Current Transformers SM6 24 cubicles

Feasibility range and referenced types

Catalogue 2004
Number: C019 rev. 1
pag. 1/20

CONTENTS

CURRENT TRANSFORMER
RECOMMENDATIONS FOR THE USE OF TABLES AND TECHNICALS NOTES PANEL TYPE CRM REFERENCED TYPES ARJP1/N2 F ARJP2/N2 F ARJP1/N1 F and ARJP1/N2 F ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 7 Page 11 Page 8 and 9 Page 12 and 13 Page 3,4,5 and 6

CONFIGURED TYPES

PANEL TYPE QMC REFERENCED TYPES CONFIGURED TYPES ARJP1/N2 F ARJP1/N1 F and ARJP1/N2 F Page 7 Page 8 and 9

PANEL TYPE DMV-A, DMV-D, IMC REFERENCED TYPES CONFIGURED TYPES ARJP2/N2 F ARJP1/N1 F and ARJP1/N2 F ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F Page 11 Page 8 and 9 Page 12 and 13

PANELS TYPE 1250A REFERENCED TYPES CONFIGURED TYPES

DM1-A, DM1-D, DM1-W, DM1-Z, GBC-A, GBC-B, DMV-A, DMV-D ARJP3/N2 F ARJP3/N1 F, ARJP3/N2 F and ARJP3/N3 F Page 15 Page 16

PANELS TYPE DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B REFERENCED TYPES CONFIGURED TYPES ARM3/N2 F ARM3/N1 F and ARM3/N2 F Page 18 Page 19

NOTE:

N1, N2 and N3 MEAN THE NUMBER OF SECONDARIES F MEANS THAT THERE IS NOT BASE PLATE

pag. 2/20

CURRENT TRANSFORMERS

PREFERABLY USE the equipment selected and marked as REFERENCED

RECOMMENDATIONS FOR THE USE OF THE FEASIBILITY AND COMPUTATION SUPPORTS

_______________
CHECK NEEDS AND NECESSARY INFORMATION ACCURATELY USE EQUIPMENT MARKED AS REFERENCE CHECK READLY AVAILABLE FEASIBILITY SECTIONS DIRECTLY TO APPLY KEYS TO FEASIBILITY TABLES CORRECTLY, PLEASE SEE ON PAGE 4 USE ALSO ELONET TO CHECK FEASIBILITY CONSULT US IF FEASIBILITY RANGE IS NOT AVAILABLE OR FOR OTHERS CHARACTERISTICS

pag. 3/20

KEYS TO THE VARIOUS TABLES TO DEFINE FEASIBILITY

1)

Define Ipn rated primary current


Use primary values defined by standard (IEC): 10, 12,5, 20, 25, 30, 40, 50, 60 and 75 A and their decimal multiples.

2)

Define Ith rated short-time thermal current for 1 second


Short-circuit current usually lasts 1 second. Should this value be different (equal to a lenght "t"), calculate the following:

Ith (for 1 sec.) = Ith x t


example: 25 kA for 3 sec. >> 25 x 3 = 43,3 kA for 1 sec.

3)

Calculate coefficient "K"


The above reperesents the key to the various tables

Ith for 1 sec.

K=
example:

Ipn

Ipn = 100 A , Ith = 12,5 kA 1 sec. >> K = 12500 / 100 = 125

4)

Finding position on the table


Locate column "K" and stop on the line corresponding to a value higher than K. example: K calculate value = 125 >> ligne K = 150

5)

Check feasibility
A possible current transformer will feature the performances shown in the columns identified by boxes : For perotection secondary is true, only for choosing in the catalogue, the following formule:

VA x FL = constant
example: 10VA 5P10 ( VA x FL= 10 x 10= 100 ) >> 5VA 5P20 ( VA x FL= 5 x 20= 100 )

pag. 4/20

TECHNICAL NOTES Diagrams of the terminals markings according to IEC standard.

SINGLE RATIO
P1 P2

P1

P2

P1

P2

S1

S2

1S1

1S2

2S1

2S2

1S1

1S2 2S1 n da

2S2

3S1 dn

3S2

CT with ONE SECONDARY WINDING

CT with TWO SECONDARY WINDINGS

CT with THREE SECONDARY WINDINGS

F WARNING !
The secondary open winding of a CT is dangereus! The unused secondary windings of a CT must be short-circuited.
pag. 5/20

Current transformer with DOUBLE RATIO through primary coulping. types ARM3
Burden values are the same for both ratios.
P1 C1 C2 P2

SERIAL PRIMARY COUPLING LOW RATIO

P1

C1

C2

P2

PARALLEL PRIMARY COUPLING HIGH RATIO

Current transformer with DOUBLE RATIO through connection on secondary. types ARJP1, ARJP2, ARJP3

