You are on page 1of 7

Corning Cable Systems

SRP-003-6S9
CORNING
Issue 1, August 2003
Discovering Beyond Imagination
Page 1 of7
Splice Tray Kit for Pretium 1U Housing
Table of Contents
Related Literature ......................................................................................................................................... 1
Admonislunents ............................................................................................................................................. 1
1. Product Infonnation ............................................................................................................................................ 2
2. Product Installation .............................................................................................................................................. 2
Install Splice Platform ................................................................................................................................... 2
Install the Cable ............................................................................................................................................ 3
Route Fiber .................................................................................................................................................... 4
Complete Installation .................................................................................................................................... 7
Revision History
Issue Date Reason for Change
1 0712003 Initial release
Related Literature
Pretium Closet Connector Housing Hardware Product Specifications
(pin LAN-538-EN)
Pretium Closet Connector Housing Hardware Ordering Guide
(pin LAN-539-EN)
Splice Tray Product Specifications (pIn LAN-331-EN)
Splice Protectors Product Specifications (pIn LAN-340-EN)
Admonishments
The precautionary terms used by Corning Cable Systems in its standard
recommended procedures conform to the guidelines expressed in the American
National Standards Institute document (ANSI 2235) for hazard alert messages.
Alerts are included in this instruction based on the following:
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, may result in
minor or moderate injury.
pIn 003-659
Page 2 SRP-003-6S9 Issue,
Retainer Nut (1)
Splice Tray Platform (1)
1
-r-
~
~ R.wning B..ck., (1)
Figure 1 - Splice Tray Bracket Kit Components
1. PRODUCT INFORMATION
Use this Splice Tray Bracket Kit (pin PCI-SPLC-04R) shown in Figure 1 when
splicing in the peR-1U housing is desired. The kit includes a splice tray platform,
retaining bracket, and hardware for installing up to four Type 2R or two Type 4R
splice trays.
Splice trays and splice protectors are purchased separately.
Factory pigtailed connector panels are also available.
Contact your customer service representative for more information or to purchase
accessories that are sold separately.
2. PRODUCT INSTALLATION
Install Splice Platform
Step 1 Slide cover off of the housing as described in the instruction provided
with the housing.
Step 2 Lift the tray stop latches on the tray and slide tray back completely.
Determine location for cable entry into housing.
Step 3 Remove the routing guides from inside the housing. Retain the lock
nuts for use later.
Step 4 Install the splice platform onto the studs where the routing guides were
located and secure with the nuts retained in Step 1 (Figure 2). Remove
retaining bracket from splice platform.
Splice Tray Kit for Pretium ,U Housing
Issue 1 SRP-003-6S9 Page 3
,.
I
Figure 2 Install Splice Platform
Install the Cable
Step 1 Secure the cable to the housing as detailed in the instruction provided
with the housing. Leave enough cable slack to allow the sliding tray to
move to the stops in the forward and back positions.
Step 2 Remove cable sheath as required for your application. Suggested
lengths are illustrated in Figure 3. Do not expose the bare fiber until
you are ready to terminate it.
Step 3 Cut strength member and yarn, when present, 4 inches from end of
cable sheath to allow for strain-relief. Strain-relieve as detailed in the
instruction provided with the housing.
NOTE: Fiber optic cable is sensitive to excessive pulling, bending and crushing forces.
Consult the cable specification sheet for the cable you are installing. Do not bend the
cable more sharply than the minimum recommended bend radius. Do not
apply more pullingforce to the cable than specified. Do not crush the cable or
allow it to kink. Doing so may cause damage that can alter the transmission
characteristics ofthe cable the cable may have to be replaced.
Bare Fibers
Refer to splice tray
instruction for length
required iu tray.
Bare Fibers Jacketed Caple
II I
Refeno splice 150 em (60 iu. )_\
I fur length reqUIred In tray.
Figure 3 - Sheath Removal
Splice Tray Kit for Pretium,U Housing
Issue 1 Page 4
Route Fiber
Step 1 Route buffer tubes from the incoming fiber optic cable over the cable
entry plate. Use a cable tie to loosely attach the buffer tubes to the
retaining flange at the rear of the housing closest to the port where the
Retaining Flange
Cable Entry Plate
\
Figure 4 Route Buffer Tube
Remove the blank panels from the unit and replace with appropriate
preconnectorized panels (Figure 5).
cable entered the housing (Figure 4).
Step 2
Figure 5 - Route Pigtails
Splice Tray Kit for Pretium 1U Housing
Issue 1 Page 5
Step 3 Place a splice tray on the splice platform.
Step 4 Lift up on tray stop latches and slide drawer toward the front of the
housing to make sure cable is not stressed. If necessary, readjust cable
strain-relief to prevent stress on fibers.
Step 5 Gather the pigtail fibers and the buffer tubes and route them as a group
around the splice platform to determine the point where they will enter
the splice tray.
Step 6 Mark the fibers and tubes at the point where they will enter the splice
tray (Figure 6).
Step 7 Uncoil the fibers and move the fibers and tray to a location where they
can be spliced. Install fibers into tray and splice according to the
instructions provided with the splice tray being used.
Figure 6 Mark Fiber
Splice Tray Kit for Pretium ,U Housing
Issue, Page 6
Step 8 Reroute the fibers and tubes around the splice platform.
Step 9 Place the splice tray inside the platform and reinstall the retaining
bracket over the splice tray as shown in Figure 7. Tighten the retainer
nut securely.
Cable Tie
Figure 7 Retaining Bracket Orientation for Type 4R Splice Trays
Splice Tray Kit for Pretium
YM
,U Housing
Issue 1 Page 7
When installing Type 2R trays, flip the retaining bracket over as
shown in Figure 8 and secure with the retainer nut. "When
installing only two Type 2 R trays, install the bracket as shown in
Figure 7.
Figure 8 - Retaining Bracket Orientation for Type 2R Splice Trays
Stipe 10 a cab[;tie secure
fibers- to the lance on the housing
(Figure 7). Do not tighten.
Complete Installation
Step 1 Carefully slide drawer back to original position. Adjust fiber slack if
necessary to prevent fiber damage during drawer actuation.
Step 2 Tighten UCC clamp or cable ties depending on the type of cable
strain-relief chosen. (Refer to installation instruction provided with
housing for more details.)
Step 3 If previously removed, slide the cover back in the retaining flanges
on top of the housing. Push the plunger fasteners to secure.
Step 4 Close the front and rear doors.
Corning Cable Systems LLC PO Box 489 Hickory, NC 28603-0489 USA
1-800-743-2671' FAX +1-828-325-5060' International +1-828-901-5000 http,IIwww.coming.com/cablesystems
Corning Cable Systems reserves the right to improve, enhance and modify the features and specifications of
Corning Cable Systems' products without prior notification. Discovering Beyond Imagination is a trademark of
Corning Incorporate. Pretium is a trademark of Corning Cable Systems Brands, Inc. All other trademarks are the
properties of their respective owners. Corning Cable Systems is ISO 9001 certified. 2003 Corning Cable Systems.
CORNING All rights reserved. published in the USA.
Discovering Beyond Imagination
SRP-003-6S9 I July 2003