz. above 2 pair 400pF for 500m of cable @ 1kHz. Mutual Inductance Maximum mutual inductance 915H for 500m of cable @1kHz.

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

* ESI standards are now covered under ENATS (Energy Network Association Technical Specification). Standard number remains same, i.e. ENATS 09-6.
Products. Technology. Services. Delivered Globally.

20

www.anixter.com

0451

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Notes 1: Cable temperature range may be restricted to figures lower than those shown in the table because of temperature limitations imposed by the insulant. 2: A cable comprising two copper conductors may be used with Type B thermocouples. The expected maximum additional deviation within the cable temperature range 0C to +100C is 40 mV. The equivalent in temperature is 3.5C when the measuring junction of the thermocouple is at 1400C.

Thermocouple Cables
The following information gives details on thermocouple wire tolerances and identification taken from BS4937 Part 30. BS4937: International thermocouple reference tables. Part 30: Extension and compensation cables. Tolerances and identification systems. Tolerance Values The table shows the specified tolerance for extension and compensating cables when used at temperatures within the ranges indicated as Cable temperature range. The table also includes, in parentheses, the approximate equivalent tolerances in degrees Celsius. Because thermocouple e.m.f. temperature relationships are non-linear the tolerance in degrees Celsius depends on the temperature of the measuring junction of the thermocouple. The figures shown in the table are those appropriate to the measuring junction temperatures in the final column. In most cases the error expressed in degrees Celsius will be larger at lower thermocouple junction temperatures.
Type JX TX EX KX NX KCA KCB NC RCA RCB SCA SCB Tolerance Class 1 85v ( 1.5C) 30v ( 1.5C) 120v ( 1.5C) 60v ( 1.5C) 60v ( 1.5C) Tolerance Class 2 140v ( 2.5C) 60v ( 1.0C) 200v ( 2.5C) 100v ( 2.5C) 100v ( 2.5C) 100v ( 2.5C) 100v ( 2.5C) 30v ( 2.5C) 60v ( 5.0C) 30v ( 2.5C) 60v ( 5.0C) Cable Temperature Range -25C to +200C -25C to +200C -25C to +200C -25C to +200C -25C to +200C 0C to +150C 0C to +100C 0C to +150C 0C to +100C 0C to +200C 0C to +100C 0C to +200C Measuring Junction Temperature 500C 300C 500C 900C 900C 900C 900C 900C 1000C 1000C 1000C 1000C

Products. Technology. Services. Delivered Globally.

0452

www.anixter.com

1 Control and Instrumentation Cables

Thermocouple Cables
Identification System for Extension and Compensating Cables Outer Sheath: The outer sheath shall be coloured as given in the table except for intrinsically safe circuits where the outer sheath colour shall be BLUE for all thermocouple types. Negative Conductor: The insulation of the negative conductor shall be WHITE for all thermocouple types. Positive Conductor: The insulation of the positive conductor shall be as given in the following table:
Thermocouple Type T E J K R S B N Colour of Positive Conductor and Sheath Insulation Brown Violet Black Green Orange Orange Grey Pink

2 3 4 5 6 7 8 9 10

Anixter stock a small selection of armoured thermocouple cables in the following sizes and pair counts, with BS4937 Part 30 colour coding:
Anixter Number Number Thermocouple Sheath of Pairs Type Colour Screen Type Diameter Nominal O/D Approx. Under Amour Weight mm A12AG9-0001L-06 A12AG9-0002L-06 A12AG9-0005L-06 A12AG9-0010L-06 1 2 5 10 KC* KC* KC* KC* Blue Blue Blue Blue C IC IC IC 6.60 11.40 15.00 21.10 mm 10.40 15.60 19.40 25.70 kg/km 167 336 576 891 Minimum Bending Radius (fixed bend) mm 90 130 160 210

11 12 13 14 15 16 17

*Formerly known as type Vx (compensating for type K thermocouples) C = Collective Screen IC = Individual and Collective Screen Cable Construction: Copper(+) copper-Nickel(-) conductors, XLPE insulation, screened, XLEVA, GSWB, XLEVA.

