In an electrical circuit containing inductance, voltage across the inductive elements is proportional to the rate of change of current.

So if the current is a sine function of time, the voltage across the inductive element is a cosine function. The instantaneous power applied to the inductive element is the product of instantaneous current and instantaneous voltage. Over one complete cycle of the current waveform, the power completed 2 complete cycles and has an average value of zero. This represents energy being stored in and removed from the inductance. Although the energy involved is not used to heat or drive a load, it is essential to allow the load to operate. I've tried to come up with a useful mechanical analogy for this and it's not easy. However, if you are into rowing at a gym, you may be able to relate to this: A rowing machine has a relatively large flywheel and some elastic bits. When you pull on the handle, some of the effort does to driving the fan or other load - this relates to active power. Some of the effort goes into accelerating the flywheel or stretching the elastic - this energy is then recovered during the return stroke and is the reactive component The first place you should look is http://www.wikipedia.org; search for 'reactive power'. There are contributors to this site who will insist that reactive power doesn't "flow", or that there's no such thing as reactive "power". But for the purposes of this contribution (and per commonly acepted convention--see http://www.wikipedia.org) we will consider that reactive power does indeed exist and that it flows. And remember: the originator of this thread asked for an explanation in layman's terms, which for me, anyway, does not initially include vector diagrams and trigonometry and mathematical formulae. All of these things are necessary for a complete and proper understanding of the phenomenon, but not for a rudimentary understanding on which to base all of the formulae and vector diagrams, etc., which just serve as mathematical proofs of the principles. In an AC power system, there are resistive loads and reactive loads. Reactive loads include inductive and capacitive loads--and the majority of loads on any grid are inductive (from induction motors used for everything from vibrators to elevators to refrigeration compressors to fans to all manner of pump motors (potable water, sewage, chemical, and so on)). Transformers are also an inductive load on the system. So, since they're the predominant load, let's focus on inductive loads. In an induction motor, a magnetic field has to be induced on the rotor of the motor in order for it try to follow the apparently rotating magnetic field of the stator that is connected to the AC power source in order to produce torque. The act of inducing the magnetic field on the rotor of the induction motor causes a shift to occur between the AC current sine wave and the AC voltage sine wave of the AC power system. Some of the total amount of energy that's being consumed from the AC power system by the induction motor is used in the induction of the magnetic field on the rotor of the motor which allows the motor to produce torque. In other words, the total amount of energy being consumed by the motor does not end up as torque (real power). The magnitude of the shift between the AC voltage- and current sine waves is measured or expressed in many ways: power factor, VArs, phase angle, etc. The key thing to remember is that if nothing is done to try to contain or reduce the phase shift

between the AC voltage- and current sine waves they can eventually shift so much that the ability of the AC system to supply real power will be reduced (such as when brownouts occur). If we think of the induction of the magnetic field on the rotor of the induction motor as needing "power" and we call that reactive power, then we can think of reactive power as being consumed, in the same was as real power is consumed. We can measure the amount of power required to induce the magnetic field on the induction motor rotor in VArs. And, to counter the effect of the phase shift on the system of lots and lots of induction motors and transformers (which also induce magnetic fields on secondary windings) we can produce reactive power to reduce the phase shift and maintain the AC power system's ability to provide power. We can produce reactive power to "compensate" for the inductive load on the system primarly by increasing excitation current to the rotors of synchronous generators over and above the amount required to maintain the generator terminal voltage equal to the voltage of the grid to which the generator is connected. This causes reactve power, called VArs to flow out of the generator terminals on to the AC power system, reducing the phase shift and supporting the AC power system's ability to transmit real power. So, VArs are "required" or "consumed" to induce the magnetic field on the induction motor rotors commonly used everyhwere, and to increase or decrease voltage through transformers used to distribute AC power. The effect of VARs on the system is to shift the AC voltage- and current sine waves out of phase with each other. If they get too far out of phase, the ability of the AC power system to supply power is reduced. VARs can be produced by synchronous generators--but since that requires DC power, and that DC power usually comes from the AC power system, that power is not available for sale to consumers. Power factor correction capacitors can be used to help with controlling the phase angle between the AC voltage- and current sine waves, but they are usually expensive and have their own idiosyncracies. Real power, watts, can be converted in to torque and work which is something we can understand and visualize. Reactive power, VArs, have no such tangible quantity that we can see or envision. A lot of people like to say that, "VArs are like foam on beer; it's just there but it doesn't do anything." Foam on a beer tells the drinker the beer is not flat. There's very little worse than a cold, flat beer especially on a hot day. Okay, a hot, flat beer is worse. And if AC power systems aren't properly managed, the beer could be flat and hot Relatively easy. Capacitance shifts the angle between the voltage and current sine waves of an AC power system in the opposite direction than inductance does, in effect "countering" the effects of inductance

You gave a great explanation for what VARS does but as an operator I have always had one point of confusion. Everything I have read so far on how "real" power is supplied says it is done by adjusting excitation. Also, in seperate texts "reactive" power is adjusted by adjusting excitation. Yet when I'm operating our units I can adjust reactive power and real power

independently. So I am confused how excitation can be increased or decreased to control MW or VARS independently from one another. Reply to this post...

