Hot water operated two stage lithium bromide absorption chiller is a kind of large-size industrial facility with hot water as the driving energy and lithium bromide solution as the absorbent and water as refrigerant. Hot water two stage units, using hot water as the energy source, not only reduces greatly the cost for electricity and operation fees in regions where there are rich hot water resources, but also compensates the peak-valley load difference. When the hot summer rolls in, shortage of electric power will poses a great worry for various cities. Concentrated consumption of power by air-conditioners is the sticking point for such a seasonal problem, for which, hot water operated two stage chillers offer an attractive solution. Shuangliang hot water operated two stage chillers are widely applied in industries, such as precision machinery manufacturing, instruments & meters, aviation & aerospace, textiles, electronics, electric power, metallurgy, pharmaceuticals, cigarettes, chemicals, hospitals, food, etc. By utilizing dozens of patented technologies with features of extremely high energy efficiency and outstanding environmental effects, in addition to her customerservice experience of over 20 years, Shuangliang guarantees to reward her users with optimal returns.
0
Working Principle
Cooling Cycle
13
Chilled water inlet termperature (I) Chilled water outlet temperature (C,I,A)
Condenser (1) Condenser (2)
Cooling water inlet temperature (C,I,A) Hot water inlet temperature (C.I,A) Hot water outlet temperature (I) Concentrated solution spray temperature (C.I) Concentrated solution outlet temperature (C.I) Concentrated temperature (C.I.A) Evaporation temperature (I.A) De-crystallization pipe temperature (I.A) Chilled water flow switch (A) Vacuum pressure (I) Generator pressure (I,A) (C)-Control (A)-Alarm (I)-Indication Hot water (High temperature) Hot water (Low temperature) Strong solution Weak solutian Cooling watef Chilled water Liquid refrigerant Refrigerant vapor
Vacuum Pump Chilled Water in Cooling Water in Heat Exchanger (2)
4 8
Regulating Valve
Hot Water in
Supplied by Customer
7 6
1 12 10
Evaporator (2) Evaporator (1) Absorber (2) Automatic Decrystallization Pipe Absorber (1)
2 11
Regulating Valve
Regulating Valve
Oil Trap
By-pass Valve
Sampling Valve
Technical Specifications
Table of Technical Parameters (SI)
1488H2 1323H2 1157H2 165H2 198H2 265H2 331H2 413H2 496H2 579H2 661H2 744H2 827H2 992H2 99H2 HSC(130/68)HSB(120/68)kW Cooling capacity 10 kcal/h USRt Inlet/outlet temp. Flow Pressure drop Piping dia. (DN) Inlet/outlet temp. Flow Pressure drop Piping dia. (DN) Outlet temp. Consump- Inlet temp. 130 tion Inlet temp. 120 Pressure drop Piping dia.(DN) Power supply Total current Electric power Length Width Height Shipping weight Operating weight t mm A kW 21 5.15 21 5.15 24 5.95 25.8 6.35 27.1 6.85 Electrical data Hot water m3/H mH2O mm m3/h mH2O mm ton/h mH2O mm 6.1 7.3 10 40 10.2 12.2 10 50 12.2 14.6 10 50 16.3 19.4 11 65 20.4 24.3 11 80 25.5 30.4 11 80 30.6 36.5 13 80 114 8 125 189 8 150 227 8 200 303 6 200 378 8 250 473 8 250 567 10 300 60 12 100 100 12 125 120 12 125 160 11 150 200 7 150 250 7 200 300 8 200 Chilled capacity
4
350 30 99
580 50 165
700 60 198
930 80 265
1160 1450 1740 2040 2330 2620 2910 3490 4070 4650 5230 100 331 125 413 150 496 175 579 127 350 8 200 3238 662 10 300 68 35.7 42.5 13 80 40.8 48.6 11 100 45.9 54.7 11 100 51 60.8 14 100 61.2 72.9 14 125 71.4 85.1 13 125 81.6 91.8 756 12 300 851 12 350 945 10 350 1134 1323 1512 1701 10 400 13 450 14 450 15 450 400 10 250 450 10 250 500 13 250 600 13 300 700 15 300 800 12 350 900 13 350 200 661 225 744 250 827 300 992 350 400 450
Note
(1) Chilled water outlet temperature minimum value of 5. (2) Cooling capacity can be adjusted in the range of 20-100%, and chilled water in the range of 60-120%. (3) On the chilled/hot and cooling water side scale factor will be 0.086m2 K/kW(0.0001m2 h /kcal). (4) Hot, chilled and cooling water box has the maximum pressure bearing capacity: 0.8MPa for standard type, and 1.6MPa for high pressure type. (5) The chiller is transported with rack of 180mm in height for chiller less than units 413, and additional height of rack of 60mm for the units 496 and above. (6) Shipping weight of chiller is the weight, including the weight of rack, but not the weight of solution, The solution needed for the chiller is charged, if the chiller had been test run in the company. The chiller should be handled with care for the 60% of charged solution is still left in it, though part of solution is discharged. The chiller should be kept balanced during handling.
3-380VAC-50Hz 28.2 7.25 28.8 7.65 32.3 8.05 33.3 8.65 36 38.7 40.5 44.2 47.1 51.6
4150 4144 4242 4610 5070 5190 5595 5760 6147 6270 7110 7160 7860 8722 9542 1950 2023 2086 2170 2275 2492 2430 '2632 2700 2856 2912 3226 3268 3146 3176 2690 2698 2852 2913 2857 3167 3295 3480 3654 3852 3852 4090 4225 4350 4350 6.8 8.3 8.4 10.9 9.3 12.2 11.4 15.0 15.3 19.8 17.4 23.1 19.5 26.2 22.2 30 25.9 34.7 30.8 40.7 34.6 45.2 40.6 53.4 45.8 59.6 52.5 66.8 60.6 75.8