PA C KA G E D E L E C T R I C / e l e c t r i c

KC

Landmark Rooftop Units


60 HZ

E N G I N E E R I N G D ATA

Bulletin No. 210504


February 2010

Supersedes October 2009

ASHRAE 90.1
COMPLIANT
2 to 7.5 Tons
Net Cooling Capacity - 23,600 to 90,000 Btuh
Optional Electric Heat - 7.5 to 30 kW
MODEL NUMBER IDENTIFICATION
K C A 060 S 4 B N 1 Y
Brand/Family
K = Landmark Product Line
Unit Type
C = Packaged Electric Cooling w/ optional Electric Heat
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity - Tons
024 = 2 Tons
030 = 2.5 Tons
036 = 3 Tons
048 = 4 Tons
060 = 5 Tons
072 = 6 Tons
090 = 7.5 Tons
Cooling Efficiency
S = Standard Efficiency

Voltage
P = 208/230V-1 phase-60hz
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Factory Installed Electric Heat
N = No Heat
Blower Type
D = Direct Drive
B = Belt Drive
Refrigerant Type
4 = R-410A

FEATURES AND BENEFITS

F
I
K
N

C
D
M
B
H

L
G

KCA090S
(Cooling with Optional Electric Heat)
Shown With Optional Electric Heat, Economizer, Power
Exhaust and Hinged Access Panels

Landmark rooftop units from Lennox are the new standard for reliable, efficient rooftop units built for long-lasting
performance that can significantly improve indoor and outdoor environments. Landmark rooftop units feature:









R-410A Refrigerant - Environmentally friendly


Scroll Compressors - Single speed scroll compressors are furnished on all models.
High Pressure Switches - Protect compressor.
Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow.
Direct or Belt Drive Blower Motors - Direct drive (024, 030, 036, 048 and 060 models). Belt drive motors (036,
048, 060, 072 and 090 models) to maximize air performance.
Independent Motor Mounts - Allows for easy and efficient service access without removing the top panel.
Downflow or Horizontal Airflow - Easy field conversion.
Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle.
Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved
serviceability.
Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 2

FEATURES AND BENEFITS


Contents
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Blower Data - Belt Drive . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Blower Data - Direct Drive . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . 27
Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . 1
Optional Conventional Temperature Control Systems . . . . . . . . . . . 34
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Specifications - Belt Drive Blower . . . . . . . . . . . . . . . . . . . . . 12
Specifications - Direct Drive Blower . . . . . . . . . . . . . . . . . . . . 10
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

High Pressure Switch


Protects the compressor from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation.
Filter/Drier
High capacity filter/drier protects
the system from dirt and moisture.
Freezestat
Protects the evaporator coil from
damaging ice build-up due to
conditions such as low/no air flow,
or low refrigerant charge.

D Coil Construction
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer. Factory leak tested.
Evaporator Coil

APPROVALS
ETL and CSA listed.
Efficiency ratings verified by CSA.
Components bonded for grounding
to meet safety standards for
servicing required by UL, ULC and
National and Canadian Electrical
Codes.
2 thru 5 ton models are certified
in accordance with the USE
certification program, which is
based on AHRI Standard 210/240
2006.
6 and 7.5 ton models are certified
in accordance with the ULE
certification program, which is
based on AHRI Standard 340/3602007.
All models are ASHRAE 90.1
compliant.
ISO 9001 Registered
Manufacturing Quality System.
WARRANTY
Limited five years on compressors.
Limited one year all other covered
components.

COOLING SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.

Cross row circuiting with rifled


copper tubing optimizes both
sensible and latent cooling
capacity.

System can operate from 30F


to 125F without any additional
controls.

Condenser Coil

R-410A Refrigerant

Condensate Drain Pan

Non-chlorine,
ozone friendly,
R-410A.

Plastic pan, sloped to meet


drainage requirements of ASHRAE
62.1.

Unit is factory pre-charged with


refrigerant. See Specifications
Tables.

Side or bottom drain connections.


Reversible to allow connection at
back of unit.

Two independent formed coils


allow separation for cleaning.

E Outdoor Coil Fan Motor

B Compressor
Resiliently mounted on rubber
grommets for quiet operation.
Scroll compressors for high
performance, reliability and quiet
operation.
Compressor Crankcase Heater
(Furnished on 072-090 Models
Only)

Thermal overload protected, totally


enclosed, permanently lubricated
sleeve (024, 030, 036 and 048
models) or ball bearings (060, 072
and 090 models), shaft up, wire
basket mount.
Outdoor Coil Fan
PVC coated fan guard furnished.

Protects against refrigerant


migration that can occur during
low ambient operation.

C Thermal Expansion Valve


Assures optimal performance
throughout the application range.
Removable element head.
Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 3

FEATURES AND BENEFITS


COOLING SYSTEM
(CONTINUED)
REQUIRED SELECTIONS
Cooling Capacity
Specify nominal cooling capacity of
the unit.
OPTIONS/ACCESSORIES
Field Installed
Condensate Drain Trap
Field installed only.
Available in copper or PVC.
Compressor Crankcase Heater
(Optional for 024-060 Models
Only)
Protects against refrigerant
migration that can occur during low
ambient operation.
Low Ambient Kit
Cycles the outdoor fan while
allowing compressor operation in
the cooling cycle. This intermittent
fan operation allows the system
to operate without icing the
evaporator coil and losing capacity.
Designed for use in ambient
temperatures no lower than 0F. A
crankcase heater must be installed
on the compressor.
CABINET
F Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
fork slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Air-Flow Choice
Units are shipped in downflow
(vertical) configuration, can be field
converted to horizontal air flow
configuration without the need of
a kit.

G Power Entry
Electrical lines can be brought
through the unit base or through
horizontal access knock-outs.

H Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.

I Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air
seal to the roof curb, eliminating
the need to add a seal during
installation.
Access Panels
Access panels are provided for
the economizer/filter section,
heating/blower section, and the
compressor/controls section.
OPTIONS/ACCESSORIES
Factory Installed
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited
dry film process. (AST ElectroFin
E-Coat) Meets Mil Spec
MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing, ASTM 1153 Standard
Specification for Methyl Isobutyl
Ketone.

J Hinged Access Panels


Large access panels are hinged
and have quarter-turn latches
for quick and easy access to
maintenance areas (economizer
/ filter, compressor / controls,
heating / blower).
Field Installed
Coil Guards
Painted, galvanized steel wire
guards to protect outdoor coil. Not
used with Hail Guards.
Hail Guards
Constructed of heavy gauge
steel, painted to match cabinet,
helps protect outdoor coils from
hail damage. Not used with Coil
Guards.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 4

CONTROLS
Unit Control
All control voltage is provided via a
24V (secondary) transformer with
built-in circuit breaker protection.
Heat/Cool Staging - Capable of
up to 2 heat / 2 cool staging with a
third party DDC control system or
thermostat.
Low Voltage Terminal Block Provides screw terminal
connections for thermostat or
controller wiring.
Night Setback Mode - Saves
energy by closing outdoor air
dampers and operating supply fan
on thermostat demand only.
OPTIONS / ACCESSORIES
Field Installed
Commercial Control Systems
L Connection Network
Complete building automation
control system for single or
multi-zone applications. Options
include local interface, software
for local or remote communication,
and hardware for networking
other control functions. See L
Connection Network Engineering
Handbook Bulletin for details.
Smoke Detector
Photoelectric type, installed in
supply air section, return air
section or both sections. Available
with power board and single
sensor (supply or return) or power
board and two sensors (supply and
return). Power board located in unit
control compartment.
Thermostats
Control system and thermostat
options. Aftermarket unit controller
options. See See page 34.

FEATURES AND BENEFITS

K BLOWER
A wide selection of supply air
blower options are available
to meet a variety of air flow
requirements.

OPTIONS/ACCESSORIES
Field Installed
Healthy Climate UVC
Germicidal Lamps

Marked & Color-Coded Wiring

Motor

All electrical wiring is color-coded


and marked to identify which
components it is connecting.

Overload protected, equipped with


ball bearings (belt drive) or sleeve
bearings (direct drive).
Direct drive motors are offered
on 024, 030, 036, 048 and 060
models.
Belt drive motors are offered
on 036, 048, 060, 072 and 090
models and are available in
several different sizes to maximize
air performance.
Supply Air Blower
Forward curved blades, blower
wheel is statically and dynamically
balanced.
All belt drive motors have
adjustable pulley for speed
change.
Ordering Information
Specify direct drive or belt drive
motor
For belt drive, specify motor
horsepower and drive kit number
when base unit is ordered.
REQUIRED SELECTIONS
Supply Air Blower
Order one, belt drive or direct
drive (See Blower Data Table for
specifications).
Order one drive kit, belt drive only,
see Drive Kit Specifications Table.
INDOOR AIR QUALITY
Air Filters
Disposable 2 inch filters furnished
as standard.

SERVICEABILITY
Designed to streamline general
maintenance and decrease
troubleshooting time.

Electrical Plugs
Helps eliminate mold and bacterial
growth on the evaporator and drain
pans. Improves indoor air quality
and maintains efficiency of system
by reducing fouling of evaporator
coil.
Indoor Air Quality (CO2) Sensor
Monitors CO2 levels adjusts
economizer dampers as needed
for Demand Control Ventilation.
ELECTRICAL

Positive connection electrical plugs


are used to connect common
accessories or maintenance parts
for easy removal or installation.
Blower Access
Supply air blower parts are located
near the access door for easy
servicing and adjustment.
Thermal Expansion Valves
Thermal expansion valves are
located near the perimeter of the
unit for easier access.

REQUIRED SELECTIONS
Voltage Choice

Removable element head allows


change out of element and bulb
without removing the TXV.

Specify when ordering base unit.

Coil Cleaning

OPTIONS/ACCESSORIES
Factory or Field Installed

Independently formed condenser


coils allow separation for easier
cleaning.

GFI Service Outlets (2)


115v ground fault circuit interrupter
(GFCI) type.
Field Installed
Disconnect Switch up to 150
Amp
Accessible from outside of unit,
spring loaded weatherproof cover
furnished. Main power to the unit is
field connected to the disconnect
which allows all power to be shut
off for service. See Electrical/
Electric Heat tables for ordering
information, page 27.

L Electric Heat
Helix wound nichrome elements,
individual element limit controls,
wiring harness.

Standard Components
A large number of common
maintenance parts are standard
throughout the entire range of
sizes, reducing the need to carry
a lot of different parts to the job or
maintain in inventory.
Compressor Compartment
Compressor is located near the
perimeter of the unit for easier
access.
Compressor is isolated from
the condenser air flow allowing
system operation checks to be
done without changing the air flow
across the outdoor coils.

Unit Fuse Block must be ordered


extra for 024-072 models. See
Electrical/Electric Heat tables for
ordering information. Furnished with
090 models.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 5

FEATURES AND BENEFITS

M ECONOMIZER/OUTDOOR
AIR/EXHAUST OPTIONS
Factory or Field Installed
Economizer, Downflow
Parallel gear-driven action return
air and outdoor air dampers,
plugin connections to unit, nylon
bearings, neoprene seals, 24-volt,
fully-modulating, spring return
motor, adjustable minimum damper
position. Economizer includes
barometric relief dampers.
Barometric Relief Dampers allow
relief of excess air, aluminum blade
dampers prevent blow back and
outdoor air infiltration during off
cycle, bird screen furnished. Hood
furnished.
Outdoor Air Hoods are included
when economizer is factory
installed and are furnished with
economizer when ordered for field
installation.
Choice of single (factory installed)
or differential (optional) enthalpy or
temperature economizer control is
available.
Horizontal conversion kit available
for field installation.
Single Enthalpy Control
Outdoor air enthalpy sensor
enables economizer if the outdoor
enthalpy is less than the setpoint
of the board. Furnished with
Economizer.
Field Installed
Outdoor Air Damper - Manual
Two sliding dampers provide 0 to
35% outdoor air, installs internal to
unit. Includes Outdoor Air Hood.
Outdoor Air Damper Motorized
Kit
Used to convert Manual Outdoor
Air Dampers to motorized
dampers. Kit includes linked
mechanical dampers and spring
return damper motor with plug-in
connection.

Differential Enthalpy Control


An optional, return air, solidstate
enthalpy sensor can be ordered
extra for field installation. Allows
the economizer control board
to select between outdoor air or
return air, whichever has lower
enthalpy. Field installed.
Economizer Temperature
Control - Single
An optional, solidstate
temperature sensor can be
ordered extra for field installation.
Enables the economizer when the
outdoor air temperature is below
the configured setpoint.
Economizer Temperature
Control - Differential
Order two single, temperature
control kits. One is field installed in
the return air section, the other in
the outdoor air section. Allows the
economizer control board to select
between outdoor air or return air,
whichever has lower temperature.
Horizontal Conversion Kit
Insulated panel covers the bottom
return air opening on the unit base
to convert downflow economizer to
horizontal air flow.

N Power Exhaust Fan


Installs internal to unit for down
flow applications only with
economizer option. Provides
exhaust air pressure relief.
Interlocked to run when supply air
blower is operating, fan runs when
outdoor air dampers are 50% open
(adjustable), motor is overload
protected. Requires Economizer
with Outdoor Air Hood. Fan is
16 in. diameter with 4 fan blades
(T1PWRE10A) or 20 in. diameter
with 5 blades (T1PWRE10N). Both
include a 3/4 hp motor.
NOTE - Not available for 024 and
030 models.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 6

CEILING DIFFUSERS
Ceiling Diffusers (Flush and
Step-Down)
Aluminum grilles, large center
grille, insulated diffuser box with
flanges, hanging rings furnished,
interior transition (even air flow),
internally sealed (prevents
recirculation), adapts to Tbar
ceiling grids or plaster ceilings.
Transitions (Supply and Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
ROOF CURB
Roof Curb, Downflow
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down. Available in 8, 14,
18, and 24 inch heights.
Cliplock curbs use interlocking
tabs to fasten together. No tools
required.
Hinged curb corners fasten
together with furnished hinge pins.
Standard roof curb corners fasten
together with furnished hardware.
NOTE - 090 models can be used
on smaller 79-3/4 in. roof curbs
(not full perimeter) with 15-3/4 in.
overhang at condenser end of unit.
See dimension drawing on page 42.

OPTIONS / ACCESSORIES
Item

Model Catalog
No.
No.
024

Unit Model No.


030

036

048

060

072

090
X

COOLING SYSTEM
Condensate Drain Trap

PVC - LTACDKP03/07

37K69

Copper - LTACDKC03/07

45K67

X
X

Corrosion Protection
Compressor Crankcase Heater

208/230V-1 or 3 ph - K1CCHT02A-1P

39W04

208/230V-1 or 3 ph - T1CCHT01AN1P

95M07

460V-3ph - K1CCHT012A-1G

39W05

460V-3ph - T1CCHT01AN1G

95M08

575V-3ph - K1CCHT02A-1J

39W06

X
X

575V-3ph - T1CCHT01AN1J

95M09

K1SNSR33AN1

41W33

Standard

R-410A

Direct Drive - 0.25 hp

O
O

Low Ambient Kit


Efficiency
Refrigerant Type
Blower - SUPPLY AIR
Motors

Direct Drive - 0.5 hp


Direct Drive - 0.75 hp

Belt Drive - 1 hp Standard Efficiency

Belt Drive - 1.5 hp Standard Efficiency

Belt Drive - 2 hp Standard Efficiency

Belt Drive - 3 hp Standard Efficiency


Drive Kits
See Blower Data Tables
for selection

O
O

Kit A01 - T1DRKT001-1 - 673-1010 rpm

Factory

Kit A02 - T1DRKT002-1 - 745-1117 rpm

Factory

Kit A03 - T1DRKT003-1 - 833-1250 rpm

Factory

Kit A04 - T1DRKT004-1 - 968-1340 rpm

Factory

Kit A05 - T1DRKT005-1 - 897-1346 rpm

Factory

Kit A06 - T1DRKT006-1 - 1071-1429 rpm

Factory

Kit A07 - T1DRKT007-1 - 1212-1548 rpm

Factory

Kit A08 - T1DRKT008-1 - 1193-1591 rpm

Factory

Kit AA01 - T1DRKT001AP1 - 522-784 rpm

Factory

Kit AA02 - T1DRKT002AP1 - 632-875 rpm

Factory

Kit AA03 - T1DRKT003AP1 - 798-1105 rpm

Factory

Kit AA04 - T1DRKT004AP1 - 921-1228 rpm

Factory

O
O
O
O
O
O
O

CABINET
Coil Guards

Hail Guards

T1GARD20A-1

17W87

T1GARD20N-1

17W88

K1GARD20AP1

53W21

T1GARD10A-1

17W89

T1GARD10N-1

17W90

K1GARD10AP1

53W22

Hinged Access Panels

X
X
X

X
X
X

CONTROLS
Smoke Detector - Supply or Return
(Power board and one sensor)

C1SNSR44AP1

53W78

Smoke Detector - Supply and Return


(Power board and two sensors)

C1SNSR43AP1

53W79

2 hp blower motor is not available for 208/230V-1ph applications.

NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 7

OPTIONS / ACCESSORIES
Item
ECONOMIZER
Economizer
Economizer, Single Enthalpy Control
Includes Outdoor Air Hood and
Barometric Relief Dampers with Hood
Horizontal Economizer Conversion Kit
Economizer Controls
Differential Enthalpy Sensor
Single Temperature Control
Differential Temperature Control
OUTDOOR AIR
Outdoor Air Dampers
Damper Section - Manual,
Includes Outdoor Air Hood
Damper Motorized Kit - Order Manual
Outdoor Air Damper Separately
Power EXhaust FAN
Standard Static

ELECTRICAL
Voltage
60 hz

Disconnect
GFI Service Outlets
ELECTRIC HEAT
7.5 kW

10 kW
15 kW

22.5 kW

30 kW

Model Catalog
No.
No.
024

Unit Model No.