Posted by CSA on 19 September, 2007 - 11:09 pm When you say you can adjust reactive power and real power independently, you should be able to do so. Reactive "power" and real power are different, VArs being controlled by excitation and watts being controlled by torque input to the generator. At small real power outputs, adjusting reactive power *can* have an effect on real power. But it's not clear exactly what your confusion is. Real power is a function of torque; reactive "power" (VArs and/or power factor) is a function of excitation. Other than when lightly loaded (real power output) there should not be too much effect on real power when adjusting excitation when connected to a large (infinite) grid. Reply to this post...

Posted by Intern on 24 May, 2010 - 3:11 pm So let's get down to practical usage. I have a list of kwh and kvarh, polled at 15min intervals; can I compare the two to identify problems? If so, what types of problems and how do I go about doing so? Reply to this post...

Posted by curt wuollet on 25 May, 2010 - 4:00 am That wouldn't be how I would use that data, unless we had a mandate to maintain a given PF for financial reasons. Some power suppliers impose a penalty and there are other cost implications. The ratio will typically bounce around as different loads are switched on and off so detecting a problem that way would require that you know a lot about what's going on. So you might use it to justify PF correction gear. But since it is almost entirely dependent on the loads connected, it is generally something you live with, or correct to the extent that the variation allows. Regards cww Reply to this post...

Posted by CSA

on 26 May, 2010 - 11:17 am

cww is exactly correct: We don't know what kind of "problems" you are trying to diagnose. Generator problems? Exciter (AVR) problems? Problems maintaining VAr setpoint or power factor setpoint? Generator heating problems? Generator vibration problems? Real power stability issues? Reactive power stability issues? Without understanding what problems you are trying to diagnose or solve, no one can say if the information will be practically useful or not. Reply to this post...

Posted by kinley on 11 July, 2010 - 2:08 am Can you please explain more, on reactive power, and its effect..........., how does it affect the winding temperature of a generators..........and in order to minimize the heating effect on a windings, what should i do.........decrease or increase the VAR components...........for a consistent load on a generator. Reply to this post...

Posted by CSA

on 12 July, 2010 - 1:54 pm

When power is being produced at a lagging power factor (lagging VAr indication), the excitation provided to the generator field (the rotor) is usually in excess of what's required. That excess current flow results in heating (current flowing in a conductor produces heat) and the ability of the generator cooling system to remove that heat from the rotor so that the insulation and windings aren't damaged is the limiting factor for the lagging VAr "production". When power is being produced at a leading power factor (leading VAr indication), the magnetic fields in the generator become slightly distorted (from their normal configuration) and the stator windings and end-turns can become overheated damaging insulation and windings and stator punchings, etc. The best way to avoid excessive heat generation is to operate the generator in accordance with the reactive capability curve provided by the generator's manufacturer, which depicts the limits of operation for lagging and leading and zero VAr conditions based on generator temperatures. Reply to this post...

Posted by LMGS on 9 December, 2010 - 2:38 am What are the causes of reactive power? I have records of 15 min interval of kwh and kvarh and observed a difference of the trend of kvarh after the changed of the substation from

69/34.5kv to 69/13.2kv. Actually, we had a double transformation, 69/34.5kv, then 34.5/13.2kv. The record shows that during off-peak,the kvarh is zero, at peak is below 100. After we switch to 69/13.2kv, it registered 100 below at off-peak and 100-300 at peak. Please advice. -lmgs Reply to this post...

Posted by Phil Corso

on 9 December, 2010 - 10:05 am

LMGS... I suggest you post a new thread outlining your problem since it is not typical of what this thread provides regarding education of Control.Com members. That said, here is my suggestion: This kind of a problem is best solved by developing an OMT or Operations Matrix Table, similar but more extensive than what you provided! It should contain, Date, Time, Electrical parameters, i.e., MVA, MW, MVAr, kV, A, PF, Excitation values, Grid exchange parameters, etc, and pertinent mechanical parameters, i.e., fuel flow, temps, etc. Regards, Phil Corso Reply to this post...

Posted by Anonymous on 14 August, 2007 - 6:12 pm If power is a glass of beer, reactive power is the foam. It takes up space, but you can't drink it. Reply to this post...

