You are on page 1of 18

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.1 Device, General Settings


No. 00003 00005 00051 00052 00055 00056 00067 00068 00069 00110 00113 00125 00140 00160 00144 00145 00146 00147 00177 00070 00071 00072 00183 D >Time Synch >Reset LED >Light on Device OK ProtActive Reset Device Initial Start Reset LED Resume Clock SyncError Event Lost Flag Lost Chatter ON Error Sum Alarm Error 5V Error 0V Error -5V Error PwrSupply Fail Battery Settings Calc. Settings Check Level-2 change Error Board 1 >Reset LED >Back Light on Device is Operational and Protecting At Least 1 Protection Funct. is Active Reset Device Initial Start of Device Reset LED Resume Clock Synchronization Error Event lost Flag Lost Chatter ON Error with a summary alarm Error 5V Error 0V Error -5V Error Power Supply Failure: Battery empty Setting calculation is running Settings Check Level-2 change Error Board 1 L >Synchronize Internal Real Time Clock SP SP OUT IntSP OUT OUT IntSP OUT OUT OUT OUT_Ev OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT IO IO Page 4 of 21 T SP_Ev H2 H3 IO IO IO I I I I IO IO I I IO IO IO IO IO IO IO IO IO BI F C BO LEDs O S T C CM

DayLightSavTime Daylight Saving Time

Alarm Sum Event Alarm Summary Event

SIMATIC No. 00184 00185 00186 00187 00188 00189 00016 00015 D Error Board 2 Error Board 3 Error Board 4 Error Board 5 Error Board 6 Error Board 7 DataStop >DataStop Test mode >Test mode Feeder gnd Brk OPENED HWTestMod SynchClock 00193 00191 00320 00321 00322 00323 00545 00546 Alarm NO calibr Error Offset Warn Mem. Data Error Board 2 Error Board 3 Error Board 4 Error Board 5 Error Board 6 Error Board 7 Stop data transmission >Stop data transmission Test mode >Test mode Feeder GROUNDED Breaker OPENED Hardware Test Mode Clock Synchronization L

Matrix - short view T OUT OUT OUT OUT OUT OUT IntSP SP IntSP SP IntSP IntSP IntSP IntSP_Ev OUT OUT OUT OUT OUT OUT VI VI IntSP IO X IO IO IO IO IO IO IO X X IO IO

19.09.11 10:41:30 BI F C BO LEDs O S T C CM IO IO IO IO IO IO IO X

Alarm: NO calibration data available Error: Offset Warn: Limit of Memory Data exceeded

Warn Mem. Para. Warn: Limit of Memory Parameter exceeded OUT Warn Mem. Oper. Warn: Limit of Memory Operation exceeded Warn Mem. New Distur.CFC PU Time TRIP Time Warn: Limit of Memory New exceeded Disturbance CFC Time from Pickup to drop out Time from Pickup to TRIP BLOCK Flexible Function

236.2127.01 BLK. Flex.Fct.

Page 5 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.2 Power System Data 1


No. D L Phase rotation ABC Phase rotation ACB T OUT OUT BI F C BO LEDs O S T C CM IO IO IO 05145 >Reverse Rot. >Reverse Phase Rotation SP 05147 Rotation ABC 05148 Rotation ACB

1.1.3 Oscillographic Fault Records


No. D L Waveform data deleted Fault Recording Start Fault recording is running T OUT_Ev IntSP OUT X BI F C BO LEDs O S T C CM X I IO 00004 >Trig.Wave.Cap. >Trigger Waveform Capture SP 00203 Wave. deleted FltRecSta 30053 Fault rec. run.

Page 6 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.4 Power System Data 2


No. D L >Manual close signal Primary fault current Ia Primary fault current Ib Primary fault current Ic Relay PICKUP Relay GENERAL TRIP command Manual close signal detected >52-a contact (OPEN, if bkr is open) Protection ON/OFF (via system port) T SP SP VI VI VI OUT OUT OUT SP IntSP H5 H4 U7 U1 L1 IO IO IO IO IO IO IO IO I I X BI F C BO LEDs O S T C CM 00356 >Manual Close 00533 Ia = 00534 Ib = 00535 Ic = 00501 Relay PICKUP 00511 Relay TRIP 00561 Man.Clos.Detect 04601 >52-a 04602 >52-b 00126 ProtON/OFF

02720 >Enable ANSI#-2 >Enable 50/67-(N)-2 (override 79 blk)

>52-b contact (OPEN, if bkr is closed) SP

Page 7 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.5 50/51 Phase/Ground Overcurrent