030

036

048

060

OX

OX

OX

OX

072

090

OX

OX

T1ECON30A-1
T1ECON30N-1

36W96
36W97

OX

T1HECK00AN1

17W45

T1SNSR60AN1
TASEK10/15
Order 2 - TASEK10/15

17W71
76M37
76M37

X
X
X

X
X
X

X
X
X

X
X
X

X
X
X

X
X
X

X
X
X

T1DAMP11A-1
T1DAMP11N-1
T1DAMP21AN1

16W88
16W91
16W92

X
X

X
X

208/230V-1 or 3ph - T1PWRE10A-1P


460V-3ph - T1PWRE10A-1G
575V-3ph - T1PWRE10A-1J
208/230V-1 or 3ph - T1PWRE10N-1P
460V-3ph - T1PWRE10N-1G
575V-3ph - T1PWRE10N-1J

17W39
17W40
17W41
17W42
17W43
17W44

X
X
X

X
X
X

X
X
X
X
X
X

X
X
X

208/230V - 1 phase
208/230V - 3 phase
460V - 3 phase
575V - 3 phase
See Electrical/Electric Heat Tables for selection
LTAGFIK10/15 74M70
208/230V-1ph - T1EH0075AN1P
208/230V-3ph - T1EH0075AN1Y
460V-3ph - T1EH0075AN1G
575V-3ph - T1EH0075AN1J
208/230V-1ph - T1EH0100A1P
208/230V-1ph - T1EH0150AN1P
208/230V-3ph - T1EH0150AN1Y
460V-3ph - T1EH0150AN1G
575V-3ph - T1EH0150AN1J
208/230V-1ph - T1EH0225AN1P
208/230V-3ph - T1EH0225AN1Y
460V-3ph - T1EH0225AN1G
575V-3ph - T1EH0225AN1J
575V-3ph - T1EH0225AN1J
208/230V-3ph - T1EH0300N-1Y
460V-3ph - T1EH0300N-1G
575V-3ph - T1EH0300N-1J

14W32
14W35
14W39
14W43
30W26
14W33
14W36
14W40
14W44
14W34
14W37
14W41
14W45
14W45
14W38
14W42
14W46

ELECTRIC HEAT ACCESSORIES


Unit Fuse Block - See Electrical/Electric Heat Tables for Selection
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 8

X
OX

X
OX

O
O
O
O
X
OX

O
O
O
O
X
OX

O
O
O
O
X
OX

O
O
O
X
OX

O
O
O
X
OX

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X

X
X
X

X
X
X
X

X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X

X
X
X

X
X
X
X
X
X
X

X
X
X
X
X
X
X

OPTIONS / ACCESSORIES
Item

Unit Model No.

Model Catalog
No.
No.
024

030

036

048

060

072

090

Indoor Air Quality


Indoor Air Quality (Co2) Sensors
Sensor - white case CO2 display

C0SNSR50AE1L

77N39

Sensor - duct mount, black case, no display

C0SNSR53AE1L

87N54

C0MISC19AE1-

85L43

E1UVCL10AN1-

50W90

RTD9-65-R

27G87

RTD11-95

29G04

(Canada Only) RTD11-95S

13K61

FD9-65-R

27G86

FD11-95

29G08

(Canada Only) FD11-95S

13K56

T1TRAN10AN1

17W53

T1TRAN20N-1

17W54

T1CURB23AN1

16W93

K1CURB23AP1

52W20

T1CURB20AN1

16W94

K1CURB20AP1

52W21

T1CURB21AN1

16W95

K1CURB21AP1

52W22

T1CURB22AN1

16W96

K1CURB22AP1

52W23

T1CURB30AN1

17W46

K1CURB30AP1

52W17

T1CURB32AN1

17W47

K1CURB32AP1

52W18

T1CURB33AN1

17W48

K1CURB33AP1

52W19

T1CURB10AN1

13W27

K1CURB10AP1

52W24

CO2 Sensor Duct Mounting Kit


UVC Germicidal Lamps
1

Healthy Climate UVC Light Kit (208/230v-1ph)

CEILING DIFFUSERS
Step-Down - Order one

Flush - Order one

Transitions (Supply and Return) - Order one

ROOF CURBS - downFlow


Cliplock
8 in. height
14 in. height
18 in. height
24 in. height

X
X

X
X

X
X

Hinged
8 in. height
18 in. height
24 in. height

X
X

X
X

Standard
14 in. height

Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply
may be used to directly power the UVC ballast(s).
2
090 models will fit smaller roof curbs with overhang. See dimension drawing.
1

NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 9

SPECIFICATIONS - DIRECT DRIVE BLOWER


General Data

Nominal Tonnage
Model No.
Efficiency Type

Cooling
Performance

Standard

24,400

29,800

Net Cooling Capacity - Btuh

23,600

28,800

AHRI Rated Air Flow - cfm

840

1000

Sound Rating Number (dB)

75

75

Total Unit Power - kW

2.1

2.6

SEER (Btuh/Watt)

13

13

11.4

11.2

R-410A

R-410A

7 lbs. 0 oz.

7 lbs. 12 oz.

7.5, 10 kW

7.5, 10 kW

Scroll

Scroll

Net face area - sq. ft.

15.6

15.6

Tube diameter - in.

3/8

3/8

Refrigerant

EER (Btuh/Watt)
Type

Charge Furnished
Electric Heat Available - See page 8
Compressor Type (one per unit)

Number of rows

Fins per inch

20

20

Motor HP

1/4

1/4

Motor rpm

825

825

Total motor watts

250

250

Diameter - in. / No. of blades

24 - 3

24 - 3

Total air volume - cfm

3700

3700

Net face area - sq. ft.

7.8

7.8

Tube diameter - in.

3/8

3/8

Outdoor
Coil Fan

Number of rows

Fins per inch

14

14

(1) 3/4 npt

(1) 3/4 npt

Drain Connection (no. and size) - in.

2.5 Ton
KCA030S4D

Standard

Indoor Coil

2 Ton
KCA024S4D

Gross Cooling Capacity - Btuh

Outdoor Coil

2 - 2.5 TON

Expansion device type

Indoor Blower

Balanced Port Thermostatic Expansion Valve, removeable power head

Nominal Motor HP
Wheel nominal diameter x width - in.

Filters

.25

.25

10 x 10

10 x 10

Type

Disposable

Number and size - in.


Electrical Characteristics - 60 Hz

(4) 16 x 20 x 2
208/230V
1 phase

208/230V
1 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Certified in accordance with the USE certification program, which is based on AHRI Standard 210/240; 95F outdoor air temperature and 80F db/67F wb entering
evaporator air; minimum external duct static pressure.
2
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 10

SPECIFICATIONS - DIRECT DRIVE BLOWER


General Data

Nominal Tonnage
Model No.
Efficiency Type

Cooling
Performance

3 - 5 TON

3 Ton

4 Ton

5 Ton

KCA036S4D

KCA048S4D

KCA060S4D

Standard

Standard

Standard

Gross Cooling Capacity - Btuh

37,500

50,000

61,800

Net Cooling Capacity - Btuh

36,000

48,000

59,000

AHRI Rated Air Flow - cfm

1200

1600

1800

Sound Rating Number (dB)

75

75

82

Total Unit Power - kW

3.4

4.4

5.3

13

13

13

10.7

11

11.2

R-410A

R-410A

R-410A

8 lbs. 5 oz.

8 lbs. 10 oz.

11 lbs. 0 oz.

7.5, 15 kW

7.5, 15 kW

7.5, 15, 22.5 kW

Compressor Type (one per unit)

Scroll

Scroll

Scroll

Outdoor Coil

Net face area - sq. ft.

15.6

15.6

15.6

Tube diameter - in.

3/8

3/8

3/8

Number of rows

1.5

Fins per inch

20

20

20

Motor HP

1/4

1/4

1/3

Motor rpm

825

825

1075

Total motor watts

250

250

370

Diameter - in. / No. of blades

24 - 3

24 - 3

24 - 3

Total air volume - cfm

3700

3500

4300

Net face area - sq. ft.

7.8

7.8

7.8

Tube diameter - in.

SEER (Btuh/Watt)
EER (Btuh/Watt)

Refrigerant

Type
Charge Furnished

Electric Heat Available - See page 8

Outdoor
Coil Fan

Indoor Coil

3/8

3/8

3/8

Number of rows

Fins per inch

14

14

14

(1) 3/4 npt

(1) 3/4 npt

(1) 3/4 npt

Drain Connection (no. and size) - in.

Expansion device type

Indoor Blower

Nominal Motor HP
Wheel nominal diameter x width - in.

Filters

Balanced Port Thermostatic Expansion Valve, removeable power head


.5
10 x 10

Type

.75

10 x 10

11 x 10

Disposable

Number and size - in.


Electrical Characteristics - 60 Hz

.5

(4) 16 x 20 x 2
208/230V
1 phase

208/230V
1 phase

208/230V
1 phase

208/230V,
460V & 575V
3 phase

208/230V,
460V & 575V
3 phase

208/230V,
460V & 575V
3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Certified in accordance with the USE certification program, which is based on AHRI Standard 210/240; 95F outdoor air temperature and 80F db/67F wb
enteringevaporator air; minimum external duct static pressure.
2
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 11

SPECIFICATIONS - BELT DRIVE BLOWER


General Data

Nominal Tonnage
Model No.
Efficiency Type
Cooling
Gross Cooling Capacity - Btuh
Net Cooling Capacity - Btuh
Performance
AHRI Rated Air Flow - cfm
4
Sound Rating Number (dB)
Total Unit Power - kW
SEER (Btuh/Watt)
3
IEER (Btuh/Watt)
EER (Btuh/Watt)
Refrigerant
Type
Charge Furnished
Electric Heat Available - See page 8
Compressor Type (one per unit)
Outdoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins / inch
Outdoor
Motor HP
Motor rpm
Coil Fan
Total motor watts
Diameter - in. / No. of blades
Total air volume - cfm
Indoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins per inch
Drain Connection (no.and size) - in.
Expansion device type
5
Indoor
Nominal Motor HP
Maximum Usable Motor HP
Blower & Drive
Selection
Available Drive Kits

3 - 7.5 TON

3 Ton
4 Ton
5 Ton
6 Ton
7.5 Ton
KCA036S4B
KCA048S4B
KCA060S4B
KCA072S4B KCA090S4B
Standard
Standard
Standard
Standard
Standard
37,500
50,000
61,800
72,800
92,000
1
1
1
2
2
36,000
48,000
59,000
70,000
90,000
1200
1600
1800
2100
2500
75
75
82
82
79
3.4
4.4
5.3
6.3
8.2
1
1
1
13.0
13.0
13.0
----------11.4
11.4
1
1
1
2
2
10.7
11
11.2
11.2
11.2
R-410A
R-410A
R-410A
R-410A
R-410A
8 lbs. 5 oz.
8 lbs. 10 oz.
11 lbs. 0 oz.
14 lbs. 12 oz.
17 lbs. 0 oz.
7.5, 15 kW
7.5, 15 kW
7.5, 15, 22.5 kW
7.5, 15, 22.5, 30 kW
Scroll
Scroll
Scroll
Scroll
Scroll
15.6
15.6
15.6
19.3
28.0
3/8
3/8
3/8
3/8
3/8
1
1.5
2
2
2
20
20
20
20
20
1/4
1/4
1/3
1/3
1/3
825
825
1075
1075
1075
250
250
370
405
350
24 - 3
24 - 3
24 - 3
24 - 3
24 - 4
3700
3500
4300
4800
4900
7.8
7.8
7.8
9.7
9.7
3/8
3/8
3/8
3/8
3/8
3
3
4
4
4
14
14
14
14
14
(1) 3/4 NPT
(1) 3/4 NPT
(1) 3/4 NPT
(1) 3/4 NPT
(1) 3/4 NPT
Balanced Port Thermostatic Expansion Valve, removeable power head
1.5 hp, 6 2 hp
1.5 hp, 6 2 hp
1.5 hp, 6 2 hp
1.5 hp, 2 hp
1 hp
1.7 hp, 2.3 hp 1.7 hp, 2.3 hp 1.7 hp, 2.3 hp 1.7 hp, 2.3 hp
1.15 hp

A01
A02
A03
A04
AA01
673 - 1010 rpm 745 - 1117 rpm 833 - 1250 rpm 968 - 1340 rpm 522 - 784 rpm
A05
A06
A07
A08
897 - 1346 rpm 1071 - 1429 rpm 1212 - 1548 rpm 1193 - 1591 rpm
Nominal Motor HP
--------2 hp
Maximum Usable Motor HP
--------2.3 hp
Available Drive Kits
--------AA02
632 - 875 rpm
AA03
798 - 1105 rpm
--------3 hp
--------3.45 hp
AA04
--------921 - 1228 rpm
Wheel nominal diameter x width - in.
10 x 10
10 x 10
10 x 10
10 x 10
15 x 9
Filters
Type
Disposable
Disposable
Number and size - in.
(4) 16 x 20 x 2
(4) 20 x 20 x 2
Electrical Characteristics - 60 Hz
208/230V
208/230V,
208/230V
208/230V,
208/230V,
1 phase
1 phase
1 phase
460V & 575V 460V & 575V
3 phase
3 phase
208/230V,
208/230V
208/230V, 460V
460V & 575V 460V & 575V
& 575V
3 phase
3 phase
3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Certified in accordance with the USE certification program, which is based on AHRI Standard 210/240; 95F outdoor air temperature and 80F db/67F wb entering
evaporator air; minimum external duct static pressure.
2
Certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360; 95F outdoor air temperature and 80F db/67F wb entering
evaporator air; minimum external duct static pressure.
3
Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.
4
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
5
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors
furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp output. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
6
2 hp blower motor is not available for 208/230V-1ph applications.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 12

RATINGS
NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

2 TON STANDARD EFFICIENCY KCA024S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
640
23.2
1.39 0.72 0.86 0.99 22.0
1.59
0.74 0.88 1.00 20.8
1.82 0.75 0.91 1.00 19.5
2.07
0.78 0.94 1.00
63F
800
24.2
1.39 0.78 0.94 1.00 23.0
1.59
0.80 0.97 1.00 21.8
1.82 0.82 0.99 1.00 20.5
2.08
0.85 1.00 1.00
960
25.1
1.39 0.84 1.00 1.00 24.0
1.60
0.86 1.00 1.00 22.8
1.83 0.89 1.00 1.00 21.5
2.08
0.93 1.00 1.00
640
24.8
1.39 0.56 0.70 0.82 23.6
1.60
0.57 0.71 0.85 22.3
1.82 0.58 0.73 0.87 20.8
2.08
0.60 0.75 0.90
67F
800
25.8
1.39 0.60 0.75 0.90 24.4
1.60
0.61 0.77 0.93 23.0
1.83 0.63 0.80 0.96 21.5
2.09
0.64 0.83 1.00
960
26.4
1.40 0.63 0.81 0.98 25.0
1.60
0.65 0.84 1.00 23.5
1.83 0.66 0.87 1.00 22.0
2.09
0.69 0.90 1.00
640
26.6
1.40 0.42 0.55 0.67 25.3
1.60
0.43 0.56 0.68 23.9
1.84 0.43 0.56 0.70 22.3
2.09
0.43 0.58 0.73
71F
800
27.5
1.40 0.44 0.59 0.73 26.1
1.61
0.44 0.60 0.75 24.6
1.84 0.45 0.61 0.78 23.0
2.10
0.45 0.63 0.80
960
28.2
1.40 0.45 0.62 0.79 26.7
1.61
0.46 0.64 0.82 25.1
1.85 0.46 0.66 0.85 23.4
2.11
0.47 0.68 0.88

2.5 TON STANDARD EFFICIENCY KCA030S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
800
28.3
1.77 0.72 0.86 1.00 26.9
2.02
0.73 0.88 1.00 25.5
2.29 0.75 0.90 1.00 23.9
2.62
0.77 0.94 1.00
63F
1000
29.5
1.78 0.78 0.94 1.00 28.1
2.02
0.79 0.97 1.00 26.6
2.30 0.82 0.99 1.00 25.1
2.63
0.85 1.00 1.00
1200
30.5
1.79 0.84 1.00 1.00 29.3
2.03
0.86 1.00 1.00 27.9
2.31 0.89 1.00 1.00 26.3
2.62
0.92 1.00 1.00
800
30.2
1.78 0.56 0.69 0.82 28.8
2.03
0.57 0.71 0.84 27.2
2.30 0.58 0.73 0.87 25.5
2.63
0.59 0.75 0.91
67F
1000
31.3
1.79 0.59 0.75 0.91 29.8
2.03
0.60 0.77 0.93 28.1
2.31 0.62 0.80 0.96 26.3
2.63
0.63 0.82 1.00
1200
32.1
1.80 0.63 0.81 0.98 30.5
2.04
0.64 0.83 1.00 28.8
2.32 0.66 0.86 1.00 26.9
2.64
0.68 0.90 1.00
800
32.4
1.80 0.42 0.54 0.66 30.8
2.04
0.42 0.55 0.68 29.2
2.32 0.43 0.56 0.70 27.3
2.64
0.43 0.58 0.72
71F
1000
33.4
1.81 0.43 0.58 0.72 31.8
2.05
0.44 0.59 0.74 30.0
2.33 0.44 0.61 0.77 28.1
2.64
0.45 0.63 0.80
1200
34.2
1.82 0.44 0.62 0.79 32.4
2.06
0.45 0.63 0.81 30.6
2.33 0.46 0.65 0.84 28.6
2.65
0.47 0.67 0.88