Posted by CSA on 14 August, 2007 - 10:14 pm Okay; if that's true, why do we care about reactive power? Why not just let the generator and the grid do whatever it bloody well pleases? For that matter, why not just break the top off the beer bottle and dump the beer in a cold mug? Because most of the beer will turn to foam! Why not shake the can of beer before you open it? It usually takes a new bartender wannabe a few pulls to get the hang of pulling a draft without having to keep pouring the foam off. Why do people take such care to keep the foam on beer to a minimum? Because it's not to be ignored, or, the glass will not contain as much alcohol. Reply to this post...

Posted by Phil Corso, PE on 15 August, 2007 - 10:59 pm Responding to CSA's not so "white" paper on Reactive Power: Although a small step for man, you appear to be leaning in the right direction, i.e., substituting the proper term "VAr" for the oxymoron expression "Reactive Power!" Thanks, Phil Corso (cepsicon@aol.com) Reply to this post...

Posted by Anonymous on 15 August, 2007 - 11:51 pm Drink straight from the bottle and there will be no foam. Perhaps we should discuss the effects of reactive power. For instance, it is ineffective to attempt to "flow" VArs over long distance transmission lines. Drink straight from the bottle. Large inductive loads need their capacitive counterpart near the inductive source to be effective. A generator may be able to produce VArs and have a manufacturer published reactive curve, but voltage limitations on the generator prevent producing maximum VAr output in relation to terminal voltage limitations. Generator and transformer limitations can cause watt output to be clamped while producing a large VAr output. When phase angle is shifted by an inductive load; the generator should produce more power, both real and/or imaginary (VAr). The additional voltage and/or current has a fuel cost associated with it. Transmission system operators have a dilemma. The voltage is low on a portion of the grid(where the inductive load resides) and they have to attempt to raise the voltage over a significant distance of tranmission line and transformers. Sometimes, these operators find that the VAr they need cannot be produced by a generator due to terminal voltage limitations of the generator. Come on, folks! Most people do not want to know the math, sine of phase angle. They want to know why we make a VAr and what we do with it. Start typing Now! No beer drinking until complete. Reply to this post...

Posted by CSA on 16 August, 2007 - 12:32 am I found this to be an excellent site: http://www.the-power-factor-site.com

An excellent discussion of the fundamentals, with graphs and graphics, and maths, all in one nice little package. If I drink from the bottle too fast, the beer will turn to foam. I only do that on a really hot day. Otherwise, I like to savor my hops and barley and yeast--and keep my bottle close. Reply to this post...

Posted by CSA on 17 August, 2007 - 10:34 am VArs are required for the magnetizing currents required for induction motors and transformers. The effect of too many induction motors and transformers on the system is to cause the AC voltage and current sine waves to shift away from each other, reducing the ability of the AC power system to deliver power (real power--watts). By producing VArs with synchronous generators or synchronous condensers or synchronous motors, or introducing capacitance using power factor correction capacitors (which serve to shift the current- and voltage sine waves in the opposite direction as the inductive load, countering the effects of the inductances), the relationship between the current- and voltage sine waves will be maintained at a level which allows the AC power system to deliver optimal (not ideal) real power--watts. It's always been my understanding that utilities with large hydroturbine plants use these plants for VAr production during summer months when air conditioning loads add to the inductive loading of the system. These hydro plants are located hundreds of miles, in some cases, from the urban loads connected to the grid. Since it takes real power (watts) to produce the DC required to produce VArs, they use the hydroturbines to provide the torque to the shaft-driven exciters to reduce fuel costs. Water from a penstock is usually cheaper than fuel in a fossil plant. Reply to this post...

Posted by THe original brewer on 19 August, 2007 - 11:40 am When a capacitor or inductor is connected to an AC source, current flows in the circuit. THis current is out of phase with the voltage. The energy in the system is stored as either a magnetic field, (in the case of an inductor) or in an electric field (in the case of a capacitor). The time rate change of this energy is referred to as 'reactive power'. If the circuit includes pure resistances, as well as reactances, then the total (apparent power) is the vector sum of these two entities. Just as the foam in a glass of beer doesn't contribute to your ability to drive a car, reactive power can't contribute to the utility's bottom line (for the home owner). Yes, it usually does for the business owner.

Reply to this post...

Posted by Oil Analyst on 30 December, 2008 - 1:57 pm Since there are a lot of water and pipes analogies in electricity... I wonder if you could compare reactive power to line-fill in a pipeline system? Reply to this post...

Posted by CSA

on 5 January, 2009 - 10:24 am

Can you elaborate on how you would liken reactive power to line-fill in a pipeline system? Are you referring to some kind of "accumulator" effect? Reply to this post...