No. D L 50(N)/51(N) TRIP >BLOCK 50/51 >BLOCK 50-3 >BLOCK 50-2 >BLOCK 50-1 >BLOCK 51 50/51 O/C switched OFF 50/51 O/C is BLOCKED 50/51 O/C is ACTIVE T OUT SP SP SP SP SP OUT OUT OUT L2 L3 L4 IO IO IO IO IO IO IO I IO I IO I IO I IO H1 BI F C BO LEDs O S T C CM IO I 01761 50(N)/51(N) PU 01791 50(N)/51(N)TRIP 01704 >BLK 50/51 01718 >BLOCK 50-3 01721 >BLOCK 50-2 01722 >BLOCK 50-1 01723 >BLOCK 51 01751 50/51 PH OFF 01752 50/51 PH BLK 01753 50/51 PH ACT 01762 50/51 Ph A PU 01763 50/51 Ph B PU 01764 50/51 Ph C PU 01767 50-3 picked up 01769 50-3 TRIP 01800 50-2 picked up 01805 50-2 TRIP 01810 50-1 picked up 01815 50-1 TRIP 01820 51 picked up 01825 51 TRIP 01787 50-3 TimeOut 01804 50-2 TimeOut 01814 50-1 TimeOut 50(N)/51(N) O/C PICKUP OUT

50/51 Phase A picked up OUT 50/51 Phase B picked up OUT 50/51 Phase C picked up OUT 50-3 picked up 50-3 TRIP 50-2 picked up 50-2 TRIP 50-1 picked up 50-1 TRIP 51 picked up 51 TRIP 50-3 TimeOut 50-2 Time Out 50-1 Time Out OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT

Page 8 of 21

SIMATIC No. D 51 Time Out 50-3 BLOCKED 50-2 BLOCKED 50-1 BLOCKED 51 BLOCKED >BLOCK 50N/51N >BLOCK 50N-3 >BLOCK 50N-2 >BLOCK 50N-1 >BLOCK 51N 50N/51N is OFF 50N/51N is BLOCKED 50N/51N is ACTIVE 50N-3 picked up 50N-3 TRIP 50N-2 picked up 50N-2 TRIP 50N-1 picked up 50N-1 TRIP 51N picked up 51N TRIP 50N-3 TimeOut 50N-2 Time Out 50N-1 Time Out 51N Time Out L T OUT OUT OUT OUT OUT SP SP SP SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT

Matrix - short view BI F C BO LEDs O S T C CM IO IO IO IO IO IO IO IO

19.09.11 10:41:30

01824 51 Time Out 10034 50-3 BLOCKED 01852 50-2 BLOCKED 01851 50-1 BLOCKED 01855 51 BLOCKED 01714 >BLK 50N/51N 01719 >BLOCK 50N-3 01724 >BLOCK 50N-2 01725 >BLOCK 50N-1 01726 >BLOCK 51N 01756 50N/51N OFF 01757 50N/51N BLK 01758 50N/51N ACT 01768 50N-3 picked up 01770 50N-3 TRIP 01831 50N-2 picked up 01833 50N-2 TRIP 01834 50N-1 picked up 01836 50N-1 TRIP 01837 51N picked up 01839 51N TRIP 01788 50N-3 TimeOut 01832 50N-2 TimeOut 01835 50N-1 TimeOut 01838 51N TimeOut

H1

IO IO IO L5 IO IO I IO I IO I IO I IO

01765 50N/51NPickedup 50N/51N picked up

Page 9 of 21

SIMATIC No. D L 50N-3 BLOCKED 50N-2 BLOCKED 50N-1 BLOCKED 51N BLOCKED T OUT OUT OUT OUT

Matrix - short view BI F C BO LEDs O S T C CM IO IO IO IO IO IO IO IO

19.09.11 10:41:30

10035 50N-3 BLOCKED 01854 50N-2 BLOCKED 01853 50N-1 BLOCKED 01856 51N BLOCKED

Page 10 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.6 50 1Ph
No. D L >BLOCK 50 1Ph >BLOCK 50 1Ph-1 >BLOCK 50 1Ph-2 50 1Ph is OFF 50 1Ph is ACTIVE T SP SP SP OUT OUT OUT IO IO IO IO IO IO IO IO I IO I IO I IO IO BI F C BO LEDs O S T C CM 05951 >BLK 50 1Ph 05952 >BLK 50 1Ph-1 05953 >BLK 50 1Ph-2 05961 50 1Ph OFF 05963 50 1Ph ACTIVE 05966 50 1Ph-1 BLK 05967 50 1Ph-2 BLK 05971 50 1Ph Pickup 05972 50 1Ph TRIP 05974 50 1Ph-1 PU 05975 50 1Ph-1 TRIP 05977 50 1Ph-2 PU 05979 50 1Ph-2 TRIP 05980 50 1Ph I:

05962 50 1Ph BLOCKED 50 1Ph is BLOCKED

50 1Ph-1 is BLOCKED OUT 50 1Ph-2 is BLOCKED OUT 50 1Ph picked up 50 1Ph TRIP 50 1Ph-1 picked up 50 1Ph-1 TRIP 50 1Ph-2 picked up 50 1Ph-2 TRIP 50 1Ph: I at pick up OUT OUT OUT OUT OUT OUT VI

Page 11 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.7 Measurement Supervision


No. D L Failure: Current Summation Failure: Current Balance Failure: General Current Supervision Failure: Phase Sequence T OUT OUT OUT OUT OUT U4 U6 BI F C BO LEDs O S T C CM U4 U6 U4 U6 IO IO IO IO IO IO 00162 Failure Sum I 00163 Fail I balance 00161 Fail I Superv. 00171 Fail Ph. Seq.

00175 Fail Ph. Seq. I Failure: Phase Sequence Current

00197 MeasSup OFF Measurement Supervision is switched OFF OUT

Page 12 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.8 79M Auto Reclosing


No. 02701 >79 ON 02702 >79 OFF 02703 >BLOCK 79 02730 >CB Ready 02715 >Start 79 Gnd 02716 >Start 79 Ph 02722 >ZSC ON 02723 >ZSC OFF 02754 >79 DT St.Delay 02781 79 OFF 02782 79 ON 02784 79 is NOT ready 02785 79 DynBlock 02801 79 in progress 02851 79 Close 02862 79 Successful 02863 79 Lockout 02878 79 L-N Sequence 02879 79 L-L Sequence 02883 ZSC active 02884 ZSC ON 02885 ZSC OFF 00127 79 ON/OFF D >79 ON >79 OFF >BLOCK 79 >Circuit breaker READY for reclosing >Start 79 Ground program >Start 79 Phase program >Switch zone sequence coordination ON >Switch zone sequence coordination OFF >79: Dead Time Start Delay 79 Auto recloser is switched OFF 79 Auto recloser is switched ON 79 Auto recloser is NOT ready 79 - in progress 79 - Close command 79 - cycle successful 79 - Lockout 79-A/R single phase reclosing sequence 79-A/R multi-phase reclosing sequence Zone Sequencing is active Zone sequence coordination switched ON 79 ON/OFF (via system port) L T SP SP SP SP SP SP SP SP SP OUT IntSP OUT OUT OUT OUT OUT OUT OUT OUT OUT IntSP OUT OUT IO I I IO I I Page 13 of 21 U2,U3 I I IO IO IO I IO IO IO I I I I I I I I BI F C BO LEDs O S T C CM IO IO IO IO I I

79 - Auto-reclose is dynamically BLOCKED OUT

Zone sequence coordination switched OFF OUT

02788 79 T-CBreadyExp 79: CB ready monitoring window expired 02810 79 TdeadMax Exp 79: Maximum dead time expired

SIMATIC No. D L

Matrix - short view T OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT I IO IO IO I I I I I I I I I I I I IO BI F C BO LEDs O S T C CM

19.09.11 10:41:30

02889 79 1.CycZoneRel 02890 79 2.CycZoneRel 02891 79 3.CycZoneRel 02892 79 4.CycZoneRel 02809 79 T-Start Exp 02865 79 Sync.Request 02844 79 1stCyc. run. 02845 79 2ndCyc. run. 02846 79 3rdCyc. run. 02847 79 4thCyc. run. 02731 >Sync.release 02711 >79 Start 02808 79 BLK: CB open 02823 79 no starter 02824 79 no cycle 02827 79 BLK by trip 02828 79 BLK:3ph p.u. 02829 79 Tact expired 02830 79 Max. No. Cyc 02899 79 CloseRequest 02753 79 DT delay ex.