3 TON STANDARD EFFICIENCY KCA036S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
960
35.6
2.33 0.72 0.85 0.98 34.0
2.65
0.73 0.87 0.99 32.2
3.01 0.75 0.89 1.00 30.3
3.44
0.77 0.92 1.00
63F
1200
37.0
2.34 0.77 0.93 1.00 35.4
2.66
0.79 0.95 1.00 33.5
3.02 0.81 0.98 1.00 31.6
3.45
0.84 1.00 1.00
1440
38.3
2.36 0.83 0.99 1.00 36.6
2.67
0.85 1.00 1.00 35.0
3.04 0.87 1.00 1.00 33.2
3.46
0.90 1.00 1.00
960
38.0
2.35 0.56 0.69 0.82 36.3
2.67
0.57 0.71 0.84 34.4
3.03 0.58 0.72 0.86 32.3
3.46
0.59 0.74 0.89
67F
1200
39.3
2.37 0.60 0.75 0.89 37.5
2.69
0.61 0.77 0.92 35.5
3.05 0.62 0.79 0.94 33.4
3.48
0.63 0.81 0.97
1440
40.3
2.38 0.63 0.80 0.96 38.4
2.70
0.64 0.83 0.98 36.3
3.06 0.66 0.85 1.00 34.1
3.49
0.68 0.88 1.00
960
40.6
2.38 0.42 0.54 0.67 38.7
2.70
0.43 0.55 0.68 36.8
3.07 0.43 0.56 0.70 34.6
3.49
0.43 0.58 0.72
71F
1200
41.9
2.40 0.43 0.58 0.72 39.9
2.72
0.44 0.59 0.74 37.8
3.08 0.44 0.61 0.76 35.6
3.51
0.45 0.62 0.79
1440
42.8
2.41 0.45 0.62 0.78 40.7
2.73
0.45 0.63 0.80 38.6
3.10 0.46 0.65 0.83 36.2
3.52
0.47 0.67 0.86

4 TON STANDARD EFFICIENCY KCA048S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
1280
47.9
3.05 0.71 0.85 0.98 45.6
3.47
0.72 0.87 1.00 43.2
3.94 0.74 0.90 1.00 40.6
4.48
0.76 0.93 1.00
63F
1600
49.7
3.07 0.76 0.93 1.00 47.3
3.49
0.78 0.95 1.00 44.9
3.96 0.80 0.98 1.00 42.4
4.50
0.83 1.00 1.00
1920
51.3
3.08 0.82 0.99 1.00 49.1
3.51
0.84 1.00 1.00 46.7
3.98 0.87 1.00 1.00 44.2
4.53
0.90 1.00 1.00
1280
50.9
3.07 0.55 0.68 0.81 48.4
3.51
0.56 0.70 0.83 45.8
3.98 0.57 0.71 0.86 43.1
4.51
0.58 0.73 0.89
67F
1600
52.6
3.09 0.58 0.74 0.89 50.0
3.52
0.60 0.76 0.92 47.2
4.00 0.61 0.78 0.95 44.3
4.53
0.63 0.81 0.98
1920
53.8
3.09 0.62 0.80 0.97 51.0
3.53
0.63 0.82 0.99 48.2
4.01 0.65 0.85 1.00 45.3
4.55
0.67 0.88 1.00
1280
54.3
3.09 0.41 0.54 0.66 51.6
3.54
0.42 0.55 0.67 48.8
4.02 0.42 0.56 0.69 45.9
4.56
0.43 0.57 0.71
71F
1600
56.0
3.11 0.43 0.57 0.71 53.1
3.55
0.43 0.58 0.73 50.2
4.04 0.44 0.60 0.76 47.1
4.58
0.44 0.61 0.79
1920
57.0
3.11 0.44 0.61 0.77 54.1
3.57
0.44 0.62 0.80 51.0
4.05 0.45 0.64 0.83 47.8
4.59
0.46 0.66 0.86

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 13

RATINGS
NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

5 TON STANDARD EFFICIENCY KCA060S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
1600
59.2
3.53 0.67 0.83 0.99 56.4
4.01
0.68 0.86 1.00 53.4
4.56 0.70 0.89 1.00 50.1
5.2
0.72 0.93 1.00
63F
2000
61.5
3.56 0.73 0.93 1.00 58.7
4.04
0.75 0.96 1.00 55.6
4.59 0.78 0.99 1.00 52.6
5.2
0.82 1.00 1.00
2400
63.8
3.58 0.80 1.00 1.00 61.1
4.06
0.83 1.00 1.00 58.1
4.62 0.86 1.00 1.00 54.8
5.3
0.91 1.00 1.00
1600
63.0
3.58 0.52 0.65 0.78 59.9
4.05
0.53 0.66 0.81 56.6
4.60 0.54 0.68 0.85 53.1
5.2
0.55 0.70 0.89
67F
2000
65.0
3.60 0.55 0.70 0.89 61.8
4.08
0.57 0.72 0.93 58.3
4.63 0.58 0.75 0.96 54.5
5.3
0.60 0.79 1.00
2400
66.4
3.62 0.59 0.77 0.98 63.1
4.10
0.60 0.80 1.00 59.5
4.65 0.62 0.84 1.00 55.7
5.3
0.64 0.88 1.00
1600
67.1
3.63 0.39 0.51 0.62 63.8
4.11
0.39 0.52 0.64 60.3
4.66 0.40 0.53 0.66 56.5
5.3
0.40 0.54 0.68
71F
2000
69.0
3.65 0.40 0.54 0.68 65.5
4.13
0.41 0.56 0.70 61.8
4.68 0.41 0.57 0.72 57.8
5.3
0.42 0.59 0.76
2400
70.3
3.67 0.42 0.58 0.75 66.7
4.15
0.42 0.59 0.78 62.9
4.70 0.43 0.61 0.81 58.8
5.3
0.44 0.63 0.86

6 TON STANDARD EFFICIENCY KCA072S4 (1ST STAGE)

Outdoor Air Temperature Entering Outdoor Coil


Entering
85F
95F
105F
115F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
1920
68.9
4.60 0.65 0.81 0.99 65.8
5.12
0.67 0.84 1.00 62.4
5.71 0.68 0.87 1.00 58.7
6.39
0.70 0.91 1.00
63F
2400
71.8
4.61 0.71 0.92 1.00 68.7
5.13
0.73 0.95 1.00 65.3
5.73 0.76 0.98 1.00 61.8
6.40
0.79 1.00 1.00
2880
74.6
4.62 0.78 1.00 1.00 71.7
5.14
0.81 1.00 1.00 68.5
5.73 0.84 1.00 1.00 65.0
6.41
0.88 1.00 1.00
1920
73.6
4.62 0.51 0.63 0.77 70.4
5.14
0.52 0.64 0.79 66.8
5.73 0.53 0.66 0.82 62.8
6.41
0.54 0.68 0.86
67F
2400
76.3
4.62 0.54 0.68 0.87 72.8
5.15
0.55 0.70 0.90 69.1
5.75 0.56 0.73 0.94 64.9
6.43
0.58 0.76 0.98
2880
78.3
4.63 0.57 0.75 0.97 74.7
5.16
0.58 0.78 0.99 70.8
5.76 0.60 0.81 1.00 66.6
6.44
0.62 0.85 1.00
1920
79.0
4.63 0.38 0.49 0.61 75.5
5.16
0.39 0.50 0.62 71.7
5.76 0.39 0.51 0.63 67.6
6.44
0.39 0.52 0.65
71F
2400
81.6
4.64 0.39 0.53 0.66 77.9
5.17
0.40 0.54 0.68 74.0
5.77 0.40 0.55 0.70 69.6
6.45
0.41 0.56 0.73
2880
83.4
4.65 0.41 0.56 0.72 79.6
5.18
0.41 0.57 0.75 75.5
5.78 0.42 0.59 0.78 71.0
6.47
0.42 0.61 0.82

7.5 TON STANDARD EFFICIENCY KCA090S4 (1ST STAGE)


Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
2400
63F
3000
3600
2400
67F
3000
3600
2400
71F
3000
3600

Total
Cool
Cap.
kBtuh
90.1
94.3
97.5
95.5
99.4
102.3
100.6
105.0
108.0

Outdoor Air Temperature Entering Outdoor Coil


85F
95F
105F
115F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F kBtuh
kW
75F 80F 85F
6.17 0.69 0.83 0.98 86.0
6.82
0.70 0.85 1.00 81.8
7.58 0.71 0.88 1.00 77.0
8.42
0.73 0.91 1.00
6.26 0.73 0.92 1.00 90.0
6.92
0.76 0.94 1.00 85.3
7.66 0.78 0.98 1.00 80.4
8.51
0.81 1.00 1.00
6.33 0.80 0.99 1.00 93.2
6.99
0.82 1.00 1.00 88.9
7.75 0.85 1.00 1.00 84.4
8.61
0.88 1.00 1.00
6.29 0.54 0.66 0.79 91.1
6.94
0.55 0.68 0.82 86.4
7.70 0.56 0.69 0.84 81.6
8.54
0.57 0.71 0.87
6.38 0.58 0.71 0.88 95.0
7.04
0.59 0.73 0.91 90.1
7.79 0.59 0.76 0.94 84.7
8.63
0.61 0.78 0.98
6.45 0.60 0.77 0.96 97.7
7.10
0.62 0.80 0.99 92.6
7.85 0.63 0.83 1.00 87.0
8.70
0.64 0.86 1.00
6.41 0.42 0.53 0.64 96.1
7.06
0.42 0.54 0.65 91.1
7.81 0.42 0.54 0.67 86.4
8.68
0.42 0.56 0.69
6.51 0.43 0.56 0.69 100.2 7.17
0.43 0.57 0.71 95.0
7.91 0.43 0.58 0.73 89.6
8.77
0.44 0.60 0.76
6.58 0.44 0.59 0.75 103.0 7.24
0.45 0.61 0.77 97.6
7.98 0.45 0.62 0.80 91.9
8.83
0.46 0.64 0.83

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 14

BLOWER DATA - DIRECT DRIVE

2 - 2.5 TON

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 25.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 25.
External Static
Pressure (in. w.g.)

Air Volume (cfm) at Various Blower Speeds


208 VOLTS
High

Medium

230 VOLTS
Low

High

Medium

2 and 2.5 Ton Standard Efficiency (Downflow)

Low

KCA024S and KCA030S

0.0

1199

928

838

1379

1085

877

0.1

1229

926

813

1409

1086

872

0.2

1206

928

782

1367

1094

850

0.3

1183

881

742

1350

1047

820

0.4

1159

843

686

1321

1009

783

0.5

1136

812

643

1282

981

762

0.6

1103

766

569

1242

921

705

0.7

1046

728

496

1195

888

625

0.8

953

648

432

1134

792

583

0.9

909

584

335

1037

738

492

1.0

783

465

247

926

592

411

2 and 2.5 Ton Standard Efficiency (Horizontal)

KCA024S and KCA030S

0.0

1152

909

801

1325

1063

838

0.1

1152

893

770

1321

1048

826

0.2

1136

866

734

1288

1021

798

0.3

1104

826

697

1260

982

771

0.4

1072

787

643

1222

942

734

0.5

1041

747

589

1175

903

698

0.6

1009

707

534

1137

850

662

0.7

946

654

467

1081

797

588

0.8

861

588

396

1024

718

535

0.9

798

508

319

911

642

468

1.0

715

443

237

846

564

394

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 15

BLOWER DATA - DIRECT DRIVE

3 - 4 TON

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 25.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 25.
External Static
Pressure (in. w.g.)

Air Volume (cfm) at Various Blower Speeds


208 VOLTS
High

Medium

230 VOLTS

460/575 VOLTS

Low

High

Medium

Low

High

3 and 4 Ton Standard Efficiency (Downflow)

Medium

Low

KCA036S and KCA048S

0.0

1938

1552

1119

2167

1772

1317

2136

1716

1212

0.1

1992

1586

1128

2167

1780

1315

2104

1728

1208

0.2

1915

1592

1137

2100

1792

1307

2052

1684

1197

0.3

1865

1536

1083

2043

1735

1266

1994

1647

1172

0.4

1813

1495

1033

1986

1678

1204

1918

1597

1134

0.5

1762

1444

976

1909

1621

1164

1861

1534

1096

0.6

1694

1391

899

1814

1535

1082

1765

1485

1059

0.7

1609

1331

817

1718

1478

1000

1689

1410

996

0.8

1471

1220

730

1603

1364

918

1613

1335

920

0.9

1368

1066

522

1488

1250

755

1498

1235

848

1.0

1108

869

402

1259

1021

640

1345

1036

763

3 and 4 Ton Standard Efficiency (Horizontal)

KCA036S and KCA048S

0.0

1862

1520

1070

2082

1736

1259

2085

1745

1247

0.1

1867

1530

1069

2031

1717

1246

2070

1744

1257

0.2

1804

1485

1067

1978

1672

1227

2016

1690

1225

0.3

1741

1440

1018

1907

1627

1190

1944

1643

1192

0.4

1677

1396

968

1837

1567

1128

1890

1596

1160

0.5

1614

1329

894

1749

1492

1066

1800

1533

1111

0.6

1550

1284

844

1660

1417

1016

1727

1455

1062

0.7

1455

1195

769

1554

1327

941

1655

1377

996

0.8

1329

1106

670

1448

1237

842

1511

1283

865

0.9

1202

927

496

1307

1087

718

1403

1190

784

1.0

1012

828

385

1025

973

613

1222

1002

670

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 16

BLOWER DATA - DIRECT DRIVE

5 TON

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 25.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 25.
External Static
Pressure (in. w.g.)

Air Volume (cfm) at Various Blower Speeds


208 VOLTS
High

230 VOLTS

460/575 VOLTS

Low

High

Low

High

Low

5 Ton Standard Efficiency (Downflow)

KCA060S

0.0

2121

1644

2324

1952

2160

1750

0.1

2162

1660

2315

1991

2128

1733

0.2

2100

1704

2285

1946

2092

1712

0.3

2078

1667

2230

1928

2054

1687

0.4

2056

1646

2185

1909

2005

1652

0.5

2014

1626

2154

1873

1972

1629

0.6

1953

1592

2049

1821

1907

1583

0.7

1913

1594

1966

1787

1858

1549

0.8

1830

1519

1936

1715

1810

1515

0.9

1774

1509

1763

1650

1744

1469

1.0

1601

1319

1649

1508

1679

1400

5 Ton Standard Efficiency (Horizontal)

KCA060S

0.0

2038

1611

2222

1875

2225

1885

0.1

2026

1601

2194

1866

2236

1895

0.2

1978

1590

2145

1833

2186

1853

0.3

1940

1563

2096

1800

2137

1818

0.4

1902

1537

2047

1766

2106

1799

0.5

1845

1497

1973

1716

2031

1763

0.6

1787

1470

1924

1666

2002

1711

0.7

1730

1431

1850

1616

1970

1677

0.8

1653

1378

1776

1549

1853

1607

0.9

1558

1312

1677

1449

1800

1586

1.0

1462

1257

1579

1377

1750

1418

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 17

BLOWER DATA - BELT DRIVE - KCA036


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
External Static - in. w.g.

Air
Volume
cfm

RPM

BHP

900

486

0.12

554

1000

508

0.15

1100

533

0.18

1200

560

1300
1400
1500

0.10

0.20
RPM

BHP

0.30

0.40

0.50

0.60

RPM

BHP

RPM

BHP

RPM

BHP

0.16

623

0.20

695

0.22

767

0.23

836

576

0.19

643

0.22

713

0.24

783

0.26

599

0.22

665

0.25

733

0.27

800

0.28

0.21

625

0.25

689

0.28

755

0.30

820

591

0.24

654

0.28

716

0.31

779

0.33

631

0.26

690

0.30

748

0.34

807

0.36

676

0.28

729

0.33

782

0.36

835

0.40

BHP

0.70

0.80

RPM

BHP

RPM

BHP

0.25

897

0.28

953

0.30

848

0.28

907

0.30

961

0.33

863

0.31

919

0.34

971

0.36

0.32

879

0.34

932

0.37

983

0.40

841

0.35

897

0.38

948

0.41

996

0.44

864

0.39

916

0.42

964

0.46

1011

0.49

887

0.43

935

0.47

981

0.50

1028

0.54

Field Furnished

RPM

Drive Kit A01

External Static - in. w.g.

Air
Volume
cfm

RPM

900

1004

1000
1100
1200

0.90
BHP

1.00

1.10

1.20

RPM

BHP

RPM

BHP

RPM

BHP

0.33

1055

0.35

1106

0.37

1152

0.40

1011

0.36

1062

0.38

1111

0.41

1157

1020

0.39

1070

0.41

1118

0.44

1163

1031

0.43

1079

0.45

1127

0.48

1300

1044

0.47

1091

0.49

1137

1400

1058

0.51

1105

0.54

1150

1500

1074

0.56

1120

0.59

1163

Kit A01

1.30
RPM

BHP

1.40

1.50

1.60

RPM

BHP

RPM

BHP

RPM

BHP

1305

0.52

Drive Kit A05


1193

0.43

1232

0.46

1269

0.49

0.43

1199

0.47

1238

0.50

1276

0.53

1311

0.56

0.47

1206

0.51

1245

0.54

1282

0.58

1318

0.61

1171

0.52

1213

0.55

1252

0.59

1289

0.62

1324

0.66

0.53

1181

0.56

1221

0.60

1259

0.64

1296

0.68

1330

0.71

0.57

1191

0.61

1231

0.65

1268

0.69

1303

0.73

1337

0.77

0.63

1203

0.67

1241

0.71

1277

0.75

1312

0.79

1345

0.82

HORIZONTAL
Air
Volume
cfm

External Static - in. w.g.


0.10
RPM

BHP

0.20
RPM

BHP

0.30
RPM

BHP

0.40
RPM

BHP

0.50
RPM

BHP

Field Furnished

0.60
RPM

BHP

0.70
RPM

BHP

0.80
RPM

BHP

Drive Kit A01

900

485

0.11

554

0.14

627

0.16

703

0.18

780

0.21

841

0.23

888

0.27

935

0.30

1000

509

0.13

578

0.16

649

0.19

722

0.21

796

0.23

854

0.26

900

0.29

947

0.33

1100

537

0.16

605

0.19

674

0.21

744

0.24

813

0.26

868

0.29

913

0.33

959

0.36

1200

567

0.19

633

0.22

700

0.24

768

0.27

833

0.30

884

0.33

928

0.37

974

0.40

1300

599

0.22

664

0.25

729

0.28

793

0.30

853

0.33

902

0.37

945

0.41

990

0.44

1400

634

0.26

697

0.29

758

0.31

819

0.34

875

0.38

921

0.42

964

0.46

1008

0.49

1500

669

0.30

730

0.33

789

0.36

846

0.39

897

0.42

941

0.47

983

0.51

1028

0.54

External Static - in. w.g.