Posted by electrics

on 30 May, 2009 - 9:13 am

pls tell me when we have a resistive load do we have a reactive current lagging because of the windings of the generator? if so pls tell me how a reactive power will go forth and back through the source? i mean the inductance of the windings will loaded and unloaded as this energy goes to and out of source ok? so how can generator get back a reactive power? is it possible to say that the energy goes back to the exciter? With whay kind of a circuit i think is this. There is a 0 degree source and it has a winding impedance at the generator side and a resistive load across its output, so this impedance will have a reactive power but this energy needs to return to the source true? so i can get how can this be? I really dont know how a source can get its energy back? does it store this energy in its windings ? if so my circuit model is wrong? as u see a lot of question Reply to this post...

Posted by Dipak Barot on 21 April, 2010 - 11:42 am > Please, can someone explain Reactive power in layman's language? < Reactive power can be explained simply with the observation of Induction motor. Remember, Rotor of IM is always shorted. When power is given to the stator, it creates rotating magnatic field which link with rotor.so induced emf produced in rotor, and this 100 % emf circulate the current inside the rotor, which also produces magnetic field opposed to stator magnetic field.This two field always push each other to rotate the rotor.

As the stator is steady and rotor field can be shift with rotor , due to this pushing activity stator field contracts and shift the electron a bit back. so current could not be remain in phase of voltage. So reactive power is just a opposition of supply power which shift the electron a bit back. so reactive power is just loss of active power nothing else. Syncronous generator/motor uses same principle to improve the PF i.e. shift the field back or forward. that's it. Reply to this post...

Posted by curt wuollet on 21 April, 2010 - 2:50 pm I understood reactive power better before that explanation :^) But, sometimes it's good to get several approaches to find one that "clicks" with the questioner. So here goes. Reactive power is the product of voltage and the current flowing to charge capacitors or magnetize inductors. These reactances store and release energy but (ideally) do not dissipate it. Lets use a capacitor as an example. With DC this is straightforward, you charge a capacitor which takes current, and the charge is maintained. But with AC, the voltage is constantly changing and even reversing, so the charge must be removed and the capacitor is charged in the opposite direction. These also take current. So you have an applied voltage and you have these alternating currents, but no power is being dissipated. That is reactive power, but it's not "real" power as no work is being done or power being dissipated. So, it's treated separately. Since it's not "real" power, it is also often referred to as Apparent power. Because it's not a perfect world, almost any AC circuit has both real and apparent power being transferred at the same time. This was the explanation that helped the most folks when I was teaching electronics. I saved vectors and phase angles for a different day. If all you remember is the first sentence, you will be doing better than 30% of the students. This is really where things get complicated. Regards cww (who kinda enjoyed teaching) Reply to this post...

Posted by G.Rajesh on 14 July, 2010 - 12:31 am Dear All, I try to explain reactive power compare with our body. if we have to do some work we need energy. for example, if we had 20 calories, 15 calories will be used for do useful work (moving the table from one place another, lifting an equipment etc...) 5 calories will be used for move the hand and foot. This 5 calories like reactive power though it's not useful but without that we can do effective work. Like above if a generator produce power or during transmission of power some of the energy

will be wasted as heat that is reactive power. Regards G.Rajesh Reply to this post...

Posted by Anthony Giorgianni on 20 August, 2010 - 6:33 pm This thread is interesting, so I thought I'd post to tell an interesting story about vars or VArs or however it's spelled. I'm a journalist who years ago covered Northeast Utilities in the Northeast. As a writer for the Hartford Courant at the time, I had a tip that New England - or at least Connecticut - might undergo its first brownouts in years. So I called Bernie Fox, an engineer who also was then president of NU. He invited me into his office in Berlin, Conn. and gave me a big talk about vars, which I had never heard of. I remember his telling me how vars are needed to operate motors and how they they didn't travel over great distances, if travel is the right word. I remember his saying that burying the transmission cables (or maybe distribution cables) enabled vars to travel further or increased them or something. It had to do with the cable and ground and magnetism, or something. Maybe induction between the cable and ground? Specifically I remember his drawing Boston on his blackboard, where I guess they intentionally buried the cables to increase this effect. Anyway, I wrote the page 1 story, breaking the news. And sure enough New England experienced its first brownout soon after, maybe that summer. I never forgot about vars, not that I really understand them or electricity in general (As I kid, I used to take the "How and Wonder Book of Electricity" out of the school library again and again. There was a story about a blackout that I like to read over and over, oddly.) I never forgot Bernie either. He died a few years back. He was a good guy. He'd always explain the engineering or utility financing (placing Millstone 3 into the rate base) behind stuff before he'd let me ask questions about anything. And he never complained about my writing stories critical of NU as long as I had my technical stuff right. Anyway, thought anyone still monitoring this thread all might find that interesting. Regards, Anthony Giorgianni Reply to this post...

Posted by Phil Corso

on 21 August, 2010 - 1:00 pm

Anthony... not bad for a lay person. Furthermore I'll give you a "plus" since your name ends in a vowel! If are looking for further enlightenment you might want to peruse Control.Com Thread # 1026242714 Regards, Phil Corso Reply to this post...

