You are on page 1of 10

PROJECT:

Description:
Date:

5290-RIANA GREEN EAST


MSB A1
5/14/2012

Reactive Power Compensation


1. Calculation Of Conventional Capacitor Bank
1.2 For application of 525V capacitor (VISHAY-ROEDERSTEIN)
System voltage
Capacitor voltage

:
:

415 Volts
525 Volts

Total kW / MD
:
Initial PF w/o capacitor :
Target PF
:

Total net effective kVAr at 415V, Nc:


Total connected kVAr at 525V, Qc :

751.88 kW
0.75
0.9

Switching programs provided by ESTAmat power factor regulator


6-step type

** MD -- Maximum demand
MCCB & contactors recommended ratings
kVAr
525 V
5
10
15
20
25
30
40
50
60
75
80
100
120
150
160
200

Capacitance
uF
3* 19.3
3* 38.5
3* 57.7
3* 77.0
3* 96.2
3* 115.5
3* 154.0
3* 192.5
3* 230.9
3* 288.7
3* 307.9
3* 384.9
3* 461.9
3* 577.4
3* 615.9
3* 769.8

Main MCCB, 25kA

Capacitor
current, A
4
9
13
17
22
26
35
43
52
65
70
87
104
130
139
174
624 A

MCCB
25kA, A
10
15
20
30
30
40
50
60
75
100
100
125
150
200
200
250

Contactor
AC3, A
9
12
22
30
30
40
50
65
80
105
105
120
150
220
220
250

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2
1: 1: 2: 2: 4: 4
1: 1: 2: 3: 3: 3
1: 1: 2: 4: 4: 4
1: 1: 2: 4: 8: 8
1: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3
1: 2: 3: 4: 4: 4
1: 2: 3: 6: 6: 6
1: 2: 4: 4: 4: 4
1: 2: 4: 8: 8: 8

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8

Assuming total capacitor output required = 250kVAr, 525V


option 1:
If a 6-step regulator is used, switching program no.2 can be selected :
Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare

-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
623.81

12-step type

Typical example for configuration of capacitor steps using above swicthing programs

REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.

Counter check

298.9 kVAr
478.4 kVAr

(output KVAR) =
MCCB
=

X kvar*(415/525)2
((output KVAR * 1000)/415*sqrt(3))*1.5

easy way
mccb

KVAR * .625 * 2.1

=
=

X KVAR * 0.625
output KVAR *2.1

PROJECT:
Description:
Date:

5290-RIANA GREEN EAST


MSB-A2
5/14/2012

Reactive Power Compensation


1. Calculation Of Conventional Capacitor Bank
1.2 For application of 525V capacitor (VISHAY-ROEDERSTEIN)
System voltage
Capacitor voltage

:
:

415 Volts
525 Volts

Total kW / MD
:
Initial PF w/o capacitor :
Target PF
:

Total net effective kVAr at 415V, Nc:


Total connected kVAr at 525V, Qc :

690.98 kW
0.75
0.9

Switching programs provided by ESTAmat power factor regulator


6-step type

** MD -- Maximum demand
MCCB & contactors recommended ratings
kVAr
525 V
5
10
15
20
25
30
40
50
60
75
80
100
120
150
160
200

Capacitance
uF
3* 19.3
3* 38.5
3* 57.7
3* 77.0
3* 96.2
3* 115.5
3* 154.0
3* 192.5
3* 230.9
3* 288.7
3* 307.9
3* 384.9
3* 461.9
3* 577.4
3* 615.9
3* 769.8

Main MCCB, 25kA

Capacitor
current, A
4
9
13
17
22
26
35
43
52
65
70
87
104
130
139
174
573 A

MCCB
25kA, A
10
15
20
30
30
40
50
60
75
100
100
125
150
200
200
250

Contactor
AC3, A
9
12
22
30
30
40
50
65
80
105
105
120
150
220
220
250

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2
1: 1: 2: 2: 4: 4
1: 1: 2: 3: 3: 3
1: 1: 2: 4: 4: 4
1: 1: 2: 4: 8: 8
1: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3
1: 2: 3: 4: 4: 4
1: 2: 3: 6: 6: 6
1: 2: 4: 4: 4: 4
1: 2: 4: 8: 8: 8

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8

Assuming total capacitor output required = 250kVAr, 525V


option 1:
If a 6-step regulator is used, switching program no.2 can be selected :
Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare

-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
573.22

12-step type

Typical example for configuration of capacitor steps using above swicthing programs

REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.