Air
Volume
cfm

RPM

900

986

0.32

1039

0.35

1090

0.37

1137

0.40

1177

1000

997

0.35

1048

0.38

1098

0.41

1143

0.44

1100

1008

0.39

1059

0.41

1107

0.44

1150

0.47

1200

1022

0.43

1071

0.45

1117

0.48

1160

1300

1037

0.47

1085

0.50

1130

0.53

1171

1400

1054

0.52

1100

0.54

1144

0.58

1500

1073

0.57

1117

0.60

1159

0.64

0.90
BHP

1.00
RPM

BHP

1.10
RPM

BHP

1.20
RPM

BHP

1.30
BHP

1.40

1.50

1.60

RPM

BHP

RPM

BHP

RPM

BHP

0.43

1214

0.46

1248

0.49

1280

0.51

1184

0.47

1221

0.50

1255

0.53

1287

0.56

1191

0.51

1228

0.54

1263

0.57

1295

0.60

0.52

1200

0.55

1237

0.59

1271

0.62

1303

0.66

0.57

1210

0.60

1246

0.64

1280

0.68

1312

0.71

1183

0.62

1221

0.66

1256

0.70

1290

0.73

1321

0.77

1197

0.67

1234

0.71

1268

0.75

1301

0.79

1332

0.83

Kit A01

RPM

Kit A05

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 18

BLOWER DATA - BELT DRIVE - KCA048


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000

0.10
RPM BHP
560
591
631
675
718
756
787
815
843

0.21
0.24
0.26
0.28
0.31
0.34
0.40
0.46
0.53

0.20
0.30
RPM BHP RPM BHP
Field Furnished
625
0.25
689
0.28
654
0.28
716
0.31
690
0.30
748
0.34
729
0.33
782
0.36
766
0.35
814
0.40
799
0.39
843
0.44
828
0.45
870
0.50
855
0.51
897
0.57
884
0.59
925
0.64

Air
Volume
cfm

0.90
1.00
RPM BHP RPM BHP
Drive Kit A02
1200
1031 0.43 1079 0.45
1300
1044 0.47 1091 0.49
1400
1058 0.51 1105 0.54
1500
1074 0.56 1120 0.59
1600
1092 0.61 1137 0.65
1700
1112 0.67 1155 0.70
1800
1133 0.73 1174 0.77
1900
1156 0.80 1193 0.84
2000
1178 0.87 1213 0.92
HORIZONTAL
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000

0.10
RPM BHP
567
599
634
669
705
741
776
812
847

0.19
0.22
0.26
0.30
0.34
0.38
0.43
0.48
0.54

1.10
RPM BHP
1127
1137
1150
1163
1178
1193
1209
1226
1243

0.48
0.53
0.57
0.63
0.68
0.75
0.81
0.89
0.97

0.20
0.30
RPM BHP RPM BHP
Field Furnished
633
0.22
700
0.24
664
0.25
729
0.28
697
0.29
758
0.31
730
0.33
789
0.36
763
0.37
819
0.40
796
0.41
850
0.45
829
0.46
880
0.51
862
0.52
910
0.57
895
0.59
941
0.64

0.90
1.00
RPM BHP RPM BHP
Drive Kit A02
1022 0.43 1071 0.45
1037 0.47 1085 0.50
1054 0.52 1100 0.54
1073 0.57 1117 0.60
1093 0.62 1136 0.66
1114 0.68 1155 0.72
1136 0.75 1175 0.79
1159 0.82 1197 0.86
1183 0.90 1218 0.95

1.10
RPM BHP
1117
1130
1144
1159
1175
1192
1210
1229
1249

0.48
0.53
0.58
0.64
0.70
0.76
0.83
0.92
1.01

External Static - in. w.g.


0.40
0.50
RPM BHP RPM BHP

0.60
RPM BHP
Drive Kit A02
879
0.34
897
0.38
916
0.42
935
0.47
955
0.52
976
0.57
999
0.63
1024 0.69
1052 0.76

755
0.30
820
0.32
779
0.33
841
0.35
807
0.36
864
0.39
835
0.40
887
0.43
862
0.44
910
0.48
887
0.49
932
0.53
912
0.55
955
0.59
939
0.62
981
0.66
968
0.68 1009 0.72
External Static - in. w.g.
1.20
1.30
1.40
RPM BHP RPM BHP RPM BHP
Drive Kit A06
1171 0.52 1213 0.55 1252 0.59
1181 0.56 1221 0.60 1259 0.64
1191 0.61 1231 0.65 1268 0.69
1203 0.67 1241 0.71 1277 0.75
1216 0.72 1253 0.76 1288 0.80
1230 0.79 1265 0.83 1299 0.87
1244 0.85 1278 0.90 1311 0.94
1260 0.93 1293 0.97 1325 1.01
1275 1.02 1307 1.06 1339 1.10
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP

0.60
RPM BHP
Drive Kit A02
884
0.33
902
0.37
921
0.42
941
0.47
963
0.52
985
0.58
1009 0.64
1035 0.71
1062 0.78

768
0.27
833
0.30
793
0.30
853
0.33
819
0.34
875
0.38
846
0.39
897
0.42
873
0.43
921
0.48
900
0.49
945
0.53
927
0.55
970
0.60
955
0.62
996
0.66
984
0.69 1023 0.74
External Static - in. w.g.
1.20
1.30
1.40
RPM BHP RPM BHP RPM BHP
Drive Kit A06
1160 0.52 1200 0.55 1237 0.59
1171 0.57 1210 0.60 1246 0.64
1183 0.62 1221 0.66 1256 0.70
1197 0.67 1234 0.71 1268 0.75
1212 0.74 1247 0.78 1281 0.82
1227 0.80 1262 0.85 1295 0.89
1245 0.88 1278 0.92 1311 0.97
1263 0.97 1296 1.01 1328 1.06
1282 1.06 1314 1.11 1346 1.15

0.70
RPM BHP

0.80
RPM BHP

932
948
964
981
1000
1020
1043
1068
1095

983
996
1011
1028
1046
1066
1089
1113
1138

0.37
0.41
0.46
0.50
0.55
0.61
0.67
0.73
0.79

0.40
0.44
0.49
0.54
0.59
0.64
0.70
0.76
0.83

1.50
RPM BHP

1.60
RPM BHP

1289
1296
1303
1312
1321
1332
1343
1356
1370

1324
1330
1337
1345
1354
1364
1375
1388
1402

0.62
0.68
0.73
0.79
0.84
0.91
0.98
1.06
1.14

0.66
0.71
0.77
0.82
0.88
0.95
1.02
1.10
1.18

0.70
RPM BHP

0.80
RPM BHP

928
945
964
983
1004
1026
1050
1076
1103

974
990
1008
1028
1048
1070
1093
1118
1144

0.37
0.41
0.46
0.51
0.56
0.62
0.68
0.74
0.81

0.40
0.44
0.49
0.54
0.59
0.65
0.71
0.78
0.85

1.50
RPM BHP

1.60
RPM BHP

1271
1280
1290
1301
1313
1327
1342
1359
1377

1303
1312
1321
1332
1344
1358
1373
1390
1408

0.62
0.68
0.73
0.79
0.86
0.93
1.01
1.10
1.20

0.66
0.71
0.77
0.83
0.90
0.97
1.05
1.14
1.24

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 19

BLOWER DATA - BELT DRIVE - KCA060


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm

0.10
RPM BHP
738
773
803
831
861
893
927
963
999

0.90
RPM BHP

1600
1107
1700
1128
1800
1150
1900
1173
2000
1195
2100
1217
2200
1238
2300
1257
2400
1278
HORIZONTAL
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400

0.32
0.36
0.42
0.48
0.56
0.63
0.71
0.79
0.88

0.62
0.68
0.74
0.81
0.89
0.98
1.08
1.19
1.30

0.20
0.30
RPM BHP RPM BHP
Field Furnished
785
0.36
831
0.41
816
0.41
859
0.46
844
0.47
886
0.52
872
0.54
915
0.59
903
0.61
945
0.66
935
0.69
978
0.73
969
0.76 1011 0.81
1004 0.84 1045 0.89
1039 0.92 1078 0.97
1.00
1.10
RPM BHP RPM BHP
Drive Kit A03
1151 0.66 1190 0.70
1169 0.72 1206 0.76
1189 0.79 1223 0.83
1208 0.86 1240 0.91
1228 0.94 1257 0.99
1247 1.04 1275 1.09
1265 1.14 1293 1.19
1284 1.25 1313 1.30
1305 1.36 1334 1.40

0.10
0.20
RPM BHP RPM BHP
Field Furnished
752
0.30
798
0.35
785
0.35
827
0.40
813
0.42
855
0.47
841
0.49
883
0.54
871
0.56
914
0.62
903
0.64
946
0.70
937
0.73
981
0.78
973
0.81 1015 0.86
1010 0.91 1051 0.96
0.90
RPM BHP
1107
1129
1152
1176
1201
1225
1249
1273
1300

0.63
0.69
0.76
0.83
0.92
1.02
1.13
1.25
1.37

0.30
RPM BHP
844
871
898
926
957
990
1023
1056
1090

0.40
0.46
0.52
0.60
0.67
0.75
0.83
0.91
1.01

1.00
1.10
RPM BHP RPM BHP
Drive Kit A03
1149 0.67 1187 0.71
1169 0.73 1204 0.78
1190 0.80 1223 0.85
1212 0.89 1243 0.94
1234 0.98 1264 1.04
1256 1.08 1285 1.14
1279 1.19 1308 1.25
1303 1.31 1332 1.36
1329 1.43 1359 1.47

External Static - in. w.g.


0.40
0.50
RPM BHP RPM BHP
878
0.45
923
0.49
903
0.51
947
0.55
929
0.57
972
0.61
957
0.63 1000 0.67
988
0.70 1030 0.74
1019 0.78 1060 0.81
1052 0.85 1091 0.89
1084 0.93 1122 0.97
1115 1.02 1151 1.06
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1228
1242
1257
1273
1290
1306
1324
1344
1364

0.74
0.80
0.87
0.95
1.04
1.14
1.24
1.34
1.44

1264
1277
1291
1306
1321
1338
1355
1375
1395

0.78
0.84
0.91
0.99
1.08
1.18
1.28
1.38
1.48

0.60
RPM BHP
Drive Kit A03
969
0.53
991
0.58
1016 0.64
1043 0.71
1072 0.77
1101 0.85
1131 0.93
1159 1.02
1186 1.12

0.70
RPM BHP

0.80
RPM BHP

1014
1036
1060
1087
1115
1143
1170
1195
1219

1061
1082
1106
1131
1157
1182
1206
1228
1250

0.57
0.62
0.68
0.74
0.81
0.89
0.97
1.07
1.18

1.40
1.50
RPM BHP RPM BHP
Drive Kit A07
1298 0.82 1332 0.86
1310 0.88 1343 0.92
1324 0.95 1356 0.99
1338 1.03 1369 1.07
1353 1.12 1384 1.16
1369 1.22 1400 1.25
1387 1.31 1418 1.35
1406 1.41 1437 1.45
1427 1.51 1458 1.55

External Static - in. w.g.


0.40
0.50
0.60
0.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive Kit A03
889
0.45
933
0.49
975
0.53 1018 0.57
914
0.51
957
0.55
999
0.59 1042 0.63
940
0.57
983
0.62 1025 0.66 1067 0.69
969
0.65 1011 0.69 1052 0.72 1094 0.76
1000 0.72 1040 0.76 1081 0.79 1122 0.83
1031 0.79 1071 0.83 1110 0.87 1150 0.91
1063 0.87 1102 0.91 1140 0.96 1178 1.01
1095 0.96 1132 1.01 1170 1.06 1206 1.12
1127 1.06 1164 1.11 1200 1.18 1235 1.24
External Static - in. w.g.
1.20
1.30
1.40
1.50
RPM BHP RPM BHP RPM BHP RPM BHP
Drive Kit A07
1223 0.75 1258 0.79 1291 0.83 1323 0.87
1240 0.82 1274 0.86 1306 0.90 1338 0.95
1258 0.90 1291 0.94 1323 0.99 1354 1.03
1277 0.99 1309 1.03 1341 1.08 1372 1.12
1296 1.09 1329 1.13 1360 1.18 1391 1.22
1318 1.19 1349 1.24 1381 1.28 1412 1.32
1340 1.30 1372 1.34 1403 1.38 1434 1.42
1364 1.41 1396 1.45 1427 1.49 1458 1.53
1390 1.52 1422 1.56 1453 1.60 1484 1.64

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 20

0.59
0.65
0.71
0.78
0.85
0.93
1.02
1.13
1.24

1.60
RPM BHP
1364
1375
1388
1401
1416
1432
1450
1470
1492

0.90
0.96
1.03
1.12
1.20
1.29
1.39
1.48
1.58

0.80
RPM BHP
1062
1085
1110
1136
1162
1189
1215
1242
1269

0.60
0.66
0.72
0.79
0.87
0.96
1.07
1.19
1.31

1.60
RPM BHP
1354
1369
1385
1402
1422
1442
1465
1490
1516

0.91
0.99
1.07
1.16
1.26
1.36
1.46
1.57
1.67

BLOWER DATA - BELT DRIVE - KCA072 - DOWNFLOW


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.

Air
Volume
cfm

RPM

1900

826

0.36

859

0.41

894

0.45

928

0.50

964

0.56

1000

0.61

1036

2000

857

0.42

889

0.47

920

0.52

952

0.57

986

0.62

1020

0.68

1055

2100

878

0.49

909

0.54

940

0.59

973

0.64

1006

0.70

1041

0.75

1076

2200

897

0.55

929

0.61

961

0.66

994

0.72

1028

0.78

1063

0.83

1099

2300

918

0.62

950

0.68

983

0.74

1017

0.80

1052

0.86

1087

0.92

2400

941

0.70

974

0.77

1008

0.83

1042

0.90

1077

0.96

1111

2500

966

0.79

1000

0.86

1034

0.93

1068

1.00

1103

1.06

1137

2600

994

0.90

1028

0.97

1062

1.04

1096

1.10

1130

1.16

2700

1023

1.01

1057

1.08

1091

1.15

1125

1.22

1159

2800

1053

1.13

1088

1.21

1122

1.27

1155

1.33

1188

2900

1085

1.26

1119

1.33

1153

1.40

1186

1.45

1218

0.10
BHP

0.20
RPM

BHP

0.30
RPM

BHP

0.40
RPM

BHP

0.50
RPM

BHP

0.60
RPM

BHP

0.70
BHP

0.80
RPM

BHP

0.66

1072

0.70

0.73

1091

0.77

0.80

1112

0.85

0.89

1134

0.93

1122

0.97

1157

1.02

1.01

1146

1.06

1181

1.11

1.11

1171

1.16

1205

1.20

1164

1.21

1197

1.26

1231

1.30

1.27

1192

1.32

1225

1.37

1258

1.41

1.39

1221

1.43

1253

1.48

1286

1.53

1.51

1250

1.55

1281

1.61

1313

1.66

Field Furnished

RPM

Drive Kit A04

External Static - in. w.g.

Air
Volume
cfm

RPM

1900

1109

0.75

1146

0.79

1183

0.82

1221

0.86

1260

0.90

1294

0.94

1323

0.98

1349

1.02

2000

1128

0.82

1164

0.86

1201

0.89

1239

0.93

1276

0.97

1310

1.01

1336

1.06

1362

1.10

2100

1148

0.89

1185

0.93

1221

0.97

1258

1.01

1294

1.05

1325

1.09

1351

1.14

1376

1.19

2200

1170

0.97

1206

1.01

1242

1.05

1277

1.09

1311

1.14

1341

1.18

1365

1.23

1390

1.28

2300

1193

1.06

1228

1.09

1262

1.14

1295

1.19

1327

1.24

1355

1.29

1380

1.33

1406

1.37

2400

1216

1.15

1250

1.19

1282

1.24

1313

1.30

1343

1.36

1371

1.40

1396

1.44

1423

1.48

2500

1240

1.24

1273

1.29

1302

1.36

1331

1.42

1360

1.48

1388

1.52

1414

1.55

1441

1.58

2600

1265

1.34

1296

1.40

1324

1.47

1352

1.54

1381

1.60

1408

1.64

1434

1.67

1460

1.70

2700

1291

1.46

1321

1.52

1347

1.60

1374

1.67

1403

1.72

1429

1.76

1455

1.79

1481

1.82

2800

1317

1.58

1346

1.66

1372

1.74

1399

1.80

1426

1.85

1451

1.89

1477

1.92

1503

1.95

2900

1343

1.72

1371

1.80

1397

1.88

1424

1.95

1450

1.99

1475

2.02

1500

2.05

1526

2.08

0.90
BHP

1.00
RPM

BHP

1.10
RPM

BHP

1.20
RPM

BHP

1.30
RPM

BHP

1.40
RPM

BHP

1.50
RPM

BHP

Drive Kit A04

1.60
RPM

BHP

Kit A08

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 21

BLOWER DATA - BELT DRIVE - KCA072 - HORIZONTAL


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.