Posted by Anthony Giorgianni on 23 August, 2010 - 1:12 pm Thanks Phil! I'll check that out. Reply to this post...

Posted by david garnett on 15 December, 2010 - 9:32 am Hello there, With reference to the text below and my understanding of VAr's can someone explain how by increasing machine (rotor) excitation current to increase terminal voltage above the "system" voltage i.e. over-excitation a lagging power factor is achieved. My understanding is that by attempting to increase generator terminal voltage it is the magnitude of the voltage sine wave that is increased? this is different to pf / var production as there is no phase shift between current and voltage sine waves- just an increased magnitude of the voltage waveform, what actually generates the shift - the same question is true for the leading region (under-excited)? "If we think of the induction of the magnetic field on the rotor of the induction motor as needing "power" and we call that reactive power, then we can think of reactive power as being consumed, in the same was as real power is consumed. We can measure the amount of power required to induce the magnetic field on the induction motor rotor in VArs. And, to counter the effect of the phase shift on the system of lots and lots of induction motors and transformers (which also induce magnetic fields on secondary windings) we can produce reactive power to reduce the phase shift and maintain the AC power system's ability to provide power. We can produce reactive power to "compensate" for the inductive load on the system primary by increasing excitation current to the rotors of synchronous generators over and above the amount required to maintain the generator terminal voltage equal to the voltage of the grid to which the generator is connected. This causes reactive power, called VArs to flow out of the generator terminals on to the AC power system, reducing the phase shift and supporting the AC power system's ability to transmit real power. So, VArs are "required" or "consumed" to induce the magnetic field on the induction motor rotors commonly used everywhere, and to increase or decrease voltage through transformers used to distribute AC power. The effect of VARs on the system is to shift the AC voltageand current sine waves out of phase with each other. If they get too far out of phase, the

ability of the AC power system to supply power is reduced. VARs can be produced by synchronous generators--but since that requires DC power, and that DC power usually comes from the AC power system, that power is not available for sale to consumers. Power factor correction capacitors can be used to help with controlling the phase angle between the AC voltage- and current sine waves, but they are usually expensive and have their own idiosyncrasy"
Power in an electric circuit is the rate of flow of energy past a given point of the circuit. In alternating current circuits, energy storage elements such as inductance and capacitance may result in periodic reversals of the direction of energy flow. The portion of power that, averaged over a complete cycle of the AC waveform, results in net transfer of energy in one direction is known as real power. The portion of power due to stored energy, which returns to the source in each cycle, is known as reactive power.

Usually hidden from the unaided eye, the blinking of (non-incandescent) lighting powered by AC mains is revealed in this motion-blurred long exposure of city lights. Light is emitted twice each cycle

In a simple alternating current (AC) circuit consisting of a source and a linear load, both the current and voltage are sinusoidal. If the load is purely resistive, the two quantities reverse their polarity at the same time. At every instant the product of voltage and current is positive, indicating that the direction of energy flow does not reverse. In this case, only real power is transferred. If the loads are purely reactive, then the voltage and current are 90 degrees out of phase. For half of each cycle, the product of voltage and current is positive, but on the other half of the cycle, the product is negative, indicating that on average, exactly as much energy flows toward the load as flows back. There is no net energy flow over one cycle. In this case, only reactive energy flowsthere is no net transfer of energy to the load. Practical loads have resistance, inductance, and capacitance, so both real and reactive power will flow to real loads. Power engineers measure apparent power as the magnitude of the vector sum of real and reactive power. Apparent power is the product of the root-meansquare of voltage and current. Engineers care about apparent power, because even though the current associated with reactive power does no work at the load, it heats the wires, wasting energy. Conductors,

transformers and generators must be sized to carry the total current, not just the current that does useful work. Another consequence is that adding the apparent power for two loads will not accurately give the total apparent power unless they have the same displacement between current and voltage (the same power factor). Conventionally, capacitors are considered to generate reactive power and inductors to consume it. If a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor tend to cancel rather than add. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors (or inductors) are inserted in a circuit to partially cancel reactive power 'consumed' by the load. Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to differentiate between them):

Real power (P) or active power[1]: watt [W] Reactive power (Q): volt-ampere reactive [VAR] Complex power (S): volt-ampere [VA] Apparent Power (|S|), that is, the absolute value of complex power S: volt-ampere [VA] Phase of Voltage Relative to Current (), the angle of difference (in degrees) between voltage and current; Current lagging Voltage (Quadrant I Vector), Current leading voltage (Quadrant IV Vector)