79 1st cycle zone extension release 79 2nd cycle zone extension release 79 3rd cycle zone extension release 79 4th cycle zone extension release 79: Start-signal monitoring time expired 79: Synchro-check request 79 1st cycle running 79 2nd cycle running 79 3rd cycle running 79 4th or higher cycle running >79: Sync. release from ext. sync.-check >79 External start of internal A/R 79: CB open with no trip 79: no starter configured 79: no cycle configured 79: blocking due to trip 79: blocking due to 3-phase pickup 79: action time expired before trip 79: max. no. of cycles exceeded 79: Close request to Control Function 79: Max. Dead Time Start Delay expired

Page 14 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.9 Control Authorization


No. D Cntrl Auth ModeLOCAL L Control Authority Controlmode LOCAL T IntSP IntSP BI F C BO LEDs O S T C CM IO IO IO ModeREMOTE Controlmode REMOTE IntSP

Page 15 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.10 Control Device


No. D 52Breaker 52Breaker Disc.Swit. Disc.Swit. GndSwit. GndSwit. 52 Open 52 Close Disc.Open Disc.Close GndSw Cl. UnlockDT Q2 Op/Cl Q2 Op/Cl Q9 Op/Cl Q9 Op/Cl 52 Breaker 52 Breaker Disconnect Switch Disconnect Switch Ground Switch Ground Switch Interlocking: 52 Open Interlocking: 52 Close L DP CF_D2 DP CF_D2 DP IntSP IntSP X X X X X X X IO IO IO IO IO T CF_D12 X4 BI F C BO LEDs O S T C CM Tr1 IO X X X X X X X X X

Interlocking: Disconnect switch Open IntSP Interlocking: Disconnect switch Close IntSP IntSP IntSP IntSP CF_D2 DP CF_D2 DP CF_D2 DP Interlocking: Ground switch Close Unlock data transmission via BI Q2 Open/Close Q2 Open/Close Q9 Open/Close Q9 Open/Close

GndSw Open Interlocking: Ground switch Open

Fan ON/OFF Fan ON/OFF Fan ON/OFF Fan ON/OFF

Page 16 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.11 Process Data


No. D >CB ready >DoorClose >Door closed >Door open >Cabinet door open >CB wait >No Volt. >Err Mot V >ErrCntrlV >SF6-Loss >Err Meter >Tx Temp. >No Voltage (Fuse blown) >Error Motor Voltage >Error Control Voltage >SF6-Loss >Error Meter >Transformer Temperature L >CB ready Spring is charged T SP SP SP SP SP SP SP SP SP SP IO IO IO IO IO IO IO IO IO BI F C BO LEDs O S T C CM X X X X X

>CB waiting for Spring charged SP

>Tx Danger >Transformer Danger

1.1.12 Measurement
No information available

Page 17 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.13 Demand Measurement Setup


No information available

1.1.14 Min/Max Measurement Setup


No. D L >I MIN/MAX Buffer Reset >I1 MIN/MAX Buffer Reset >Idmd MIN/MAX Buffer Reset T SP SP SP BI F C BO LEDs O S T C CM I I I I 00395 >I MinMax Reset 00396 >I1 MiMaReset 00403 >Idmd MiMaReset

00412 > Theta MiMa Reset >Theta MIN/MAX Buffer Reset SP

Page 18 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.15 Set Points (Measured Values)


No. D L Set Point Phase A dmd> Set Point Phase B dmd> Set Point Phase C dmd> T OUT OUT OUT OUT BI F C BO LEDs O S T C CM X X X X X IO IO IO IO IO 00273 SP. I A dmd> 00274 SP. I B dmd> 00275 SP. I C dmd> 00276 SP. I1dmd>

Set Point positive sequence I1dmd> OUT

00284 SP. 37-1 alarm Set Point 37-1 Undercurrent alarm

1.1.16 Energy
No information available

Page 19 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.17 Statistics
No. D L Counter of operating hours Accumulation of interrupted current Ph A Accumulation of interrupted current Ph B Accumulation of interrupted current Ph C T VI SP VI VI VI X X IO BI F C BO LEDs O S T C CM 01020 Op.Hours= 01021 Sum Ia = 01022 Sum Ib = 01023 Sum Ic = 02896 79 #Close1./3p= 02898 79 #Close2./3p=

00409 >BLOCK Op Count >BLOCK Op Counter

No. of 1st AR-cycle CLOSE commands,3pole VI No. of higher AR-cycle CLOSE commands,3p VI

1.1.18 Set Points (Statistic)


No. D L T BI F C BO LEDs O S T C CM IO 00272 SP. Op Hours> Set Point Operating Hours OUT

Page 20 of 21

SIMATIC

Matrix - short view

19.09.11 10:41:30

1.1.19 Threshold-Switch
No. D L T BI F C BO LEDs O S T C CM IO X ThreshVal1 Threshold Value 1 IntSP

Page 21 of 21