Air
Volume
cfm

RPM

1900

853

0.41

886

0.46

919

0.50

952

0.55

986

0.60

1021

0.64

2000

883

0.48

913

0.53

944

0.57

976

0.62

1009

0.67

1043

0.71

2100

906

0.56

936

0.60

967

0.65

999

0.70

1033

0.75

1067

2200

930

0.64

960

0.68

991

0.73

1024

0.78

1058

0.83

1092

2300

954

0.72

985

0.77

1017

0.82

1051

0.87

1085

0.92

2400

981

0.81

1013

0.86

1046

0.91

1079

0.96

1113

2500

1010

0.91

1042

0.96

1075

1.00

1109

1.05

1142

2600

1040

1.01

1073

1.05

1106

1.10

1139

1.14

2700

1072

1.10

1104

1.15

1137

1.20

1169

2800

1105

1.21

1137

1.25

1168

1.30

1200

2900

1138

1.32

1169

1.37

1200

1.42

1231

0.10
BHP

0.20
RPM

BHP

0.30
RPM

BHP

0.40
RPM

BHP

0.50
RPM

BHP

0.60
RPM

0.70
RPM

0.80

BHP

RPM

BHP

1056

0.69

1091

0.73

1078

0.76

1112

0.80

0.79

1101

0.84

1135

0.88

0.88

1126

0.92

1160

0.96

1119

0.96

1152

1.00

1186

1.04

1.00

1146

1.05

1180

1.09

1213

1.13

1.09

1175

1.14

1207

1.18

1239

1.23

1171

1.19

1203

1.23

1235

1.28

1266

1.33

1.24

1201

1.29

1232

1.34

1263

1.40

1293

1.46

1.35

1231

1.40

1261

1.46

1291

1.52

1321

1.59

1.47

1261

1.53

1291

1.60

1321

1.66

1350

1.73

Field Furnished

BHP

Drive Kit A04

External Static - in. w.g.

Air
Volume
cfm

RPM

1900

1126

0.77

2000

1148

2100

1170

2200

0.90
BHP

1.00
RPM

BHP

1.10
RPM

BHP

1.20
RPM

BHP

1.30
RPM

BHP

1.40
RPM

BHP

1.50
RPM

BHP

Drive Kit A04

1.60
RPM

BHP

Kit A08

1163

0.81

1200

0.85

1237

0.88

1273

0.92

1306

0.96

1339

1.00

1371

1.04

0.84

1183

0.88

1220

0.92

1257

0.96

1291

1.00

1323

1.04

1354

1.08

1385

1.12

0.92

1206

0.96

1242

1.00

1277

1.04

1310

1.08

1340

1.13

1371

1.17

1401

1.21

1195

1.00

1230

1.04

1265

1.08

1299

1.13

1330

1.18

1359

1.23

1388

1.27

1418

1.31

2300

1220

1.08

1254

1.13

1288

1.17

1320

1.23

1350

1.28

1378

1.34

1406

1.38

1435

1.42

2400

1245

1.18

1278

1.22

1311

1.28

1341

1.33

1370

1.40

1397

1.45

1425

1.50

1454

1.54

2500

1271

1.28

1303

1.33

1334

1.39

1363

1.45

1391

1.52

1418

1.57

1446

1.62

1474

1.66

2600

1297

1.39

1328

1.45

1357

1.52

1385

1.58

1412

1.64

1439

1.70

1467

1.74

1495

1.78

2700

1323

1.52

1353

1.58

1382

1.65

1409

1.72

1435

1.77

1462

1.82

1490

1.86

1517

1.90

2800

1351

1.65

1380

1.72

1407

1.78

1434

1.85

1460

1.90

1486

1.95

1513

1.99

1541

2.02

2900

1379

1.79

1407

1.86

1434

1.92

1460

1.98

1485

2.04

1511

2.08

1538

2.12

1565

2.15

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 22

BLOWER DATA - BELT DRIVE - KCA090 - DOWNFLOW


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
Drive Kit AA01
Drive Kit AA02
2400

553 0.65 585 0.71 617 0.78 649 0.85 680 0.91 711 0.98 740 1.04 769 1.10 796 1.15 821 1.21

2500

570 0.71 602 0.78 633 0.84 665 0.91 695 0.97 725 1.04 753 1.10 781 1.16 807 1.22 832 1.27

2600

588 0.77 619 0.84 650 0.91 680 0.97 710 1.04 739 1.10 767 1.16 793 1.22 818 1.28 842 1.33

2700

607 0.84 637 0.91 667 0.97 697 1.04 726 1.11 753 1.17 780 1.23 806 1.29 830 1.35 854 1.40

2800

626 0.91 655 0.97 684 1.04 713 1.11 741 1.18 768 1.24 794 1.30 819 1.36 842 1.42 866 1.47

2900

646 0.98 674 1.05 702 1.11 730 1.18 757 1.25 783 1.32 808 1.38 832 1.44 855 1.49 878 1.54

3000

666 1.06 693 1.12 721 1.19 747 1.26 774 1.33 799 1.40 823 1.46 846 1.52 868 1.57 891 1.62

3100

686 1.14 713 1.21 739 1.28 765 1.35 790 1.41 814 1.48 838 1.55 860 1.61 882 1.66 904 1.70

3200

707 1.22 732 1.29 758 1.36 783 1.43 807 1.50 830 1.57 853 1.64 874 1.70 896 1.75 918 1.79

3300

727 1.31 752 1.38 776 1.46 800 1.53 823 1.60 846 1.67 868 1.73 889 1.79 911 1.84 932 1.89

3400

747 1.41 771 1.48 794 1.55 817 1.63 840 1.70 862 1.77 883 1.83 904 1.89 925 1.94 947 1.98

3500

767 1.51 790 1.58 812 1.66 835 1.73 856 1.80 878 1.87 899 1.93 920 1.99 940 2.04 961 2.08

3600

786 1.61 808 1.69 830 1.77 852 1.84 873 1.91 894 1.98 915 2.04 935 2.09 955 2.14 975 2.19

External Static - in. w.g.


Air
0.90
1.00
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
Volume
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
cfm
Drive Kit AA02
Drive Kit AA03
2400

846 1.25 870 1.29 895 1.33 920 1.37 947 1.41 972 1.45 996 1.50 1018 1.55 1039 1.61 1059 1.67

2500

856 1.31 880 1.35 905 1.39 930 1.43 956 1.47 980 1.52 1003 1.57 1024 1.63 1044 1.69 1064 1.76

2600

866 1.38 891 1.42 915 1.46 940 1.50 965 1.54 988 1.59 1010 1.65 1031 1.71 1050 1.78 1069 1.84

2700

878 1.44 902 1.48 926 1.52 950 1.57 974 1.61 997 1.67 1018 1.73 1037 1.80 1056 1.87 1075 1.93

2800

889 1.51 913 1.55 937 1.59 961 1.64 984 1.69 1006 1.75 1026 1.82 1044 1.89 1063 1.96 1081 2.03

2900

902 1.58 925 1.63 949 1.67 972 1.72 994 1.78 1015 1.84 1034 1.91 1052 1.99 1069 2.06 1087 2.13

3000

914 1.66 938 1.71 961 1.75 983 1.81 1004 1.87 1024 1.94 1042 2.01 1059 2.09 1076 2.16 1093 2.23

3100

927 1.75 950 1.79 972 1.84 994 1.90 1014 1.96 1033 2.04 1050 2.11 1067 2.19 1083 2.27 1100 2.34

3200

941 1.84 963 1.88 984 1.94 1005 2.00 1024 2.07 1042 2.14 1059 2.23 1075 2.31 1091 2.39 1107 2.46

3300

954 1.93 976 1.98 996 2.04 1016 2.10 1035 2.18 1052 2.26 1067 2.35 1083 2.43 1098 2.51 1114 2.59

3400

968 2.03 989 2.08 1008 2.14 1027 2.22 1045 2.30 1061 2.38 1076 2.47 1091 2.57 1106 2.65 1121 2.73

3500

982 2.13 1001 2.19 1020 2.26 1038 2.33 1054 2.42 1070 2.51 1084 2.61 1099 2.71 1113 2.79 1128 2.87

3600

995 2.24 1014 2.30 1031 2.38 1048 2.46 1064 2.55 1079 2.65 1093 2.76 1107 2.86 1121 2.95 1136 3.03
Drive Kit - AA03

Drive Kit - AA04

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 23

BLOWER DATA - BELT DRIVE - KCA090 - HORIZONTAL


BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 25 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
Drive Kit AA01
Drive Kit AA02
2400

596 0.79 626 0.82 657 0.85 688 0.89 718 0.92 749 0.96 778 1.01 806 1.06 833 1.11 858 1.16

2500

616 0.85 645 0.88 676 0.91 706 0.95 736 0.99 765 1.03 794 1.08 821 1.13 847 1.18 871 1.23

2600

636 0.91 665 0.94 695 0.98 724 1.02 754 1.06 782 1.10 809 1.15 836 1.20 861 1.25 885 1.30

2700

657 0.97 685 1.01 714 1.04 743 1.08 771 1.13 799 1.17 826 1.22 851 1.27 875 1.32 899 1.37

2800

677 1.03 706 1.07 734 1.11 762 1.16 790 1.20 816 1.25 842 1.30 867 1.35 890 1.40 913 1.45

2900

698 1.10 726 1.14 754 1.19 781 1.23 808 1.28 834 1.33 859 1.38 883 1.43 906 1.48 928 1.54

3000

720 1.17 747 1.22 774 1.26 801 1.31 826 1.36 851 1.41 876 1.46 899 1.52 921 1.57 943 1.63

3100

741 1.25 768 1.30 794 1.35 820 1.40 845 1.45 869 1.50 893 1.56 915 1.61 937 1.67 959 1.73

3200

763 1.34 789 1.39 815 1.44 840 1.49 864 1.54 888 1.60 910 1.66 932 1.72 954 1.78 975 1.84

3300

785 1.43 811 1.48 836 1.53 860 1.59 883 1.65 906 1.71 928 1.77 950 1.83 970 1.90 991 1.96

3400

807 1.53 832 1.58 856 1.64 880 1.70 903 1.76 925 1.82 946 1.88 967 1.95 987 2.02 1007 2.09

3500

830 1.63 854 1.69 877 1.75 900 1.81 922 1.88 944 1.94 964 2.01 985 2.08 1004 2.15 1024 2.23

3600

852 1.74 876 1.81 898 1.87 921 1.94 942 2.01 963 2.07 983 2.15 1002 2.22 1022 2.29 1041 2.37

External Static - in. w.g.


Air
0.90
1.00
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
Drive Kit AA03
2400

883 1.21 907 1.25 931 1.30 955 1.35 979 1.40 1003 1.45 1027 1.51 1050 1.57 1072 1.63 1094 1.69

2500

895 1.28 919 1.32 942 1.37 966 1.42 990 1.48 1013 1.53 1036 1.59 1059 1.65 1081 1.71 1102 1.78

2600

908 1.35 931 1.40 955 1.45 978 1.50 1001 1.56 1024 1.62 1046 1.68 1068 1.74 1089 1.80 1110 1.87

2700

922 1.43 945 1.48 967 1.53 990 1.59 1013 1.65 1035 1.71 1056 1.77 1078 1.84 1099 1.90 1119 1.96

2800

936 1.51 958 1.56 980 1.62 1003 1.68 1025 1.74 1046 1.80 1067 1.87 1088 1.93 1109 2.00 1129 2.06

2900

950 1.60 972 1.66 994 1.72 1016 1.78 1037 1.84 1058 1.91 1079 1.97 1099 2.04 1119 2.11 1139 2.17

3000

965 1.69 986 1.76 1008 1.82 1029 1.88 1050 1.95 1070 2.02 1091 2.08 1110 2.15 1130 2.22 1149 2.28

3100

980 1.80 1001 1.86 1022 1.93 1043 2.00 1063 2.07 1083 2.13 1103 2.20 1122 2.27 1141 2.33 1160 2.40

3200

995 1.91 1016 1.98 1036 2.05 1057 2.12 1077 2.19 1096 2.26 1116 2.33 1134 2.39 1153 2.46 1171 2.52

3300

1011 2.03 1031 2.11 1051 2.18 1071 2.25 1091 2.32 1110 2.39 1129 2.45 1147 2.52 1165 2.59 1183 2.65

3400

1027 2.16 1047 2.24 1067 2.31 1086 2.38 1105 2.45 1124 2.52 1142 2.59 1160 2.66 1178 2.72 1196 2.78

3500

1043 2.30 1063 2.38 1082 2.45 1101 2.52 1120 2.59 1138 2.66 1156 2.73 1174 2.80 1191 2.86 1208 2.92

3600

1060 2.45 1079 2.52 1098 2.60 1117 2.67 1135 2.74 1153 2.81 1170 2.87 1188 2.94 1205 3.00 1222 3.06
Drive Kit AA04

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 24

BLOWER DATA
BELT DRIVE KIT SPECIFICATIONS
Blower Motor Choice (HP)
Model No.
Nominal
Maximum
Nominal
Maximum
036

1.5

1.7

2.3

048

1.5

1.7

2.3

060

1.5

1.7

2.3

072

1.5

1.7

2.3

1.15

---

---

2.3

---

---

3.45

---

---

090

Drive Kit No.

RPM Range

A01
A05
A02
A06
A03
A07
A04
A08
AA01
AA02
AA03
AA04

673 - 1010 rpm


897 - 1346 rpm
745 - 1117 rpm
1071 - 1429 rpm
833 - 1250 rpm
1212 - 1548 rpm
968 - 1340 rpm
1193 - 1591 rpm
522 - 784 rpm
632 - 875 rpm
798 - 1105 rpm
921 - 1228 rpm

NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of
motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.

POWER EXHAUST FANS PERFORMANCE


Return Air System
Static Pressure
in. w.g.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7

Low
1290
1045
805
580
390
245
155
145

208V
Medium
1300
1055
805
580
405
315
340
515

Air Volume Exhausted - cfm


T1PWRE10A
230V, 460V and 575V
208V
High Low
Medium High Low
Medium
1320 1300
1305
1295 3545
3915
1055 1040
1050
1055 2880
3215
815
805
810
810
2290
2665
600
595
590
585
1735
2175
400
405
400
410
1165
1660
215
240
255
300
530
1045
35
90
165
290
--250
----140
400
-----

T1PWRE10N
230V, 460V and 575V
High Low
Medium High
4230 3880
4135
4340
3580 3255
3550
3755
3055 2710
3010
3240
2605 2200
2500
2770
2175 1685
2010
2325
1710 1120
1510
1885
1160
470
990
1420
470
--430
915

OPTIONS / ACCESSORIES AIR RESISTANCE FOR 024-072 MODELS - in. w.g.


Air Volume
cfm

Economizer

800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000

0.04
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06

Electric Heat
0.01
0.03
0.06
0.09
0.12
0.15
0.18
0.20
0.22
0.24
0.26
0.28

036-048
0.01
0.02
0.03
0.04
0.05
0.06
0.08
0.09
0.10
0.11
0.13
0.14

Wet Indoor Coil


060
0.01
0.02
0.04
0.05
0.06
0.07
0.09
0.10
0.12
0.13
0.15
0.16

072
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.12

OPTIONS / ACCESSORIES AIR RESISTANCE FOR 090 MODELS - in. w.g.


Air Volume
cfm
2400
2600
2800
3000
3200
3400
3600

Economizer

Electric Heat

Wet Indoor Coil

0.05
0.06
0.06
0.06
0.06
0.06
0.06

0.22
0.24
0.26
0.28
0.30
0.31
0.32

0.08
0.09
0.10
0.11
0.12
0.14
0.15
Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 25

BLOWER DATA
CEILING DIFFUSERS AIR RESISTANCE (in. w.g.)
RTD9-65 StepDown Diffuser

RTD11-95 StepDown Diffuser

2 Ends
Open

1 Side &
2 Ends Open

All Ends &


Sides Open

FD9-65
Flush
Diffuser

800

0.15

0.13

0.11

0.11

---

---

---

---

1000

0.19

0.16

0.14

0.14

---

---

---

---

1200

0.25

0.20

0.17

0.17

---

---

---

---

1400

0.33

0.26

0.20

0.20

---

---

---

---

1600

0.43

0.32

0.20

0.24

---

---

---

---

1800

0.56

0.40

0.30

0.30

0.13

0.11

0.09

0.09

2000

0.73

0.50

0.36

0.36

0.15

0.13

0.11

0.10

2200

0.95

0.63

0.44

0.44

0.18

0.15

0.12

0.12

2400

---

----

---

---

0.21

0.18

0.15

0.14

2600

---

----

---

---

0.24

0.21

0.18

0.17

2800

---

----

---

---

0.27

0.24

0.21

0.20

3000

---

----

---

---

0.32

0.29

0.25

0.25

3200

---

----

---

---

0.41

0.37

0.32

0.31

3400

---

----

---

---

0.50

0.45

0.39

0.37

3600

---

----

---

---

0.61

0.54

0.48

0.44

Air Volume
cfm

CEILING DIFFUSER AIR THROW DATA


Air Volume - cfm

Effective Throw - ft.

Model No.

RTD9-65

FD9-65

800

10 - 17

14 - 18

1000

10 - 17

15 - 20

1200

11 - 18

16 - 22

1400

12 - 19

17 - 24

1600

12 - 20

18 - 25

1800

13 - 21

20 - 28

2000

14 - 23

21 - 29

2200

16 - 25

22 - 30

Model No.