Counter check

274.7 kVAr
439.6 kVAr

(output KVAR) =
MCCB
=

X kvar*(415/525)2
((output KVAR * 1000)/415*sqrt(3))*1.5

easy way
mccb

KVAR * .625 * 2.1

=
=

X KVAR * 0.625
output KVAR *2.1

PROJECT:
Description:
Date:

5290-RIANA GREEN EAST


MSB-BC1
5/14/2012

Reactive Power Compensation


1. Calculation Of Conventional Capacitor Bank
1.2 For application of 525V capacitor (VISHAY-ROEDERSTEIN)
System voltage
Capacitor voltage

:
:

415 Volts
525 Volts

Total kW / MD
:
Initial PF w/o capacitor :
Target PF
:

Total net effective kVAr at 415V, Nc:


Total connected kVAr at 525V, Qc :

529.52 kW
0.75
0.9

Switching programs provided by ESTAmat power factor regulator


6-step type

** MD -- Maximum demand
MCCB & contactors recommended ratings
kVAr
525 V
5
10
15
20
25
30
40
50
60
75
80
100
120
150
160
200

Capacitance
uF
3* 19.3
3* 38.5
3* 57.7
3* 77.0
3* 96.2
3* 115.5
3* 154.0
3* 192.5
3* 230.9
3* 288.7
3* 307.9
3* 384.9
3* 461.9
3* 577.4
3* 615.9
3* 769.8

Main MCCB, 25kA

Capacitor
current, A
4
9
13
17
22
26
35
43
52
65
70
87
104
130
139
174
439 A

MCCB
25kA, A
10
15
20
30
30
40
50
60
75
100
100
125
150
200
200
250

Contactor
AC3, A
9
12
22
30
30
40
50
65
80
105
105
120
150
220
220
250

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2
1: 1: 2: 2: 4: 4
1: 1: 2: 3: 3: 3
1: 1: 2: 4: 4: 4
1: 1: 2: 4: 8: 8
1: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3
1: 2: 3: 4: 4: 4
1: 2: 3: 6: 6: 6
1: 2: 4: 4: 4: 4
1: 2: 4: 8: 8: 8

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8

Assuming total capacitor output required = 250kVAr, 525V


option 1:
If a 6-step regulator is used, switching program no.2 can be selected :
Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare

-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
439.30

12-step type

Typical example for configuration of capacitor steps using above swicthing programs

REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.

Counter check

210.5 kVAr
336.9 kVAr

(output KVAR) =
MCCB
=

X kvar*(415/525)2
((output KVAR * 1000)/415*sqrt(3))*1.5

easy way
mccb

KVAR * .625 * 2.1

=
=

X KVAR * 0.625
output KVAR *2.1

PROJECT:
Description:
Date:

5290-RIANA GREEN EAST


MSB-BC2
5/14/2012

Reactive Power Compensation


1. Calculation Of Conventional Capacitor Bank
1.2 For application of 525V capacitor (VISHAY-ROEDERSTEIN)
System voltage
Capacitor voltage

:
:

415 Volts
525 Volts

Total kW / MD
:
Initial PF w/o capacitor :
Target PF
:

Total net effective kVAr at 415V, Nc:


Total connected kVAr at 525V, Qc :

535.15 kW
0.75
0.9

Switching programs provided by ESTAmat power factor regulator


6-step type

** MD -- Maximum demand
MCCB & contactors recommended ratings
kVAr
525 V
5
10
15
20
25
30
40
50
60
75
80
100
120
150
160
200