18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0453

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
Used in vehicle monitoring equipment for detection of traffic movements via creation of inductive loop to frequency signal flowing in cable and metallic parts of vehicle. These cables are designed for installation in a slot cut into the carriageway.

Traffic Signal Cables

Single-Core Loop Detector Cables


EPR or EPR/PCP 85C 450/750 V

10 11 12 13 14 15 16 17 18 19 20

Generally in accordance with DoT specification TR2029 Conductors: Flexible (Class 5) tinned copper conductors to BS EN 60228 Insulation: Black EPR insulation Type GP1 to BS7655 Sheath (sheathed versions only): Black heavy duty PCP Type RS2 to BS7655

Flame retardant to BS EN 60332-1-2 Temperature Rating: 85C maximum conductor operating temperature Voltage Rating: 450/750 V

Products. Technology. Services. Delivered Globally.

0454

www.anixter.com

1 Control and Instrumentation Cables

Traffic Signal Cables

2 3 4 5 6

Single-Core Loop Detector Cables


EPR or EPR/PCP 85C 450/750 V
Anixter Number Number Nominal Nominal of Cond Cond Cores Area Stranding mm2 EPR insulated only A4-C30-0115-EPR-02 1 A4-C50-0125-EPR-02 1 EPR insulated/PCP sheath TR2029-1.5MM 1 1.5 30/0.25 0.80 1.4 6.80 7.20 65 30 1.5 2.5 30/0.25 50/0.25 1.10 2.10 3.80 6.05 4.00 6.35 30 48 15 20 #/mm Insulation Thickness Sheath Thickness* Minimum O/D Nominal O/D Approx. Cable Weight kg/km Minimum Bending Radius (fixed bend) mm

mm

mm

mm

mm

7 8 9

*Applicable to sheathed versions only. Technical Information: Maximum d.c. conductor resistance at 20C 1.5mm2 ohms/km 13.7 2.5mm2 ohms/km 8.21

10 11 12 13 14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0455

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
To be used as feeder cable for inductive loop detectors. Suitable for installation in ducted network. For direct buried applications, see armoured feeder cables.

Traffic Signal Cables

Single and Multipair Unarmoured Feeder Cables


PE Insulated, PE Sheathed, 70C, 600/1000 V

10 11 12 13 14

Generally in accordance with DOT specification TR2031 Conductors: Solid Class 1 copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Core Identification: 1 pair red, black 2 pair laid up in quad formation in order of rotation: red, yellow, blue, black Outer Sheath: Orange polythene Type 03 to BS6234, embossed TRAFFIC SIGNAL
Anixter Number Number of Pairs

Temperature Rating: 70C maximum conductor operating temperature Voltage Rating: 600/1000 V N.B: Polythene sheathed cables are not considered flame retardant and are not recommended for indoor use.

Nominal Cond. Nominal Cond. Insulation Area Stranding Thickness mm2 #/mm 1/1.38 1/1.38 mm 0.60 0.60

Maximum O/D

Approx. Cable Weight kg/km 67 118

15
mm 7.90 9.00

Minimum Radius (fixed bend) mm 64 73

16 17

A7-E15-P001-08 1 A7-E15-P002-08 2(Quad)

1.5 1.5

A7-E25-P001-08 1

2.5 2.5

1/1.78 1/1.78

0.70 0.70

9.30 10.70

99 166

75 87

18 19 20

A7-E25-P002-08 2(Quad)

Products. Technology. Services. Delivered Globally.