RTD11-95

FD11-95

2600

24 - 29

19 - 24

2800

25 - 30

20 - 28

3000

27 - 33

21 - 29

3200

28 - 35

22 - 29

3400

30 - 37

22 - 30

3600

25 - 33

22 - 24

1 Effective throw based on terminal velocities of 75 ft. per minute.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 26

2 Ends
Open

1 Side &
2 Ends Open

All Ends &


Sides Open

FD11-95
Flush
Diffuser

ELECTRICAL/ELECTRIC HEAT DATA

2 - 2.5 TON

DIRECT DRIVE BLOWER


1

Voltage - 60hz

Compressor 1
Outdoor Fan
Motors (1)

KCA024S

KCA030S

208/230V - 1 Ph

208/230V - 1 Ph

Rated Load Amps

13.5

14.1

Locked Rotor Amps

58.3

73

Full Load Amps (total)

1.7

1.7

15 Amps

15 Amps

Horsepower

.25

.25

Service Outlet 115V GFI


Indoor Blower
Motor

Full Load Amps

1.8

1.8

Maximum
Overcurrent
Protection

Unit Only

30

35

Minimum
Circuit
Ampacity

Unit Only

21

22

ELECTRIC HEAT DATA


Electric Heat Voltage

208

240

208

240

Maximum
Overcurrent
Protection

Unit +
Electric Heat

7.5 kW

40

45

40

45

10 kW

50

60

50

60

Minimum
Circuit
Ampacity

Unit +
Electric Heat

7.5 kW

37

42

37

42

10 kW

48

55

48

55

Standard Access - 0-10 kW

20W15

20W15

20W15

20W15

Hinged Access - 0-10 kW

20W21

20W21

20W21

20W21

28W69

28W69

17W94

17W94

ELECTRICAL ACCESSORIES
Disconnect
Kit
Fuse Block
1
2
3

Extremes of operating range are plus and minus 10% of line voltage.
HACR type breaker or fuse.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 27

ELECTRICAL/ELECTRIC HEAT DATA

3 TON

KCA036S
1

Voltage - 60hz

Compressor 1

208/230V - 1 Ph

208/230V - 3 Ph

460V - 3 Ph

575V - 3 Ph

16.7

10.4

5.8

3.8

Rated Load Amps


Locked Rotor Amps

79

73

38

36.5

Outdoor Fan
Motors (1)

Full Load Amps (total)

1.7

1.7

1.1

0.7

Power Exhaust
(1) 0.75 HP

Full Load Amps (total)

2.2

1.5

15 Amps

15 Amps

15 Amps

15 Amps

Service Outlet 115V GFI


Indoor Blower
Motor
Maximum
Overcurrent
Protection

Horsepower

.5

1.5

.5

1.5

.5

1.5

.5

1.5

Full Load Amps

3.9

11

3.9

6.6

7.5

3.4

2.4 2.7

Unit Only

40

50

25

30

30

15

15

15

15

15

15

with (1) 0.75 HP


Power Exhaust

45

50

30

35

35

15

15

15

15

15

15

Unit Only

27

34

19

22

23

11

12

12

with (1) 0.75 HP


Power Exhaust

32

39

24

27

28

13

14

14

10

10

Minimum
Circuit
Ampacity
3

ELECTRIC HEAT DATA


Electric Heat Voltage 208 240 208 240 208 240 208 240 208 240 480 480 480 600 600 600
Maximum
Overcurrent
Protection

Unit + 7.5 kW
Electric Heat 15 kW

40

45

50

60

25

30

30

35

30

35

15

20

20

15

15

15

80

90

90

100

45

50

50

60

50

60

30

30

30

25

25

25

Minimum
Circuit
Ampacity

Unit + 7.5 kW
Electric Heat 15 kW

39

44

48

53

25

28

28

31

29

32

14

16

16

12

13

13

73

83

82

92

44

50

48

54

49

55

27

27

27

21

22

22

Maximum
Overcurrent
Protection

Unit + 7.5 kW
Electric Heat 15 kW
and (1) 0.75 HP
Power Exhaust

45

60

60

60

35

35

35

40

40

40

20

20

20

15

15

15

80

90

90

100

60

60

60

60

60

70

30

30

30

25

25

25

Minimum
Circuit
Ampacity

Unit + 7.5 kW
Electric Heat 15 kW
and (1) 0.75 HP
Power Exhaust

45

51

54

60

31

34

35

38

36

39

17

18

19

14

14

15

79

90

88

99

51

57

54

60

55

61

28

30

30

23

23

24

ELECTRICAL ACCESSORIES
Disconnect
Kit

Fuse Block

Standard Access - 0-7.5 kW

20W15

20W15

20W15

20W15

20W15

20W15

20W15

15 kW

20W16

20W16

20W15

20W15

20W15

20W15

20W15

Hinged Access - 0-7.5 kW

20W21

20W21

20W21

20W21

20W21

20W21

20W21

15 kW

20W22

20W22

20W21

20W21

20W21

20W21

20W21

Unit Only

17W95

17W97

18W00

18W01

18W01

18W06

18W06

Unit + Power Exhaust

17W96

17W97

18W01

18W02

18W02

18W06

18W06

Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 28

ELECTRICAL/ELECTRIC HEAT DATA

4 TON

KCA048S
1

Voltage - 60hz

Compressor 1

208/230V - 1 Ph

208/230V - 3 Ph

460V - 3 Ph

575V - 3 Ph

Rated Load Amps

21.8

13.7

6.2

4.8

Locked Rotor Amps

117

83.1

41

33

Outdoor Fan
Motors (1)

Full Load Amps (total)

1.7

1.7

1.1

0.7

Power Exhaust
(1) 0.75 HP

Full Load Amps (total)

2.2

1.5

15 Amps

15 Amps

15 Amps

15 Amps

Service Outlet 115V GFI


Indoor Blower
Motor
Maximum
Overcurrent
Protection

Horsepower

.5

1.5

.5

1.5

.5

1.5

.5

1.5

Full Load Amps

3.9

11

3.9

6.6

7.5

3.4

2.4 2.7

Unit Only

50

60

35

35

40

15

15

15

15

15

15

with (1) 0.75 HP


Power Exhaust

50

60

40

40

45

15

20

20

15

15

15

Unit Only

33

40

23

26

27

11

12

13

10

10

with (1) 0.75 HP


Power Exhaust

38

45

28

31

32

14

15

15

11

11

11

Minimum
Circuit
Ampacity
3

ELECTRIC HEAT DATA


Electric Heat Voltage

208 240 208 240 208 240 208 240 208 240 480 480 480 600 600 600

Maximum
Overcurrent
Protection

Unit +
Electric Heat

7.5 kW

50

50

60

35

35

35

35

40

40

15

20

20

15

15

15

15 kW

80

90

90 100 45

50

50

60

50

60

30

30

30

25

25

25

Minimum
Circuit
Ampacity

Unit +
Electric Heat

7.5 kW

39

44

48

53

25

28

28

31

29

32

14

16

16

12

13

13

15 kW

73

83

82

92

44

50

48

54

49

55

26

27

27

21

22

22

Maximum
Overcurrent
Protection

Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust

7.5 kW

50

60

60

60

40

40

40

40

45

45

20

20

20

15

15

15

15 kW

80

90

90 100 60

60

60

60

60

70

30

30

30

25

25

25

Minimum
Circuit
Ampacity

Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust

7.5 kW

45

51

54

60

31

34

35

38

36

39

17

18

19

14

14

15

15 kW

79

90

88

99

51

57

54

60

55

61

28

30

30

23

23

24

60

ELECTRICAL ACCESSORIES
Disconnect
Kit

Fuse Block

Standard Access - 0-7.5 kW

20W15

20W15

20W15

20W15

20W15

20W15

20W15

15 kW

20W16

20W16

20W15

20W15

20W15

20W15

20W15

Hinged Access - 0-7.5 kW

20W21

20W21

20W21

20W21

20W21

20W21

20W21

15 kW

20W22

20W22

20W21

20W21

20W21

20W21

20W21

Unit Only

17W97

17W98

18W02

18W02

18W03

18W06

18W06

Unit + Power Exhaust

17W97

17W98

18W03

18W03

18W04 18W06 (.5 hp)

18W06

18W07 (1.5-2 hp)


Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 29

ELECTRICAL/ELECTRIC HEAT DATA

5 TON

KCA060S
1

Voltage - 60hz

Compressor 1

208/230V - 1 Ph

208/230V - 3 Ph

460V - 3 Ph

575V - 3 Ph

Rated Load Amps

26.4

16

7.8

5.7

Locked Rotor Amps

134

110

52

38.9

Outdoor Fan
Motors (1)

Full Load Amps (total)

2.4

2.4

1.3

Power
Exhaust
(1) 0.75 HP

Full Load Amps (total)

2.2

1.5

Service Outlet 115V GFI


Indoor
Blower
Motor
Maximum
Overcurrent
Protection

15 Amps

15 Amps

1.5

.75

1.5

Full Load Amps

4.9

11

4.9

6.6

7.5

2.5

3.4 2.5 2.4 2.7

Unit Only

60

70

40

45

45

20

20

20

15

15

15

with (1) 0.75 HP


Power Exhaust

70

70

45

50

50

20

20

20

15

15

15

Unit Only

41

47

28

29

30

14

15

15

11

11

11

with (1) 0.75 HP


Power Exhaust

46

52

33

34

35

16

17

17

13

13

13

.75 1.5

15 Amps

.75

Minimum
Circuit
Ampacity

15 Amps

Horsepower

.75 1.5

ELECTRIC HEAT DATA


Electric Heat Voltage 208 240 208 240 208 240 208 240 208 240 480 480 480 600 600 600
Maximum
Overcurrent
Protection

Unit +
Electric Heat

Minimum
Circuit
Ampacity

Unit +
Electric Heat

7.5 kW
15 kW

70

70

40

40

45

45

45

45

20

20

20

15

15

15

80

90

90

100

50

60

50

60

50

60

30

30

30

25

25

25

70

80

70

80

70

80

40

40

40

35

35

35

7.5 kW

41

46

48

53

28

29

29

31

30

32

15

16

16

13

13

13

15 kW

74

85

82

92

46

52

48

54

49

55

26

27

27

22

22

22

108 124 116 131

65

74

67

76

68

77

37

38

39

31

31

31

70

70

70

70

45

45

50

50

50

50

20

20

20

15

15

15

90

100

90

100

60

60

60

60

60

70

30

30

30

25

25

25

125 150 125 150

80

90

80

90

80

90

40

45

45

35

35

35

47

52

54

60

33

35

35

38

36

39

18

18

19

15

14

15

81

91

88

99

52

58

54

60

55

61

29

30

30

24

23

24

114 130 122 138

72

81

74

83

75

84

40

41

41

33

32

33

22.5 kW
Unit + 7.5 kW
Electric Heat
15 kW
and (1) 0.75 HP
Power Exhaust 22.5 kW

Minimum
Circuit
Ampacity

Unit + 7.5 kW
Electric Heat
15 kW
and (1) 0.75 HP
Power Exhaust 22.5 kW

60

110 125 125 150

22.5 kW

Maximum
Overcurrent
Protection
2

60

ELECTRICAL ACCESSORIES
Disconnect
Kit

Fuse Block
1
2
3

Standard Access - 0-7.5 kW

20W15

20W15

20W15

20W15

20W15

20W15

20W15

15-22.5 kW

20W16

20W16

20W15

20W15

20W15

20W15

20W15

Hinged Access - 0-7.5 kW

20W21

20W21

20W21

20W21

20W21

20W21

20W21

15-22.5 kW

20W22

20W22

20W21

20W21

20W21

20W21

20W21

Unit Only

17W98

17W99

18W03

18W04

18W04

18W07

18W06

Unit + Power Exhaust

17W99

17W99

18W04

18W05

18W05

18W07

18W06

Extremes of operating range are plus and minus 10% of line voltage.
HACR type breaker or fuse.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 30

ELECTRICAL/ELECTRIC HEAT DATA

6 TON

KCA072S
1

Voltage - 60hz

Compressor 1

208/230V - 3 Ph

460V - 3 Ph

575V - 3 Ph

Rated Load Amps

19

9.7

7.4

Locked Rotor Amps

123

62

50

Outdoor Fan
Motors (1)

Full Load Amps (total)

2.4

1.3

Power Exhaust
(1) 0.75 HP

Full Load Amps (total)

2.2

1.5

15 Amps

15 Amps

15 Amps

Service Outlet 115V GFI


Indoor Blower
Motor
Maximum
Overcurrent
Protection

Horsepower

1.5

1.5

1.5

Full Load Amps

6.6

7.5

3.4

2.4

2.7

Unit Only

50

50

25

25

20

20

with (1) 0.75 HP


Power Exhaust

50

50

25

25

20

20

Unit Only

33

34

17

17

13

13

with (1) 0.75 HP


Power Exhaust

38

39

19

20

15

15

Minimum
Circuit
Ampacity
3

ELECTRIC HEAT DATA


Maximum
Overcurrent
Protection
2

Minimum
Circuit
Ampacity
3

Electric Heat Voltage

208

240

208

240

480

480

600

600

7.5 kW

50

50

50

50

25

25

20

20

15 kW

50

60

50

60

30

30

25

25

22.5 kW

70

80

70

80

40

40

35

35

30 kW

90

100

90

100

50

50

40

40

7.5 kW

33

33

34

34

17

17

13

13

Unit +
Electric Heat

Unit +
Electric Heat

Maximum
Overcurrent
Protection

Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust

Minimum
Circuit
Ampacity

Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust

15 kW

48

54

49

55

27

27

22

22

22.5 kW

67

76

69

78

38

39

31

31

30 kW

87

99

88

100

49

50

40

40

7.5 kW

50

50

50

50

25

25

20

20

15 kW

60

60

60

70

30

30

25

25

22.5 kW

80

90

80

90

45

45

35

35

30 kW

100

110

100

110

60

60

45

45

7.5 kW

38

38

39

39

19

20

15

15

15 kW

54

60

55

61

30

30

23

24

22.5 kW

74

83

75

84

41

41

32

33

30 kW

93

105

94

106

52

53

41

42

ELECTRICAL ACCESSORIES
Disconnect
Kit

Fuse Block

Standard Access - 0-22.5 kW

20W18

20W18

20W18

20W18

30 kW

20W19

20W19

20W18

20W18

Hinged Access - 0-22.5 kW

20W24

20W24

20W24

20W24

30 kW

20W25

20W25

20W24

20W24

Unit Only

18W05

18W05

18W08

18W07

Unit + Power Exhaust

18W05

18W05

18W08

18W07

Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 31

ELECTRICAL/ELECTRIC HEAT DATA

7.5 TON

KCA090S
1

Voltage - 60hz

Compressor 1

208/230V - 3 Ph

460V - 3 Ph

575V - 3 Ph

Rated Load Amps

25

12.2

Locked Rotor Amps

164

100

78

Outdoor Fan
Motors (1)

Full Load Amps (total)

2.4

1.3

Power Exhaust
(1) 0.75 HP

Full Load Amps (total)

2.2

1.5

15 Amps

15 Amps

15 Amps

Service Outlet 115V GFI


Indoor Blower
Motor

Horsepower

Maximum
Overcurrent
Protection

Full Load Amps

4.6

7.5

10.6

2.1

3.4

4.8

1.7

2.7

3.9

Unit Only

60

60

60

30

30

30

20

20

25

with (1) 0.75 HP


Power Exhaust

60

70

70

30

30

35

20

25

25

Unit Only

39

42

45

19

20

22

14

15

17

with (1) 0.75 HP


Power Exhaust

44

47

50

21

23

24

16

17

18

Minimum
Circuit
Ampacity
3

ELECTRIC HEAT DATA


Maximum
Overcurrent
Protection
2

Minimum
Circuit
Ampacity
3

Electric Heat Voltage

208

240

208

240

208

240

480

480

480

600

600

600

7.5 kW

60

60

60

60

60

60

30

30

30

20

20

25

15 kW

60

60

60

60

60

60

30

30

30

25

25

25

22.5 kW

70

80

70

80

80

90

40

40

40

30

35

35

30 kW

90

100

90

100

100

110

50

50

60

40

40

45

7.5 kW

39

39

42

42

45

45

19

20

22

14

15

17

Unit +
Electric Heat

Unit +
Electric Heat

15 kW

45

51

49

55

53

59

26

27

29

21

22

23

22.5 kW

65

74

69

78

72

81

37

39

40

30

31

32

30 kW

84

96

88

100

92

104

48

50

52

39

40

41

Maximum
Overcurrent
Protection

Unit + 7.5 kW
Electric Heat 15 kW
and (1) 0.75 HP
Power Exhaust 22.5 kW
30 kW

60

60

70

70

70

70

30

30

35

20

25

25

60

60

70

70

70

70

30

30

35

25

25

25

80

80

80

90

80

90

40

45

45

35

35

35

100

110

100

110

100

110

60

60

60

45

45

45

Minimum
Circuit
Ampacity

Unit + 7.5 kW
Electric Heat 15 kW
and (1) 0.75 HP
Power Exhaust 22.5 kW
30 kW

44

44

47

47

50

50

21

23

24

16

17

18

52

58

55

61

59

65

28

30

32

23

24

25

71

80

75

84

79

88

40

41

43

32

33

34

91

103

94

106

98

110

51

53

54

41

42

43

ELECTRICAL ACCESSORIES
Disconnect
Kit

Standard Access - 0-22.5 kW

20W18

20W18

20W19

20W18

20W18

30 kW

20W19

20W19

20W19

20W18

20W18

Hinged Access - 0-22.5 kW

20W24

20W24

20W25

20W24

20W24

30 kW

20W25

20W25

20W25

20W24

20W24

Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 32

ELECTRIC HEAT CAPACITIES


7.5 kW
10 kW
15 kW
22.5 kW
30 kW
Input
No
of
kW
Btuh
No
of
kW
Btuh
No
of
kW
Btuh
No
of
kW
Btuh
No
of
kW
Btuh
Voltage
Stages input Output Stages input Output Stages input Output Stages input Output Stages input Output
208

5.6

19,200

7.5

25,600

11.2

38,400

16.9

57,700

22.5

76,800

220

6.3

21,500

8.4

28,700

12.6

43,000

18.9

64,500

25.2

86,000

230

6.9

23,500

9.2

31,400

13.8

47,000

20.7

70,700

27.5

93,900

240

7.5

25,600

10.0

34,200

15.0

51,200

22.5

76,800

30.0

102,400

440

6.3

21,500

---

---

---

12.6

43,000

18.9

64,500

25.2

86,000

460

6.9

23,500

---

---

---

13.8

47,000

20.7

70,700

27.5

93,900

480

7.5

25,600

---

---

---

15.0

51,200

22.5

76,800

30.0

102,400

550

6.3

21,500

---

---

---

12.6

43,000

18.9

64,500

25.2

86,000

575

6.9

23,500

---

---

---

13.8

47,000

20.7

70,700

27.5

93,900

600

7.5

25,600

---

---

---

15.0

51,200

22.5

76,800

30.0

102,400

UNIT CLEARANCES - INCHES (MM)

OUTDOOR AIR
HOOD

Unit Clearance

in.

mm

in.

mm

in.

mm

in.

mm

Service Clearance

36

914

36

914

36

914

36

914

Minimum Operation Clearance

36

914

36

914

36

914

36

914

Top
Clearance
Unobstructed

NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1 Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 33

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS - FIELD INSTALLED


COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface - Two Stage Heating / Two Stage Cooling
Conventional or Heat Pump - Seven Day Programmable - Four Time Periods/
Day - Economizer Output - Title 24 Compliant - ENERGY STAR Qualified Backlit Display - Automatic Changeover

C0STAT02AE1L
(14W81)

Sensors For Touchscreen Thermostat


1

Remote non-adjustable wall mount 20k temperature sensor..........................