Capacitance
uF
3* 19.3
3* 38.5
3* 57.7
3* 77.0
3* 96.2
3* 115.5
3* 154.0
3* 192.5
3* 230.9
3* 288.7
3* 307.9
3* 384.9
3* 461.9
3* 577.4
3* 615.9
3* 769.8

Main MCCB, 25kA

Capacitor
current, A
4
9
13
17
22
26
35
43
52
65
70
87
104
130
139
174
444 A

MCCB
25kA, A
10
15
20
30
30
40
50
60
75
100
100
125
150
200
200
250

Contactor
AC3, A
9
12
22
30
30
40
50
65
80
105
105
120
150
220
220
250

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2
1: 1: 2: 2: 4: 4
1: 1: 2: 3: 3: 3
1: 1: 2: 4: 4: 4
1: 1: 2: 4: 8: 8
1: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3
1: 2: 3: 4: 4: 4
1: 2: 3: 6: 6: 6
1: 2: 4: 4: 4: 4
1: 2: 4: 8: 8: 8

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8

Assuming total capacitor output required = 250kVAr, 525V


option 1:
If a 6-step regulator is used, switching program no.2 can be selected :
Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare

-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
444.12

12-step type

Typical example for configuration of capacitor steps using above swicthing programs

REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.

Counter check

212.8 kVAr
340.6 kVAr

(output KVAR) =
MCCB
=

X kvar*(415/525)2
((output KVAR * 1000)/415*sqrt(3))*1.5

easy way
mccb

KVAR * .625 * 2.1

=
=

X KVAR * 0.625
output KVAR *2.1

PROJECT:
Description:
Date:

5290-RIANA GREEN EAST


MSB-D
5/14/2012

Reactive Power Compensation


1. Calculation Of Conventional Capacitor Bank
1.2 For application of 525V capacitor (VISHAY-ROEDERSTEIN)
System voltage
Capacitor voltage

:
:

415 Volts
525 Volts

Total kW / MD
:
Initial PF w/o capacitor :
Target PF
:

Total net effective kVAr at 415V, Nc:


Total connected kVAr at 525V, Qc :

438.12 kW
0.75
0.9

Switching programs provided by ESTAmat power factor regulator


6-step type

** MD -- Maximum demand
MCCB & contactors recommended ratings
kVAr
525 V
5
10
15
20
25
30
40
50
60
75
80
100
120
150
160
200

Capacitance
uF
3* 19.3
3* 38.5
3* 57.7
3* 77.0
3* 96.2
3* 115.5
3* 154.0
3* 192.5
3* 230.9
3* 288.7
3* 307.9
3* 384.9
3* 461.9
3* 577.4
3* 615.9
3* 769.8

Main MCCB, 25kA

Capacitor
current, A
4
9
13
17
22
26
35
43
52
65
70
87
104
130
139
174
364 A

MCCB
25kA, A
10
15
20
30
30
40
50
60
75
100
100
125
150
200
200
250

Contactor
AC3, A
9
12
22
30
30
40
50
65
80
105
105
120
150
220
220
250

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2
1: 1: 2: 2: 4: 4
1: 1: 2: 3: 3: 3
1: 1: 2: 4: 4: 4
1: 1: 2: 4: 8: 8
1: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3
1: 2: 3: 4: 4: 4
1: 2: 3: 6: 6: 6
1: 2: 4: 4: 4: 4
1: 2: 4: 8: 8: 8

1
2
3
4
5
6
7
8
9
10
11
12

1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8

Assuming total capacitor output required = 250kVAr, 525V


option 1:
If a 6-step regulator is used, switching program no.2 can be selected :
Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare

-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
363.54

12-step type

Typical example for configuration of capacitor steps using above swicthing programs

REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.

Counter check

174.2 kVAr
278.8 kVAr

(output KVAR) =
MCCB
=

X kvar*(415/525)2
((output KVAR * 1000)/415*sqrt(3))*1.5

easy way
mccb

KVAR * .625 * 2.1

=
=

X KVAR * 0.625
output KVAR *2.1