0456

www.anixter.com

1 Control and Instrumentation Cables

Traffic Signal Cables

Technical Information
Electrical Characteristics
Units Maximum d.c. conductor resistance @ 20C Capacitance Loop inductance Current rating in air (30C) Ohms/km pF/m H/km A Cond. Size 1.5mm2 Cond. Size 2.5mm2 12.1 <75 630 (1P) 770 (2P) 24* 7.41 39 (1P) 52 (2P) 630 (1P) 770 (2P) 33*

2 3 4 5 6 7 8

*These ratings are based on only two cores loaded simultaneously. In two pair cables where all four cores could be loaded simultaneously, the above values should be multiplied by 0.78. For ambient temperatures other than 30C, the following rating factors should be applied: Ambient air temp C Rating factor 10 15 20 25 30 1.22 1.17 1.12 1.06 1.0 35 40 0.94 0.87 45 0.79

9 10 11 12 13 14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0457

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15


mm2 #/mm 1/1.38 1/1.38 1/1.78 1/1.78 mm 0.60 0.60 0.70 0.70

Traffic Signal Cables

Single and Multipair Armoured Feeder Cables


PE Insulated, PE Bedded, SWA, PE Sheathed, 70C, 600/1000 V

Application
To be used as feeder cable for inductive loop detectors. Suitable for direct buried installations.

Specifications
Generally in accordance with DoT specification TR2031 Conductors: Solid Class 1 copper conductors to BS EN 60228 Insulation: Polythene insulation Type 03 to BS6234 Core Identification: 1 pair red/black 2 pair laid up in quad formation in order of rotation: red, yellow, blue, black Inner Sheath: Natural polythene Type 03 to BS6234
Anixter Number Number Nominal Nominal of Pairs Cond. Cond. Area Stranding Insulation Thickness Nominal Diameter Under Armour mm 7.30 8.50 8.10 9.50 Armour Wire Size Nominal O/D Approx. Cable Weight kg/km 265 335 336 375 Minimum Bending Radius (fixed bend) mm 100 110 110 120

Mild galvanised steel wires to BS EN 10257-1 Outer Sheath: Orange polythene Type 03 to BS6234. Embossed TRAFFIC SIGNALS Voltage Rating: 600/1000 V N.B: Polythene sheathed cables are not considered flame retardant and are not recommended for indoor use.

mm 0.90 0.90 0.90 0.90

mm 11.90 13.10 12.70 14.10

16 17 18

A7-D15-P001-08 A7-D15-P002-08 A7-D25-P001-08 A7-D25-P002-08

1 2 (Q) 1 2 (Q)

1.5 1.5 2.5 2.5

(Q) = Quad

19 20

Products. Technology. Services. Delivered Globally.

0458

www.anixter.com

1 Control and Instrumentation Cables

Traffic Signal Cables

Technical Information
Electrical Characteristics
Units Maximum d.c. conductor resistance @ 20C Capacitance Loop inductance Current rating in ground (15C, 1.2C m/W) Ohms/km pF/m H/km A Cond. Size 1.5mm2 Cond. Size 2.5mm2 12.1 <75 630 (1P) 770 (2P) 32* 7.41 64 (1P) 53.5 (2P) 630 (1P) 770 (2P) 41*

2 3 4 5 6 7 8

*These ratings are based on only two cores being loaded simultaneously. In two pair cables where all four cores could be loaded simultaneously, the above values should be multiplied by 0.78. For ground temperatures other than 15C the following rating factors should be applied: Ground temp C Rating factor 10 15 1.04 1.0 20 25 30 35 40 0.95 0.90 0.85 0.80 0.74

9 10 11 12 13 14 15 16 17 18 19 20

Products. Technology. Services. Delivered Globally.

www.anixter.com

0459

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9


Specifications Application
These cables are used to control the display sequence of the traffic signals (e.g. red, red and amber, green etc) and are also known as Junction High Voltage Cables. Cores are individually colour coded.