C0SNZN01AE2-

Remote non-adjustable wall mount 10k averaging temperature sensor.........

C0SNZN73AE1-

Remote non-adjustable duct mount temperature sensor................................

C0SNDC00AE1-

Outdoor temperature sensor.............................................................................

C0SNSR03AE1-

(47W36)
(47W37)
(19L22)
(X4148)
Accessories For Touchscreen Thermostat
Locking cover (clear).........................................................................................

C0MISC15AE1(39P21)

Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1)
C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4)
C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.

DIGITAL NON-PROGRAMMABLE THERMOSTATS


Intuitive Interface - Automatic Changeover - Simple Up and Down Temperature Control
Two-stage heating / cooling conventional systems........................................

C0STAT10AE1L
(13K98)

Sensor For Digital Non-Programmable Thermostats Above


Remote wall mounted temperature sensor.......................................................

C0SNZN00AE1(26K57)

Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature Control
One-stage heating / cooling conventional systems...........................................

C0STAT12AE1L
(51M32)

Sensor For Digital Non-Programmable Thermostats Above


Outdoor temperature sensor.............................................................................

C0SNSR04AE1(X2658)

Accessories For Digital Non-Programmable Thermostats Above


Optional wall mounting plate.............................................................................

C0MISC17AE1(X2659)

OUTDOOR SOUND DATA


Unit
Model No.

125

250

500

1000

2000

4000

8000

Sound Rating
Number (dB)

024, 030, 036 and 048

63

66

70

71

68

62

53

75

060 and 072

67

72

77

76

73

68

61

82

090

66

71

73

74

70

65

57

79

Octave Band Sound Power Levels dBA, re 10-12 Watts - Center Frequency - HZ

NOTE - The octave sound power data shown does not include tonal correction.
1
Tested according to AHRI Standard 27095 test conditions.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 34

WEIGHT DATA
Model Number
024S
030S
036S
048S
060S
072S
090S

lbs.
495
497
498
535
565
664
767

Base

Net
kg
225
225
226
243
256
301
348

lbs.
607
609
610
647
681
767
873

Max.

kg
275
276
277
293
309
348
396

lbs.
555
557
558
595
625
724
827

Base

Shipping
kg
252
253
253
270
283
328
375

lbs.
676
678
679
716
750
839
942

Max.

kg
307
308
308
325
340
381
427

Base Unit - The unit with NO OPTIONS.


Max. Unit - The unit with ALL OPTIONS installed (Economizer, etc.).

OPTIONs / ACCESSORIES
Shipping Weights
lbs.
kg
ECONOMIZER / OUTDOOR AIR
Economizer
Economizer, Includes Outdoor Air Hood and
Barometric Relief Dampers with Hood
OUTDOOR AIR
Outdoor Air Dampers
Outdoor Air Damper Motorized Kit
Damper Section Manual
Power Exhaust
Standard Static
ELECTRIC HEAT
Electric Heat

ROOF CURBS - DOWNFLOW


Cliplock
8 in. height
14 in. height
18 in. height
24 in. height
Hinged
8 in. height
18 in. height
24 in. height
Standard
14 in. height
CEILING DIFFUSERS
Step-Down
Flush
Transitions (Supply and Return)

T1ECON30A-1
T1ECON30N-1

123
142

56
65

T1DAMP11A-1
T1DAMP11N-1
T1DAMP21AN1

25
29
18

12
14
9

T1PWRE10A-1
T1PWRE10N-1

35
39

17
19

7.5 kW - T1EH0075AN1
10 kW - T1EH0100AN1
15 kW - T1EH0150AN1
22.5 kW - T1EH0225AN1
30 kW - T1EH0300N-1

31
31
31
35
35

14
14
14
16
16

T1CURB23AN1
K1CURB23AP1
T1CURB20AN1
K1CURB20AP1
T1CURB21AN1
K1CURB21AP1
T1CURB22AN1
K1CURB22AP1

78
83
96
101
108
113
126
131

35
38
44
46
49
51
57
59

T1CURB30AN1
K1CURB30AP1
T1CURB32AN1
K1CURB32AP1
T1CURB33AN1
K1CURB33AP1

78
83
108
113
126
131

35
38
49
51
57
59

T1CURB10AN1
K1CURB10AP1

96
101

44
46

RTD9-65
RTD11-95
FD9-65
FD11-95
T1TRAN10AN1
T1TRAN20N-1

67
88
37
75
22
21

30
40
17
34
10
10

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 35

DIMENSIONS - INCHES (mm)


Model
No.

024
030
036
048
060
072
090

AA
Base
lbs. kg
86 39
86 39
86 39
93 42
98 44
115 52
164 74

Max.
lbs. kg
109 50
109 50
110 50
116 53
122 56
138 63
187 85

CORNER WEIGHTS
BB
CC
Base
Max.
Base
Max.
lbs. kg lbs. kg lbs. kg lbs. kg
104 47 123 56 167 76 199 90
104 47 124 56 168 76 199 91
105 48 124 56 169 77 200 91
112 51 132 60 181 82 212 96
119 54 138 63 191 87 223 101
139 63 156 71 225 102 251 114
179 81 203 92 221 100 252 114

DD
Base
lbs. kg
138 63
138 63
139 63
149 68
157 72
185 84
203 92

EE

Max.
Base
lbs. kg in. mm
176 80 38-1/2 978
176 80 38-1/2 978
177 80 38-1/2 978
187 85 38-1/2 978
197 90 38-1/2 978
222 101 38-1/2 978
231 105 47 1194

CENTER OF GRAVITY
FF
Max.
Base
Max.
in. mm in. mm in. mm
40 1016 18 457 18
457
40 1016 18 457 18
457
40 1016 18 457 18
457
40 1016 18 457 18
457
40 1016 18 457 18
457
40 1016 18 457 18
457
47 1194 21 533 21
533

Base Unit - The unit with NO INTERNAL OPTIONS.


Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external
to unit or high static power exhaust.
5-5/8
16-1/4
18
(143)
(413)
(457)
11
(279)

AA

BB

5 (102)

7 (178)

BOTTOM
RETURN
AIR
OPENING

29
(737)

BOTTOM
SUPPLY
AIR
OPENING

47 (1192)
BASE

20
(508) CENTER
OF
GRAVITY
25-3/4 (654)
024 thru 072
38-3/4 (984) 090

FF

9-1/2
(241)

6-5/8
(168)

DD

CC
26-1/2
(673)

BOTTOM
CONDENSATE
OUTLET

EE
BOTTOM POWER ENTRY
3 X 8 (76 X 203)

TOP VIEW (Base)


83-1/4 (2115) 024 thru 072
96-1/4 (2445) 090
35-3/8 (899) 024 thru 060
43-3/8 (1102) 072 / 090

38-7/8 (987) 024 thru 060


46-7/8 (1191) 072 / 090

45
(1143)

ELECTRICAL
INLET
CONDENSATE
OUTLET
(EITHER SIDE)
5-1/2
(140)

1 (25)

1 (25)

3-1/2 (89)
47 (1192)
BASE

END VIEW

26-1/2
(673)

LIFTING HOLES
(For rigging)
85-1/4 (2165) 024 thru 072 BASE
98-1/4 (2496) 090 BASE

SIDE VIEW
19-1/2
(495)

20
(508)

FORKLIFT SLOTS
(Front, Back and
Blower End)

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 36

18-3/8
(467)

11
(279)
2 (51)

29
(737)

5-1/2 HORIZONTAL HORIZONTAL 5-1/2


RETURN AIR (140)
(140) SUPPLY AIR
OPENING
OPENING
(Without Economizer)

BACK VIEW

ACCESSORY DIMENSIONS - INCHES (MM)


OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Downflow Applications)
11-3/4 (298) 024 thru 060
15-3/4 (400) 072 and 090

OPTIONAL OUTDOOR
AIR HOOD
(Furnished with Economizer)

12
(305)

OPTIONAL BAROMETRIC
RELIEF HOOD
(Furnished with Economizer)

SIDE VIEW
BAROMETRIC RELIEF HOOD FOR ECONOMIZER
(Furnished)

OUTDOOR AIR HOOD FOR ECONOMIZER


(Furnished)

1-1/4
(32)

2-1/2
(64)
12
(305)
33
(838)

30-1/2
(775)

1-1/4
(32)

2-1/2
(64)
1-1/2
(38)

3/4 (19)

1 (25)

3/8 (10)

Model
No.

in.

mm

in.

mm

in.

mm

024, 030, 036, 048, 060

19-1/4

489

13

330

11-3/4

298

072, 090

23-1/4

591

17

432

15-3/4

400

OUTDOOR AIR DAMPER HOOD DETAIL FOR OPTIONAL MANUAL OR MOTORIZED OUTDOOR AIR DAMPERS
(Downflow or Horizontal Applications)
10-1/2
(267)

35
(889)

OPTIONAL
OUTDOOR
AIR DAMPERS
AND PANEL

13-1/2
(343)
OUTDOOR AIR
DAMPER HOOD

OUTDOOR AIR
DAMPER HOOD
(Furnished)

35 (889)
024 thru 060
43 (1092)
072 and 090

SIDE VIEW

16-1/2
(419)

10-1/2
(267)

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 37

ACCESSORY DIMENSIONS - INCHES (MM)


OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)

Barometric Relief Hood


and Dampers

ECONOMIZER DAMPERS

RETURN AIR DUCT


(Field Fabricated - Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)

SUPPLY AIR DUCT


(Field Provided)
SUPPLY
AIR
OUTLET

BAROMETRIC RELIEF HOOD DIMENSIONS


Width - 35-1/2 in. (902 mm)
Height - 21 in. (533 mm) (024, 030, 036, 048, 060)
25 in. (635 mm) (072, 090)
See previous page for details.

RETURN
AIR
INLET

TOP VIEW
OUTDOOR AIR HOOD
(Furnished with Economizer)
29-1/4
(743)

19-1/2
(495)

HORIZONTAL
SUPPLY AIR
OPENING

20
(508)

This opening
not used in
Horizontal
Applications
with
Economizer

BAROMETRIC RELIEF HOOD


(Furnished with Economizer and
Field Installed on Field fabricated
Return Air Duct)
7/8
(22)

OUTDOOR
AIR

2-1/4
(57)

HORIZONTAL
RETURN AIR
OPENING

30-7/16
(773)

2-1/4
(57)

EXHAUST
AIR
5 (127)

BACK VIEW

RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)

RETURN AIR DUCT INLET


(Field Fabricated - Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)

NOTE - Return Air Duct and Transition must be supported.

Model
No.

in.

mm

in.

mm

024, 030, 036, 048, 060

18-3/4

476

11-3/4

298

072, 090

22-1/2

572

15-3/4

400

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 38

7/8
(22)

UNIT RETURN AIR DUCT


OPENING WITH ECONOMIZER
INSTALLED

END VIEW

ACCESSORY DIMENSIONS - INCHES (MM)


CLIPLOCK 1000 ROOF CURBS - DOUBLE DUCT OPENING
1-13/16
(46)

21-1/8
(537)

C
A

41-1/2
(1054)

37-7/8
(962)

B
19-1/8
(486)

15-1/8
(384)

8 (203)
14 (356)
18 (457)
24 (610)

SUPPLY
OPENING

12-5/8
(321)
1-13/16
(46)

RETURN
OPENING

32
(813)

NOTE - Roof deck may be omitted within confines of curb.

DETAIL ROOF CURB

TYPICAL FLASHING DETAIL FOR ROOF CURB


BASE BOTTOM

1-13/16
(46)

PACKAGED
UNIT

1/2 (13)
FIBERGLASS
INSULATION
(Furnished)

COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP

NAILER STRIP
(Furnished)
CANT STRIP
(Field Supplied)

ROOF CURB
(Extends around entire
perimeter of unit)

8 (203)
14 (356)
18 (457)
24 (610)

ROOFING
MATERIAL

RIGID INSULATION
(Field Supplied)
1-13/16
(46)

Model
No.

in.

mm

in.

mm

in.

mm

024, 030, 036, 048, 060, 072, 1 090

29-1/4

743

79-3/4

2026

76-1/8

1934

090

42-1/4

1073

92-3/4

2356

89-1/8

2264

090 models can be used on smaller 79-3/4 in. (2026 mm) roof curbs (not full perimeter) with 15-3/4 in. (400 mm) overhang at
condenser end of unit. See dimension drawing on page 42.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 39

ACCESSORY DIMENSIONS - INCHES (MM)


HINGED ROOF CURBS - DOUBLE DUCT OPENING
1-13/16
(46)
41-1/2
(1054)

21-1/8
(537)

A
37-7/8
(962)

B
19-1/8
(486)
15-1/8
(384)

8 (203)
18 (457)
24 (610)

SUPPLY
OPENING

12-5/8
(321)
1-13/16
(46)

RETURN
OPENING

32
(813)

NOTE - Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB


BASE BOTTOM

DETAIL ROOF CURB


1-13/16
(46)

PACKAGED
UNIT

1/2 (13)
FIBERGLASS
INSULATION
(Furnished)

COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP

NAILER STRIP
(Furnished)
CANT STRIP
(Field Supplied)

ROOF CURB
(Extends around entire
perimeter of unit)

8 (203)
18 (457)
24 (610)

ROOFING
MATERIAL

RIGID INSULATION
(Field Supplied)
1-13/16
(46)

Model
No.

in.

mm

in.

mm

in.

mm

024, 030, 036, 048, 060, 072, 090

29-1/4

743

79-3/4

2026

76-1/8

1934

090

42-1/4

1073

92-3/4

2356

89-1/8

2264

090 models can be used on smaller 79-3/4 in. (2026 mm) roof curbs (not full perimeter) with 15-3/4 in. (400 mm) overhang
at condenser end of unit. See dimension drawing on page 42.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 40

ACCESSORY DIMENSIONS - INCHES (MM)


STANDARD ROOF CURBS - DOUBLE DUCT OPENING
1-13/16
(46)
41-1/2
(1054)

21-1/8
(537)

C
A

37-7/8
(962)

B
19-1/8
(486)

15-1/8
(384)

14
(356)
SUPPLY
OPENING

12-5/8
(321)
1-13/16
(46)

RETURN
OPENING

32
(813)

NOTE - Roof deck may be omitted within confines of curb.

DETAIL ROOF CURB

TYPICAL FLASHING DETAIL FOR ROOF CURB


BASE BOTTOM

1-13/16
(46)

PACKAGED
UNIT

1 (25)
FIBERGLASS
INSULATION
(Furnished)

COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP

NAILER STRIP
(Furnished)
CANT STRIP
(Field Supplied)

ROOF CURB
(Extends around entire
perimeter of unit)

14 (356)

ROOFING
MATERIAL

RIGID INSULATION
(Field Supplied)
2 (51)

Model
No.

in.

A
mm

in.

B
mm

in.

mm

024, 030, 036, 048, 060, 072, 1 090

29-1/4

743

79-3/4

2026

76-1/8

1934

090

42-1/4

1073

92-3/4

2356

89-1/8

2264

090 models can be used on smaller 79-3/4 in. (2026 mm) roof curbs (not full perimeter) with 15-3/4 in. (400 mm) overhang
at condenser end of unit. See dimension drawing on page 42.
1

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 41

ACCESSORY DIMENSIONS - INCHES (MM)


090 MODELS - SHOWING OVERHANG ON SMALLER 79-3/4 INCH LENGTH ROOF CURBS
(Not Full Perimeter)

ROOF CURB
79-3/4
(2026)

2-3/4
(686)

15-3/4
(400)

SIDE VIEW

TRANSITIONS

T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCT


T1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
12
(305)

31-1/2
(800)

8 (203)

1-1/2 inch (38 mm) T1TRAN10AN-1


2 inch (51mm) T1TRAN20N-1

32
(813)

12-5/8
(321)

19-1/8
(486)

RETURN
OPENING

RETURN TRANSITION

SUPPLY
OPENING

21-1/8
(521)

T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCT


T1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
18-1/2
(470)

20-1/2
(521)
8 (203)

1-1/2 inch (38 mm) T1TRAN10AN-1


2 inch (51mm) T1TRAN20N-1

SUPPLY TRANSITION

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 42

ACCESSORY DIMENSIONS - INCHES (MM)


COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER

FLUSH CEILING DIFFUSER

F
G

F
C

2 (51)

2 (51)

D
H

B
J
K

Model Number
A

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

in.
mm

Duct Size

RTD9-65

RTD11-95

47-5/8

47-5/8

1159

1159

23-5/8

29-5/8

600

752

11-3/8

14-3/8

289

365

21-1/2

27-1/2

546

699

45-1/2

45-1/2

1156

1158

22-1/2

22-1/2

572

572

11-1/2

11-1/2

292

292

10-3/4

13-3/4

273

349

45-1/2

45-1/2

1156

1156

21-1/2

27-1/2

546

699

7-1/8

8-1/8

181

206

in.

18 round

20 round

mm

457 round

508 round

Model Number
A

in.
mm

in.
mm

C
D
E

1159

23-5/8

29-5/8
752

mm

343

422

in.

21

27

mm

533

686

in.
in.
in.
in.
mm

Duct Size

47-5/8

1159

16-5/8

mm
H

47-5/8

600

mm
G

FD11-95

13-1/2

in.

mm
F

FD9-65

45

45

1143

1143

22-1/2

22-1/2

572

572

11-1/4

11-1/4

286

286

10-1/2

13-1/2

267

343

in.