In the diagram, P is the real power, Q is the reactive power (in this case positive), S is the complex power and the length of S is the apparent power. Reactive power does not transfer energy, so it is represented as the imaginary axis of the vector diagram. Real power moves energy, so it is the real axis. The unit for all forms of power is the watt (symbol: W), but this unit is generally reserved for real power. Apparent power is conventionally expressed in volt-amperes (VA) since it is the product of rms voltage and rms current. The unit for reactive power is expressed as var, which stands for volt-amperes reactive. Since reactive power transfers no net energy to the load, it is sometimes called "wattless" power. It does, however, serve an important function in electrical grids and its lack has been cited as a significant factor in the Northeast Blackout of 2003.[2] Understanding the relationship between these three quantities lies at the heart of understanding power engineering. The mathematical relationship among them can be represented by vectors or expressed using complex numbers, S = P + jQ (where j is the imaginary unit).

[edit] Power factor


Main article: Power factor The ratio between real power and apparent power in a circuit is called the power factor. It's a practical measure of the efficiency of a power distribution system. For two systems

transmitting the same amount of real power, the system with the lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the load. These higher currents produce higher losses and reduce overall transmission efficiency. A lower power factor circuit will have a higher apparent power and higher losses for the same amount of real power. The power factor is one when the voltage and current are in phase. It is zero when the current leads or lags the voltage by 90 degrees. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle of current with respect to voltage. Purely capacitive circuits cause reactive power with the current waveform leading the voltage wave by 90 degrees, while purely inductive circuits cause reactive power with the current waveform lagging the voltage waveform by 90 degrees. The result of this is that capacitive and inductive circuit elements tend to cancel each other out. Where the waveforms are purely sinusoidal, the power factor is the cosine of the phase angle () between the current and voltage sinusoid waveforms. Equipment data sheets and nameplates often will abbreviate power factor as "cos " for this reason. Example: The real power is 700 W and the phase angle between voltage and current is 45.6. The power factor is cos(45.6) = 0.700. The apparent power is then: 700 W / cos(45.6) = 1000 VA.[3]

[edit] Reactive power


Main article: Volt-ampere reactive Reactive power flow on the alternating current transmission system is needed to support the transfer of real power over the network. In alternating current circuits energy is stored temporarily in inductive and capacitive elements, which can result in the periodic reversal of the direction of energy flow. The portion of power flow remaining after being averaged over a complete AC waveform is the real power, which is energy that can be used to do work (for example overcome friction in a motor, or heat an element). On the other hand the portion of power flow that is temporarily stored in the form of electric or magnetic fields, due to inductive and capacitive network elements, and returned to source is known as the reactive power. AC connected devices that store energy in the form of a magnetic field include inductive devices called reactors, which consist of a large coil of wire. When a voltage is initially placed across the coil a magnetic field builds up, and it takes a period of time for the current to reach full value. This causes the current to lag the voltage in phase, and hence these devices are said to absorb reactive power. A capacitor is an AC device that stores energy in the form of an electric field. When current is driven through the capacitor, it takes a period of time for charge to build up to produce the full voltage difference. On an AC network the voltage across a capacitor is always changing the capacitor will oppose this change causing the voltage to lag behind the current. In other words the current leads the voltage in phase, and hence these devices are said to generate reactive power.

Energy stored in capacitive or inductive elements of the network give rise to reactive power flow. Reactive power flow strongly influences the voltage levels across the network. Voltage levels and reactive power flow must be carefully controlled to allow a power system to be operated within acceptable limits.

[edit] Reactive power control


Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.95 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation: Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors The System gain is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day. To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.

[edit] Unbalanced polyphase systems


While real power and reactive power are well defined in any system, the definition of apparent power for unbalanced polyphase systems is considered to be one of the most controversial topics in power engineering. Originally, apparent power arose merely as a figure of merit. Major delineations of the concept are attributed to Stanley's Phenomena of Retardation in the Induction Coil (1888) and Steinmetz's Theoretical Elements of Engineering (1915). However, with the development of three phase power distribution, it became clear that the definition of apparent power and the power factor could not be applied to unbalanced polyphase systems. In 1920, a "Special Joint Committee of the AIEE and the National Electric Light Association" met to resolve the issue. They considered two definitions:

that is, the quotient of the sums of the real powers for each phase over the sum of the apparent power for each phase.

that is, the quotient of the sums of the real powers for each phase over the magnitude of the sum of the complex powers for each phase. The 1920 committee found no consensus and the topic continued to dominate discussions. In 1930 another committee formed and once again failed to resolve the question. The transcripts of their discussions are the lengthiest and most controversial ever published by the AIEE (Emanuel, 1993). Further resolution of this debate did not come until the late 1990s.