P1

P2

P1

P2

S1

S2

S3

1S1

1S2

1S3 2S1

2S2

2S3

CT with ONE SECONDARY WINDING


S1-S2 LOW RATIO S1-S3 HIGH RATIO

CT with TWO SECONDARY WINDINGS


1S1-1S2 2S1- 2S2 1S1-1S3 2S1- 2S3 LOW RATIO HIGH RATIO

H
Burden values are different for each of the two ratios

F WARNING !
The secondary open winding of a CT is dangereus! The unused secondary windings of a CT must be short-circuited.
pag. 6/20

REFERENCED CURRENT TRANSFORMERS Type ARJP1/N2 F Panel type CRM - QMC

Dimensions Characteristics

Drawing n H 103441 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz

CTs type ARJP1/N2F


Reference number 51238639F0 51238640F0 51238641F0 51238643F0 51238644F0 51238645F0 51238646F0 51238647F0 Ratio (A/A) 10/5-5 20/5-5 30/5-5 50/5-5 75/5-5 100/5-5 150/5-5 200/5-5 Short-time current I th t (kA) (s) 1,2 2,4 3,6 6 10 10 10 10 1 1 1 1 1 1 1 1 1st secondary 2nd secondary

15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10 15 VA cl. 0,5 Fs<10

2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20 2,5 VA 5P20

For others characteristics see next page.


pag. 7/20

CONFIGURED CURRENT TRANSFORMER Type ARJP1/N1 F - ARJP1/N2 F Single Primary Ratio SR Panels type CRM, DMV-A, DMV-D, IMC, QMC Dimensions Drawing n H 103441

Characteristics Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Table of options:
N of secondaries for CT

1
ARJP1/N1 F

2
ARJP1/N2 F
1st measure secondary

STANDARD TYPE

Classe 0,5 Fs = 10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 2nd protection secondary

"K"
K=Ith/Ipn Ith max 25 kA for 1s

Ipn
Rated primary current [A]

measure secondary

protection secondary

Cl. 0,5 Fs=10 VA

Cl. 5P Fl=10 VA

Cl. 5P Fl=10 VA

SR 10 to 800 10 to 150 10 to 100 10 to 100 10 to 75 10 to 50

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50

100 150 200 250 300 400

For others characteristics please contact us.


pag. 8/20

CONFIGURED CURRENT TRANSFORMER Type ARJP1/N1 F Double Primary Ratio DR Panels type CRM, DMV-A, DMV-D, IMC, QMC Dimensions Characteristics Drawing n H 103441 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio . Values of outputs are gived for the smaller ratio, for the high ratio they are the double. Table of options:
N of secondaries for CT

1
ARJP1/N1 F

STANDARD TYPE

alternatively

"K"
K=Ith/Ipn Ith max 25 kA for 1s

Ipn
Rated primary current [A]

measure secondary

protection secondary

Class 0,5 Fs = 10 VA

Class 5P Fl = 10 VA

DR 10-20 to 400-800 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200 10-20 to 75-150 10-20 to 50-100

7 , 5 10 15 2 0 3 0 5 0 5 7,5 1 0 1 5 2 0 30 50

100 150 200 250 300 400

For others characteristics please contact us.


pag. 9/20

REFERENCED CURRENT TRANSFORMERS Type ARJP2/N2 F Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz

Panel type CRM


CTs type ARJP2/N2F
Reference number 51238223F0 Ratio (A/A) 50 / 5-5 Short-time current I th t (kA) (s) 25 1 1st secondary 2nd secondary

10VA cl.0,5 Fs10

2,5VA 5P20

Panels type DMV-A, DMV-D, IMC


CTs type ARJP2/N2F Reference number 51238223F0 51238224F0 51238225F0 51238226F0 3730519 Ratio (A/A) 50 / 5-5 100 / 5-5 200 / 5-5 400 / 5-5 600 / 5-5 Short-time current I th t (kA) 25 25 25 25 25 (s) 1 1 1 1 1 10VA cl.0,5 Fs10 15VA cl.0,5 Fs10 15VA cl.0,5 Fs10 15VA cl.0,5 Fs10 20VA cl.0,5 Fs<10 2,5VA 5P20 2,5VA 5P20 5VA 5P20 5VA 5P20 7,5VA 5P20 1st secondary 2nd secondary

For others characteristics see next page.


pag. 11/20

CONFIGURED CURRENT TRANSFORMER Type ARJP2/N1 F - ARJP2/N2 F - ARJP2/N3 F Single Primary Ratio SR Panels type CRM, DMV-A, DMV-D, IMC Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A.

Table of options:
n of secondaries for CT

1
ARJP2/N1 F

2
ARJP2/N2 F

3
ARJP2/N3 F
1st measure sec.

STANDARD TYPE

Class 0,5 Fs = 10 VA
5 10 15 20 30 1st measure secondary 2nd protection sec.