18 round

20 round

mm

457 round

508 round

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 43

GUIDE SPECIFICATIONS
This specification is for [Lennox Industries Landmark] rooftop units. Revise specification section number and
title below to suit project requirements, specification practices and section content. Refer to CSI MasterFormat for
other section numbers and titles.
Optional text and text that requires a decision are indicated by bold brackets [ ] and proprietary information is
indicated by bold italic brackets[ ]; delete text that is not needed in final copy of specification. Specifier Notes
typically precede specification text; delete notes in final copy of specification. Trade/brand names with appropriate
symbols typically are used in Specifier Notes; symbols are not used in specification text. Metric conversion, where
used, is soft metric conversion.
SECTION 237433
UNITARY AIR CONDITIONING EQUIPMENT
PART 1GENERAL
PART 1.01
SUMMARY
A. Section Includes: Packaged rooftop units and commercial packaged, gas/electric, electric/electric and electric/heat
pumps.
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI MasterFormat
and specifiers practice.
B.

Related Sections:

Specifier Note: Article below may be omitted when specifying manufacturers proprietary products and recommended
installation. Retain Reference Article when specifying products and installation by an industry reference standard. If
retained, list standard(s) referenced in this section. Indicate issuing authority name, acronym, standard designation and
title. Establish policy for indicating edition date of standard referenced. Conditions of the Contract or Division 1 References
Section may establish the edition date of standards. This article does not require compliance with standard, but is merely
a listing of references used. Article below should list only those industry standards referenced in this section. Retain only
those reference standards to be used within the text of this Section. Add and delete as required for specific project.
PART 1.02
REFERENCES
A. Agency Listings:
1. Intertek (ETL).
2. Canadian Standards Association (CSA).
B. Safety Standards:
1. Underwriters Laboratories (UL).
2. Underwriters Laboratories of Canada (ULC).
3. National Electric Code (NEC).
4. Canadian Electric Code (CEC).
C. Air-Conditioning, Heating and Refrigeration Institute (AHRI):
1. AHRI 340/360 Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment.
2. AHRI 370 Sound Rating of Large Outdoor Refrigerating and Air Conditioning Equipment.
3. AHRI 210/240 Performance Rating of Unitary Air Conditioning and Air-Source Heat Pump Equipment.
D. American Society for Testing and Materials (ASTM):
1. ASTM B117 Standard Practice for Operating Salt Spray.
2. ASTM 1153 Standard Method for Methyl Isobutyl Ketone.
E. ISO 9001, Quality Management Systems.
F. Meet Military Specification MIL-P-53084
Specifier Note: Article below should be restricted to statements describing design or performance requirements and
functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and operational properties
required to link components of a system together and to interface with other systems.
PART 1.03
SYSTEM DESCRIPTION
A. Performance Requirements:
Specifier Note: Article below should be restricted to Landmark (KH), heat pumps packaged roof top units only.
1. [2, 2.5, 3, 4, 5 and 6 ton capacity.]
Specifier Note: Article below should be restricted to Landmark (KG) gas/electric packaged roof top units or Landmark
(KC) electric/electric packaged roof top units.
2.
[2, 2.5, 3, 4, 5, 6 and 7.5 ton capacity.]
3. Electrical Characteristics:
a. 60 Hz
Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 44

GUIDE SPECIFICATIONS
Specifier Note 208/230 volt 1 phase is the only voltage and phase available for the 2 and 2.5 ton models. 208/230 volt
1 phase is an optional voltage and phase for the 3, 4 and 5 ton models. All other voltages are available on 3-7.5 ton
Landmark RTUs.
b. [208/230 v 1 Phase] [208/230 v 3 Phase] [460 v 3 Phase] [575 v 3 Phase]
Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or after
construction. Coordinate this article with Architects and Contractors duties and responsibilities in Conditions of the
Contract and Division 1 Submittal Procedures Section.
PART 1.04
SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal Procedures.
B. Product Data: Submit product data for specified products.
C. Shop Drawings:
1. Submit shop drawings in accordance with Section 01330 - Submittal Procedures.
2. Indicate:
a. Equipment, piping and connections, together with valves, strainers, control assemblies, thermostatic controls,
auxiliaries and hardware, and recommended ancillaries which are mounted, wired and piped ready for final
connection to building system, its size and recommended bypass connections.
b. Piping, valves and fittings shipped loose showing final location in assembly.
c. Control equipment shipped loose, showing final location in assembly.
d. Dimensions, internal and external construction details, recommended method of installation with proposed
structural steel support, mounting curb details, sizes and location of mounting bolt holes; include mass
distribution drawings showing point loads.
e. Detailed composite wiring diagrams for control systems showing factory installed wiring and equipment on
packaged equipment or required for controlling devices or ancillaries, accessories and controllers.
f.
Fan performance curves.
g. Details of vibration isolation.
h. Estimate of sound levels to be expected across individual octave bands in dB.
i.
Type of refrigerant used.
j.
Plan view, front view end view, back view and curb detail with dimensions.
D. Quality Assurance:
1. Test Reports: Certified test reports showing compliance with specified performance characteristics and physical
properties.
2. Certificates: Product certificates signed by manufacturer certifying materials comply with specified performance
characteristics and criteria and physical requirements.
3. Manufacturers Instructions: Manufacturers installation instructions.
Specifier Note: Coordinate paragraph below with Part 3 Field Quality Requirements Article herein. Retain or delete as
applicable.
E.
F.

Manufacturers Field Reports: Manufacturers field reports specified.


Closeout Submittals: Submit following:
1. Warranty: Warranty documents specified.
2. Operation and Maintenance Data: Operation and maintenance data for installed products in accordance with
Division 1 Closeout Submittals (Maintenance Data and Operation Data) Section. Include methods for maintaining
installed products and precautions against cleaning materials and methods detrimental to finishes and performance.
Include names and addresses of spare part suppliers.
3. Provide brief description of unit, with details of function, operation, control and component service.
4. Provide equipment inspection report and equipment operation test report.
5. Commissioning Report: Submit commissioning reports, report forms and schematics in accordance with Section
01810 - Commissioning.
PART 1.05
QUALITY ASSURANCE
A. Qualifications:
1. Installer experienced in performing work of this section who has specialized in installation of work similar to that
required for this project.
PART 1.06
DELIVERY, STORAGE & HANDLING
A. General: Comply with Division 1 Product Requirements.
B. Ordering: Comply with manufacturers ordering instructions and lead time requirements to avoid construction delays.
C. Packing, Shipping, Handling and Delivery:
1. Deliver materials in manufacturers original, unopened, undamaged containers with identification labels intact.
2. Ship, handle and unload units according to manufacturers instructions.
Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 45

GUIDE SPECIFICATIONS
D.

Storage and Protection:


1. Store materials protected from exposure to harmful weather conditions.
2. Factory shipping covers to remain in place until installation.
PART 1.07
PROJECT CONDITIONS
A. Installation Location: [Confirm design conditions and temperature.].
Specifier Note: Coordinate article below with Conditions of the Contract and with Division 1 Closeout Submittals (Warranty).
PART 1.08
WARRANTY
A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B. Manufacturers Warranty: Submit, for Owners acceptance, manufacturers standard warranty document executed by
authorized company official. Manufacturers warranty is in addition to, and not a limitation of, other rights Owner may have
under Contract Documents.
Specifier Note: Aluminized Heat Exchanger and Stainless steel Heat Exchanger limited warranty is only available on
Landmark (KG) Gas/Electric models. Compressor and Other System Components are covered on all Landmark
units.
C.

Warranty: Commencing on Date of Installation.


1. Compressors: 5 years (limited).
2. Other Covered System Components: 1 year (limited).
3. [Aluminized Heat Exchangers: 10 years (limited).] [Stainless Steel Heat Exchangers: 15 years (limited).]
PART 2PRODUCTS
Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance
characteristics, material standards and descriptions as applicable. Use of such phrases as or equal or or approved
equal or similar phrases may cause ambiguity in specifications. Such phrases require verification (procedural, legal and
regulatory) and assignment of responsibility for determining or equal products.
PART 2.01
ROOFTOP UNITS
A. Manufacturer: Lennox Industries Inc.
1. Contact: 2100 Lake Park Blvd., Richardson, TX 75080; Telephone: (800) 453-6669; website: www.lennox.com.
B. Proprietary Products/Systems: Lennox Landmark Packaged Rooftop Units, including the following equipment:
1. Cabinet:
a. Heavy gauge steel panels.
b. Pre-painted steel panels.
c. Heavy Gauge galvanized steel base rail.
d. Rigging holes on all four corners.
e. Forklift slots (on three sides, not directly below condenser coil) on base rail.
f.
Raised or flanged edges around duct and power entry openings.
Specifier Note: Downflow is the standard configuration that all Landmark units are shipped as.
Specifier Note: Horizontal Flow is an option for all Landmark models. Landmark KH, KG and KC models of tonnages
2, 2.5, 3, 4, 5 and 6 can be converted, in the field, to horizontal flow without the need of a conversion kit. If applied
horizontally with an economizer, a conversion kit is required.
g. [Downflow] [Horizontal] Air Flow configuration
Specifier Note: add the and gas lines only if using a Landmark (KG) gas/electric model.
h. Electrical lines [and gas lines] can be brought through the base of the unit or through horizontal knockouts.
i.
Insulation:
1) All panels adjacent to conditioned air are fully insulated with non-hygroscopic fiberglass insulation.
2) Unit base is fully insulated.
3) Unit base insulation also serves as a roof curb seal.
j.
Access Panels:
1) Provided for economizer/filter section.
2) Provided for heating/blower section.
k. Condensate Drain Pan.
Specifier Note: Factory Installed Options are options that can be selected for the Landmark roof top units. The Factory
Installed Options are installed at the Lennox manufacturing facility.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 46

GUIDE SPECIFICATIONS

l.

[Factory Installed Options:]


1)

[Corrosion Protection, meets standards:


a) Military Specification MIL-P-53084.
b) ASTM B117
c) ASTM 1153]
2) [Hinged Access panels]
3) [GFI Service Outlets (field wired)]
4) [Disconnect Switch (up to 80 amps for KG model]
Specifier Note: Field Installed Accessories are options that can be selected for the Landmark roof top units. The Field
Installed Accessories are shipped separately and installed in the field.
m. [Field Installed Accessories:]
Specifier Note: Of the selections below, [Coil Guards] [Hail Guards], only one can be selected.
1) [Coil Guards] [Hail Guards].
2) [Disconnect Switch (up to 80 amps for KG model, up to 150 amps for KC and KH models)]
3) [Condensate drain trap]
2. Cooling System:
a. Refrigerant type: R-410A.
b. Capable of operating from 30 - 125 degrees F (-1 - 52 degrees C) without installation of additional controls.
c. Compressors:
1) Scroll Type.
2) Resiliently mounted on rubber mounts for vibration isolation.
3) Overload Protected
4) Internal excessive current and temperature protection.
5) Isolated from condenser fan air stream.
6) Refrigerant cooled.
d. TXV
e. High pressure switch
f.
Freezestat
g. High capacity filter driers
Specifier Note: Include following 2 articles for Landmark (KH) packaged heat pumps models.
h.
i.
j.
k.

Reversing Valves: Four-way interchange reversing valve.


Defrost Control.
Efficiency: Standard.
[Low ambient kit: Field installed]

Specifier Note: Crankcase heater is available to be field installed on all units except the Landmark model KH on tonnages
2-6, as well as 6 and 7.5 ton KG/KC models where it is standard.
3.

l.
[Crankcase heater: field installed]
Coil Construction:
a.

b.

c.

Condensing/evaporator coil general construction:


1) Aluminum Rippled and Lanced fins.
2) Copper tube construction.
3) Aluminum fins mechanically bonded to copper tubes.
4) All coils are high pressure leak tested at manufacturing facility.
Evaporator Coils:
1) With balanced port thermal expansion valves, freeze protection on each compressor circuit, pressure and
leak tested to 500 psi, and maximum 14 fins per inch.
2) Each compressor circuit on coil divided across face of coil and active through full depth of coil.
3) [With flexible immersed coating electrodeposited by dry film process].
Condenser Coils:
1) [With flexible immersed coating electrodeposited by dry film process] on corrosion hardened
units only.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 47

GUIDE SPECIFICATIONS
a.
b.

4. Wiring:
Color coded and continuously marked to identify point-to-point component connections.
Not in contact with hot-gas refrigerant lines or sharp metal edges.

Specifier Note: Landmark units with Gas Heating Systems are KG models.
5.

Gas Heating System:


a. Induced draft
b. Natural gas fired system with direct spark ignition
c. Electronic flame sensors
d. Flame rollout switches
e. High heat limit switches
f.
Induced draft failure switch and capable of operating to altitude of 2000 feet (610 m) with no derate to manifold
pressure.
g. Service access for controls, burners and heat exchanger.
h. Heat Exchanger:
1) Tubular Design
2) [Aluminized steel] [Stainless steel].
i.
Gas piping system tight and free of leaks when pressurized to maximum supply pressure.
j.
Gas Valve: Two-stage, redundant type gas heat valve with manual shutoff.
k. Gas Valve: Single-stage.
l.
Gas Burners: Aluminized steel inshot-type gas burners.
m. Direct spark pilot ignition.
n. Fan and Limit Controls.
o. Safety Switches.
p. Gas piping system tight and free of leaks.
q. [Low NOx]
Specifier Note: Field Installed Accessories are options that can be selected for the Landmark KG Gas/Electric models.
The Field Installed Accessories are shipped separately and installed in the field.
r.
[Field Installed Accessories:]
1) [Combustion Air Intake Extensions].
2) [Vertical Vent Extension Kit].
3) [LPG/Propane Kit].
4) [Low Temperature Vestibule Heater].
Specifier Note: The Electric Heating System is an option for Landmark (KH), heat pump, and Landmark (KC), electric/
electric models only. The Electric Heating System is only available for field installation.
6.

Electric Heating System:


a. Electrical resistance heater.
b. [Field] installed.
c. [Field] installed Fuse Block.

Specifier Note: The Fuse Block is an option for 024-072 KCA models and the KHA024-060 models. It is furnished standard
on KCA090 and KHA072 models.
d.
e.
f.

Reset thermal limit protection.


Single point power supply.
Heater Element:
1) Nickel chromium wire.

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 48

GUIDE SPECIFICATIONS
2) Individually fused.
g. Electric heater slides out of unit for service.
7. Heating Controls:
Specifier Note: 2 stages of heating control are only available on Landmark (KG) gas/electric models of tonnages 4-6, on
two stage units.
a. Support 2 stages of heating control from thermostat or DDC.
b. With delay time of 30 seconds between low and high heat stages.
8. Supply Air Fan Motor and Drives:
a. Permanently lubricated ball bearings (for belt drive motors).
b. Thermal overload protected motors with automatic reset.
c. Adjustable sheaves on belt drive motors for blower speed adjustment.
d. Optional low and high static motor/drive combinations and optional drive kits.
9. Supply Air Fan:
a. Double inlet type, G90 (Z275) galvanized steel with forward curved blades.
b. Statically and dynamically balanced.
c. Continuous or automatic control for occupied periods.
10. Supply Air Filters:
a. Disposable 2 inch.
11. Condenser Fan Motor:
Specifier Note: Landmark 2-4 ton models have sleeve bearings.
a. Direct drive with permanently lubricated ball bearings.
b. Watertight with thermal overload protection and automatic reset.
c. Motor mount isolated from fan safety guard.
12. Condenser Fans:
a. Corrosion resistant propeller type with vertical discharge and finger safety guard.
13. Unit Control System (2 through 7.5 tons): Terminal strip is standard with up to 2 stage heat/2 stage cool thermostat
inputs along with supply fan and occupied mode ( for the economizer option). Self contained 24 volt control circuit is
protected by an integral manual reset circuit breaker.
a. [Control Options:]
1)
[Single Enthalpy Control] : [Field] [Factory]
2)
[Differential Enthalpy Control : Field]
3)
[CO2 Sensor: Field Mounted]
14. [Accessories:]
a. [Economizer]: [Field] [Factory]
Specifier Note: Motorized outdoor air damper is only available in a field mounted version for the Landmark models of
tonnages 2, 2.5, 3, 4, 5 and 6.
b. [Motorized Outdoor Air Damper: Field Mounted]
Specifier Note: Manual outdoor air damper is only available in a field mounted version for the Landmark models of
tonnages 2, 2.5, 3, 4, 5 and 6.
c. [Manual Outdoor Air Damper: Field Mounted]
Specifier Note: Barometric relief damper is included with factory or field installed economizer on 2-7.5 ton models.
d. Barometric relief damper
Specifier Note: Power Exhaust Fans only available for the Landmark models of tonnages 3, 4, 5, 6 and7.5.
e. [Power exhaust fan: Field Mounted]
f.
[Dirty filter switch: Field]
g. [Smoke detectors: Field]
h. [Roof curb: Field]
i.
[Outdoor air hood: Field]
j.
[Barometric relief damper hood: Field]
Specifier Note: Edit article below to suit project requirements. If substitutions are permitted, edit text below. Add text to refer to
Division 1 Project Requirements (Product Substitutions Procedures) Section.
PART 2.02
PRODUCT SUBSTITUTIONS
A. Substitutions: No substitutions permitted.

Landmark Packaged Electric / Electric 2 to 7.5 Tons/ Page 49

GUIDE SPECIFICATIONS
PART 3EXECUTION
PART 3.01
MANUFACTURERS INSTRUCTIONS
Specifier Note: Revise article below to suit project requirements and specifiers practice.
A.

Compliance: Comply with manufacturers written data, including product technical bulletins, product catalog installation
instructions, product carton installation instructions and manufacturers SPEC-DATA sheets.
PART 3.02
EXAMINATION
A. Site Verification of Conditions: Verify substrate conditions, which have been previously installed under other sections, are
acceptable for product installation in accordance with manufacturers instructions
PART 3.03
INSTALLATION
A. Install [Packaged rooftop units] [And] [Commercial packaged, gas/electric, electric/electric and electric/heat
pumps] in accordance with manufacturers instructions [On roof curbs provided by manufacturer] [As indicated].
END OF SECTION

Landmark Packaged Electric / Electric 2 to 7.5 Tons / Page 50

REVISIONS
Sections

Description of Change

Optional Accessories

Removed Field Installed Drive Kits (factory only)

Blower Data

Updated Blower Data. Revised Drive Kit Table.

Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1-800-4-LENNOX

NOTE - Due to Lennox ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
2010 Lennox Industries, Inc.