[edit] Basic calculations using real numbers


A perfect resistor stores no energy, so current and voltage are in phase. Therefore there is no reactive power and P = S. Therefore for a perfect resistor

For a perfect capacitor or inductor there is no net power transfer, so all power is reactive. Therefore for a perfect capacitor or inductor:

Where X is the reactance of the capacitor or inductor. If X is defined as being positive for an inductor and negative for a capacitor then we can remove the modulus signs from Q and X and get

[edit] Multiple frequency systems


Since an RMS value can be calculated for any waveform, apparent power can be calculated from this. For real power it would at first appear that we would have to calculate loads of product terms and average all of them. However if we look at one of these product terms in more detail we come to a very interesting result.

however the time average of a function of the form cos(t+k) is zero provided that is nonzero. Therefore the only product terms that have a nonzero average are those where the frequency of voltage and current match. In other words it is possible to calculate real (average) power by simply treating each frequency separately and adding up the answers. Furthermore, if we assume the voltage of the mains supply is a single frequency (which it usually is), this shows that harmonic currents are a bad thing. They will increase the rms current (since there will be non-zero terms added) and therefore apparent power, but they will have no effect on the real power transferred. Hence, harmonic currents will reduce the power factor. Harmonic currents can be reduced by a filter placed at the input of the device. Typically this will consist of either just a capacitor (relying on parasitic resistance and inductance in the supply) or a capacitor-inductor network. An active power factor correction circuit at the input would generally reduce the harmonic currents further and maintain the power factor closer to unity.

In a simple alternating current (AC) circuit consisting of a source and a linear load, both the current and voltage are sinusoidal. If the load is purely resistive, the two quantities reverse their polarity at the same time. At every instant the product of voltage and current is positive, indicating that the direction of energy flow does not reverse. In this case, only real power is transferred. If the loads are purely reactive, then the voltage and current are 90 degrees out of phase. For half of each cycle, the product of voltage and current is positive, but on the other half of the cycle, the product is negative, indicating that on average, exactly as much energy flows toward the load as flows back. There is no net energy flow over one cycle. In this case, only reactive energy flowsthere is no net transfer of energy to the load. Practical loads have resistance, inductance, and capacitance, so both real and reactive power will flow to real loads. Power engineers measure apparent power as the magnitude of the vector sum of real and reactive power. Apparent power is the product of the root-meansquare of voltage and current. Engineers care about apparent power, because even though the current associated with reactive power does no work at the load, it heats the wires, wasting energy. Conductors, transformers and generators must be sized to carry the total current, not just the current that does useful work. Another consequence is that adding the apparent power for two loads will not accurately give the total apparent power unless they have the same displacement between current and voltage (the same power factor). Conventionally, capacitors are considered to generate reactive power and inductors to consume it. If a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor tend to cancel rather than add. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors (or inductors) are inserted in a circuit to partially cancel reactive power 'consumed' by the load.

Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to differentiate between them):

Real power (P) or active power[1]: watt [W] Reactive power (Q): volt-ampere reactive [VAR] Complex power (S): volt-ampere [VA] Apparent Power (|S|), that is, the absolute value of complex power S: volt-ampere [VA] Phase of Voltage Relative to Current (), the angle of difference (in degrees) between voltage and current; Current lagging Voltage (Quadrant I Vector), Current leading voltage (Quadrant IV Vector)

In the diagram, P is the real power, Q is the reactive power (in this case positive), S is the complex power and the length of S is the apparent power. Reactive power does not transfer energy, so it is represented as the imaginary axis of the vector diagram. Real power moves energy, so it is the real axis. The unit for all forms of power is the watt (symbol: W), but this unit is generally reserved for real power. Apparent power is conventionally expressed in volt-amperes (VA) since it is the product of rms voltage and rms current. The unit for reactive power is expressed as var, which stands for volt-amperes reactive. Since reactive power transfers no net energy to the load, it is sometimes called "wattless" power. It does, however, serve an important function in electrical grids and its lack has been cited as a significant factor in the Northeast Blackout of 2003.[2] Understanding the relationship between these three quantities lies at the heart of understanding power engineering. The mathematical relationship among them can be represented by vectors or expressed using complex numbers, S = P + jQ (where j is the imaginary unit).

[edit] Power factor


Main article: Power factor The ratio between real power and apparent power in a circuit is called the power factor. It's a practical measure of the efficiency of a power distribution system. For two systems transmitting the same amount of real power, the system with the lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the load. These higher currents produce higher losses and reduce overall transmission efficiency. A lower power factor circuit will have a higher apparent power and higher losses for the same amount of real power. The power factor is one when the voltage and current are in phase. It is zero when the current leads or lags the voltage by 90 degrees. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle of current with respect to voltage. Purely capacitive circuits cause reactive power with the current waveform leading the voltage wave by 90 degrees, while purely inductive circuits cause reactive power with the current

waveform lagging the voltage waveform by 90 degrees. The result of this is that capacitive and inductive circuit elements tend to cancel each other out. Where the waveforms are purely sinusoidal, the power factor is the cosine of the phase angle () between the current and voltage sinusoid waveforms. Equipment data sheets and nameplates often will abbreviate power factor as "cos " for this reason. Example: The real power is 700 W and the phase angle between voltage and current is 45.6. The power factor is cos(45.6) = 0.700. The apparent power is then: 700 W / cos(45.6) = 1000 VA.[3]