Traffic Signal Cables

Armoured Multicore Junction High Voltage Cable


PVC/PVC/SWA/PVC 600/1000 V, 70C

10 11 12 13 14 15

Generally in accordance with BS6346 Conductors: Solid (Class 1) plain copper conductors to BS EN 60228 Insulation: PVC Type TI.1 to BS EN 50363-3 Core Identification: See colour code chart on page 4:65 Inner Sheath: Black PVC inner sheath Type TM.1 to BS EN 50363-4-1
Anixter Number Number Nominal Nominal of Cond. Cond. Cores Area Stranding mm2 A7-D10-C004-08 4 8 12 16 20 4 8 12 16 20 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 #/mm 1/1.13 1/1.13 1/1.13 1/1.13 1/1.13 1/1.38 1/1.38 1/1.38 1/1.38 1/1.38 Insulation Thickness

Mild galvanised steel wires to BS EN 10257-1 Outer Sheath: Orange PVC outer sheath type TM.1 to BS EN 50363-4-1 embossed TRAFFIC SIGNALS Flame retardant to BS EN 60332-1-2 Voltage Rating: 600/1000 V Temperature Rating: 70C maximum conductor operating temperature
Nominal Diameter Under Armour mm 7.50 9.70 11.60 12.90 14.50 8.10 10.50 12.70 14.10 15.80 Armour Wire Size Nominal O/D Approx. Cable Weight kg/km 308 425 546 754 881 340 492 742 894 1117 Minimum Bending Radius (fixed bend) mm 80 90 110 120 130 80 100 110 120 130

mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60

mm 0.90 0.90 1.25 1.25 1.25 0.90 0.90 1.25 1.25 1.25

mm 12.10 14.30 17.10 18.40 20.20 12.70 15.10 18.20 19.80 21.50

16 17 18

A7-D10-C008-08 A7-D10-C012-08 A7-D10-C016-08 A7-D10-C020-08 A7-D15-C004-08

19 20

A7-D15-C008-08 A7-D15-C012-08 A7-D15-C016-08 A7-D15-C020-08

Products. Technology. Services. Delivered Globally.

0460

www.anixter.com

1 Control and Instrumentation Cables

Traffic Signal Cables

Technical Information
Colour code charts for multicore Junction High Voltage Cable
Core Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Core Colour Brown* Yellow Green/blue Red White Blue Black Orange Red/white Grey Red/blue Purple Brown/red Yellow/red Grey/red Black/red Purple/red Orange/red Green/red Blue/white

2 3 4 5 6 7 8 9 10 11 12

*N.B: Core number 1 on 4 core cable is blue.

13 14

Electrical Characteristics
Units Maximum d.c. conductor resistance @ 20C Minimum insulation resistance @ 20C Sustained Current Ratings: Buried direct in ground In single-way duct In air A A A 26 21 19 32 26 24 Ohms/km Mohms/km Cond. Size 1.0mm 18.1 11
2

Cond. Size 1.5mm 12.1 10

15 16 17 18 19 20

Current ratings are based on the following standard conditions: Standard depth of laying 0.5m. Thermal resistivity of soil 1.2C m/W. Standard ground temperature 15C. Ambient air temperature 25C. Maximum conductor temperature 70C.

Products. Technology. Services. Delivered Globally.

www.anixter.com

0461

1 Control and Instrumentation Cables 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20


Cables Laid Direct in Ground Ground temp C 10 15 Rating factor 1.04 1.0 Rating factor need not apply if the number of cores carrying appreciable current does not exceed the square root of n, where n = total number of cores in cable. If cables are to be used in ambient air or ground temperatures other than those specified, the following rating factors should be applied: Cables Laid in Air Ambient air temp C Rating factor

Traffic Signal Cables


Ratings assume that only two cores are loaded simultaneously. Where more than two cores are loaded simultaneously, the following factors should be applied to the current ratings shown: Number of cores loaded Rating factor 2 1.0 3 4 5 6 7 10 0.87 0.78 0.72 0.67 0.63 0.56 12 14 19 0.53 0.51 0.45

25 1.0

30 35 40 45 50 55 0.94 0.88 0.82 0.75 0.67 0.58

20 25 30 35 40 0.95 0.90 0.85 0.80 0.74

45 50 0.67 0.60

Cables Laid in Ducts Ground temp C Rating factor

10 15 1.04 1.0

20 25 30 35 40 0.95 0.90 0.85 0.80 0.74

45 50 0.67 0.60

Products. Technology. Services. Delivered Globally.

0462

www.anixter.com

You might also like