CONTENTS
CURRENT TRANSFORMER
RECOMMENDATIONS FOR THE USE OF TABLES AND TECHNICALS NOTES PANEL TYPE CRM REFERENCED TYPES ARJP1/N2 F ARJP2/N2 F ARJP1/N1 F and ARJP1/N2 F ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 7 Page 11 Page 8 and 9 Page 12 and 13 Page 3,4,5 and 6
CONFIGURED TYPES
PANEL TYPE QMC REFERENCED TYPES CONFIGURED TYPES ARJP1/N2 F ARJP1/N1 F and ARJP1/N2 F Page 7 Page 8 and 9
PANEL TYPE DMV-A, DMV-D, IMC REFERENCED TYPES CONFIGURED TYPES ARJP2/N2 F ARJP1/N1 F and ARJP1/N2 F ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 11 Page 8 and 9 Page 12 and 13
DM1-A, DM1-D, DM1-W, DM1-Z, GBC-A, GBC-B, DMV-A, DMV-D ARJP3/N2 F ARJP3/N1 F, ARJP3/N2 F and ARJP3/N3 F Page 15 Page 16
PANELS TYPE DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B REFERENCED TYPES CONFIGURED TYPES ARM3/N2 F ARM3/N1 F and ARM3/N2 F Page 18 Page 19
NOTE:
N1, N2 and N3 MEAN THE NUMBER OF SECONDARIES F MEANS THAT THERE IS NOT BASE PLATE
pag. 2/20
CURRENT TRANSFORMERS
_______________
CHECK NEEDS AND NECESSARY INFORMATION ACCURATELY USE EQUIPMENT MARKED AS REFERENCE CHECK READLY AVAILABLE FEASIBILITY SECTIONS DIRECTLY TO APPLY KEYS TO FEASIBILITY TABLES CORRECTLY, PLEASE SEE ON PAGE 4 USE ALSO ELONET TO CHECK FEASIBILITY CONSULT US IF FEASIBILITY RANGE IS NOT AVAILABLE OR FOR OTHERS CHARACTERISTICS
pag. 3/20
1)
2)
3)
K=
example:
Ipn
4)
5)
Check feasibility
A possible current transformer will feature the performances shown in the columns identified by boxes : For perotection secondary is true, only for choosing in the catalogue, the following formule:
VA x FL = constant
example: 10VA 5P10 ( VA x FL= 10 x 10= 100 ) >> 5VA 5P20 ( VA x FL= 5 x 20= 100 )
pag. 4/20
SINGLE RATIO
P1 P2
P1
P2
P1
P2
S1
S2
1S1
1S2
2S1
2S2
1S1
1S2 2S1 n da
2S2
3S1 dn
3S2
F WARNING !
The secondary open winding of a CT is dangereus! The unused secondary windings of a CT must be short-circuited.
pag. 5/20
Current transformer with DOUBLE RATIO through primary coulping. types ARM3
Burden values are the same for both ratios.
P1 C1 C2 P2
P1
C1
C2
P2
Current transformer with DOUBLE RATIO through connection on secondary. types ARJP1, ARJP2, ARJP3
P1
P2
P1
P2
S1
S2
S3
1S1
1S2
1S3 2S1
2S2
2S3
H
Burden values are different for each of the two ratios
F WARNING !
The secondary open winding of a CT is dangereus! The unused secondary windings of a CT must be short-circuited.
pag. 6/20
Dimensions Characteristics
Drawing n H 103441 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz
15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10
2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20
CONFIGURED CURRENT TRANSFORMER Type ARJP1/N1 F - ARJP1/N2 F Single Primary Ratio SR Panels type CRM, DMV-A, DMV-D, IMC, QMC Dimensions Drawing n H 103441
Characteristics Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Table of options:
N of secondaries for CT
1
ARJP1/N1 F
2
ARJP1/N2 F
1st measure secondary
STANDARD TYPE
Classe 0,5 Fs = 10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 2nd protection secondary
"K"
K=Ith/Ipn Ith max 25 kA for 1s
Ipn
Rated primary current [A]
measure secondary
protection secondary
Cl. 5P Fl=10 VA
Cl. 5P Fl=10 VA
CONFIGURED CURRENT TRANSFORMER Type ARJP1/N1 F Double Primary Ratio DR Panels type CRM, DMV-A, DMV-D, IMC, QMC Dimensions Characteristics Drawing n H 103441 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.
Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio . Values of outputs are gived for the smaller ratio, for the high ratio they are the double. Table of options:
N of secondaries for CT
1
ARJP1/N1 F
STANDARD TYPE
alternatively
"K"
K=Ith/Ipn Ith max 25 kA for 1s
Ipn
Rated primary current [A]
measure secondary
protection secondary
Class 0,5 Fs = 10 VA
Class 5P Fl = 10 VA
DR 10-20 to 400-800 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200 10-20 to 75-150 10-20 to 50-100
7 , 5 10 15 2 0 3 0 5 0 5 7,5 1 0 1 5 2 0 30 50
REFERENCED CURRENT TRANSFORMERS Type ARJP2/N2 F Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz
2,5VA 5P20
CONFIGURED CURRENT TRANSFORMER Type ARJP2/N1 F - ARJP2/N2 F - ARJP2/N3 F Single Primary Ratio SR Panels type CRM, DMV-A, DMV-D, IMC Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A.
Table of options:
n of secondaries for CT
1
ARJP2/N1 F
2
ARJP2/N2 F
3
ARJP2/N3 F
1st measure sec.
STANDARD TYPE
Class 0,5 Fs = 10 VA
5 10 15 20 30 1st measure secondary 2nd protection sec.
Class 0,5 Fs = 10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 2nd protection secondary
Class 5P Fl = 10 VA
5 7,5 10 15 3rd protection sec.
"K"
K=Ith/Ipn Ith max 25 kA for 1sec.
Ipn
Rated primary current [A]
measure secondary
protection secondary
Class 0,5 Fs = 10 VA
Class 5P Fl = 10 VA
5
Class 5P FI = 10 VA
5 7,5 5 10 10 15 20 30 50 5
Class 5P Fl = 15 VA
5 7,5 10 15
7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5
CONFIGURED CURRENT TRANSFORMER Type ARJP2/N1 F - ARJP2/N2 F Double Primary Ratio DR Panels type CRM, DMV-A, DMV-D, IMC Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.
Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio . Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:
N of secondaries for CT
1
ARJP2/N1 F
2
ARJP2/N2 F
1st measure secondary
STANDARD TYPE
"K"
K=Ith/Ipn Ith max 25 kA for 1s
Ipn
Rated primary current [A]
measure secondary
protection secondary
Cl. 5P Fl=10 VA
5 7,5 1 0 1 5 2 0 3 0 5 0 5 5
Cl. 5P Fl=10 VA
5 7,5 5 10 10 15 20 30 50
DR 10-20 to 400-800 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200 10-20 to 75-150 10-20 to 50-100 10-20 to 50-100
REFERENCED CURRENT TRANSFORMERS Type ARJP3/N2 F Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A, GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A
Dimensions
Drawing n H 103443
Characteristics Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz
CONFIGURED CURRENT TRANSFORMER Type ARJP3/N1 F - ARJP3/N2 F - ARJP3/N3 F Single and Double Primary Ratio Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A, GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A Dimensions Characteristics Drawing n H 103443 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.
Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:
N of secondaries for CT
1
ARJP3/N1 F
2
ARJP3/N2 F
3
ARJP3/N3 F
1st measure sec.
STANDARD TYPE
Class 0,5 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 2nd protection secondary
Cl. 5P Fl=10 VA
5 7,5 10 15 3rd protection sec.
Ipn
Rated primary current [A]
measure secondary
protection secondary
Cl. 5P Fl=10 VA
5
Cl. 5P Fl=10 VA
5 7,5 5 10 10 15 20 30 50 5
Cl. 5P Fl=15 VA
5 7,5 10 15
SR
DR
7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5
REFERENCED CURRENT TRANSFORMERS Type ARM3/N2 F Panel type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B Dimensions Characteristics Drawing n H 103005 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz Double primary ratio through primary coupling.
CONFIGURED CURRENT TRANSFORMER Type ARM3/N1 F - ARM3/N2 F Single and Double Primary Ratio Panels type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
Dimensions Characteristics
Drawing n H 103005 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A Double primary ratio through primary coupling.
Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio .
Table of options:
N of secondaries for CT
1
ARM3/N1 F
2
ARM3/N2 F
1st measure secondary
STANDARD TYPE
Cl 0,5 Fs=10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 2nd protection secondary
"K"
K=Ith/Ipn Ith max 25 kA for 1s
Ipn
Rated primary current [A]
measure secondary
protection secondary
Cl 0,5 Fs=10 VA
Cl 5P Fl=10 VA
Cl 5P Fl=10 VA
DR 10-20 to 400-800 10-20 to 300-600 10-20 to 300-600 10-20 to 200-400 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200