[edit] Reactive power


Main article: Volt-ampere reactive Reactive power flow on the alternating current transmission system is needed to support the transfer of real power over the network. In alternating current circuits energy is stored temporarily in inductive and capacitive elements, which can result in the periodic reversal of the direction of energy flow. The portion of power flow remaining after being averaged over a complete AC waveform is the real power, which is energy that can be used to do work (for example overcome friction in a motor, or heat an element). On the other hand the portion of power flow that is temporarily stored in the form of electric or magnetic fields, due to inductive and capacitive network elements, and returned to source is known as the reactive power. AC connected devices that store energy in the form of a magnetic field include inductive devices called reactors, which consist of a large coil of wire. When a voltage is initially placed across the coil a magnetic field builds up, and it takes a period of time for the current to reach full value. This causes the current to lag the voltage in phase, and hence these devices are said to absorb reactive power. A capacitor is an AC device that stores energy in the form of an electric field. When current is driven through the capacitor, it takes a period of time for charge to build up to produce the full voltage difference. On an AC network the voltage across a capacitor is always changing the capacitor will oppose this change causing the voltage to lag behind the current. In other words the current leads the voltage in phase, and hence these devices are said to generate reactive power. Energy stored in capacitive or inductive elements of the network give rise to reactive power flow. Reactive power flow strongly influences the voltage levels across the network. Voltage levels and reactive power flow must be carefully controlled to allow a power system to be operated within acceptable limits.

[edit] Reactive power control


Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.95 power factor leading at the designated terminals. The system operator will perform

switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation: Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors The System gain is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day. To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.

[edit] Unbalanced polyphase systems


While real power and reactive power are well defined in any system, the definition of apparent power for unbalanced polyphase systems is considered to be one of the most controversial topics in power engineering. Originally, apparent power arose merely as a figure of merit. Major delineations of the concept are attributed to Stanley's Phenomena of Retardation in the Induction Coil (1888) and Steinmetz's Theoretical Elements of Engineering (1915). However, with the development of three phase power distribution, it became clear that the definition of apparent power and the power factor could not be applied to unbalanced polyphase systems. In 1920, a "Special Joint Committee of the AIEE and the National Electric Light Association" met to resolve the issue. They considered two definitions:

that is, the quotient of the sums of the real powers for each phase over the sum of the apparent power for each phase.

that is, the quotient of the sums of the real powers for each phase over the magnitude of the sum of the complex powers for each phase. The 1920 committee found no consensus and the topic continued to dominate discussions. In 1930 another committee formed and once again failed to resolve the question. The transcripts of their discussions are the lengthiest and most controversial ever published by the AIEE (Emanuel, 1993). Further resolution of this debate did not come until the late 1990s.

[edit] Basic calculations using real numbers

A perfect resistor stores no energy, so current and voltage are in phase. Therefore there is no reactive power and P = S. Therefore for a perfect resistor

For a perfect capacitor or inductor there is no net power transfer, so all power is reactive. Therefore for a perfect capacitor or inductor:

Where X is the reactance of the capacitor or inductor. If X is defined as being positive for an inductor and negative for a capacitor then we can remove the modulus signs from Q and X and get

[edit] Multiple frequency systems


Since an RMS value can be calculated for any waveform, apparent power can be calculated from this. For real power it would at first appear that we would have to calculate loads of product terms and average all of them. However if we look at one of these product terms in more detail we come to a very interesting result.

however the time average of a function of the form cos(t+k) is zero provided that is nonzero. Therefore the only product terms that have a nonzero average are those where the frequency of voltage and current match. In other words it is possible to calculate real (average) power by simply treating each frequency separately and adding up the answers. Furthermore, if we assume the voltage of the mains supply is a single frequency (which it usually is), this shows that harmonic currents are a bad thing. They will increase the rms current (since there will be non-zero terms added) and therefore apparent power, but they will have no effect on the real power transferred. Hence, harmonic currents will reduce the power factor.

Harmonic currents can be reduced by a filter placed at the input of the device. Typically this will consist of either just a capacitor (relying on parasitic resistance and inductance in the supply) or a capacitor-inductor network. An active power factor correction circuit at the input would generally reduce the harmonic currents further and maintain the power factor closer to unity.

The complex power is the vector sum of real and reactive power. The apparent power is the magnitude of the complex power. Real power (P) Reactive power (Q) Complex power (S) Apparent Power (|S|) Phase of Current (