Class 0,5 Fs = 10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 2nd protection secondary

Class 5P Fl = 10 VA
5 7,5 10 15 3rd protection sec.

"K"
K=Ith/Ipn Ith max 25 kA for 1sec.

Ipn
Rated primary current [A]

measure secondary

protection secondary

Class 0,5 Fs = 10 VA

Class 5P Fl = 10 VA
5

Class 5P FI = 10 VA
5 7,5 5 10 10 15 20 30 50 5

Class 5P Fl = 15 VA
5 7,5 10 15

SR 10 to 800 10 to 300 10 to 250 10 to 200 10 to 150 10 to 100 10 to 100

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5

100 150 200 250 300 400 500

Switch to smaller type ARJP1

For others characteristics please contact us.


pag. 12/20

CONFIGURED CURRENT TRANSFORMER Type ARJP2/N1 F - ARJP2/N2 F Double Primary Ratio DR Panels type CRM, DMV-A, DMV-D, IMC Dimensions Characteristics Drawing n H 103442 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio . Values of outputs are gived for the smaller ratio, for the high ratio they are the double.

Table of options:
N of secondaries for CT

1
ARJP2/N1 F

2
ARJP2/N2 F
1st measure secondary

STANDARD TYPE

Cl. 0,5 Fs=10 VA


alternatively 5 7,5 1 0 1 5 2 0 2 0 3 0 3 0 3 0 3 0 3 0 2nd protection secondary

"K"
K=Ith/Ipn Ith max 25 kA for 1s

Ipn
Rated primary current [A]

measure secondary

protection secondary

Cl. 0,5 Fs=10 VA


7,5 1 0 1 5 2 0 3 0 5 0

Cl. 5P Fl=10 VA
5 7,5 1 0 1 5 2 0 3 0 5 0 5 5

Cl. 5P Fl=10 VA
5 7,5 5 10 10 15 20 30 50

DR 10-20 to 400-800 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200 10-20 to 75-150 10-20 to 50-100 10-20 to 50-100

100 150 200 250 300 400 500

Switch to the smaller type ARJP1

For others characteristics please contact us.


pag. 13/20

REFERENCED CURRENT TRANSFORMERS Type ARJP3/N2 F Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A, GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A

Dimensions

Drawing n H 103443

Characteristics Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz

CTs type ARJP3/N2F


Reference number 3730521 3730522 3730525 3730526 Ratio (A/A) 1000 / 5-5 1250 / 5-5 1000 / 1-1 1250 / 1-1 Short-time current I th t (kA) 25 25 25 25 (s) 1 1 1 1 30 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 10 VA 5P20 10 VA 5P20 10 VA 5P20 10 VA 5P20 1st secondary 2nd secondary

For others characteristics see next page.


pag. 15/20

CONFIGURED CURRENT TRANSFORMER Type ARJP3/N1 F - ARJP3/N2 F - ARJP3/N3 F Single and Double Primary Ratio Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A, GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A Dimensions Characteristics Drawing n H 103443 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A. Double primary ratio through connection to secondary.

Values of outputs are gived for the smaller ratio, for the high ratio they are the double.

Table of options:
N of secondaries for CT

1
ARJP3/N1 F

2
ARJP3/N2 F

3
ARJP3/N3 F
1st measure sec.

STANDARD TYPE

Cl. 0,5 Fs=10 VA


5 10 15 20 30 1st measure secondary 2nd protection sec.

Class 0,5 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 5 2nd protection secondary

Cl. 5P Fl=10 VA
5 7,5 10 15 3rd protection sec.

Ipn
Rated primary current [A]

measure secondary

protection secondary

Cl. 0,5 Fs=10 VA

Cl. 5P Fl=10 VA
5

Cl. 5P Fl=10 VA
5 7,5 5 10 10 15 20 30 50 5

Cl. 5P Fl=15 VA
5 7,5 10 15

SR

DR

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5

750 800 1000 1200 1250 400-800 500-1000 600-1200

For others characteristics please contact us.


pag. 16/20

REFERENCED CURRENT TRANSFORMERS Type ARM3/N2 F Panel type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B Dimensions Characteristics Drawing n H 103005 Standard reference IEC 60044-1 Rated highest voltage : 24 kV Rated continous thermal current 1,2 x In Frequency 50 and 60 Hz Double primary ratio through primary coupling.

CTs type ARM3/N2F


Reference number 51303122F0 51303123F0 51303124F0 51303125F0 3731090 3731092 3731094 3731096 3731097 3731098 3731099 3731100 3731101 3731102 3731103 3731104 3731105 3731708 3730426 Ratio (A/A) 40-20 / 5-1 100-50 / 5-1 200-100 / 5-1 400-200 / 5-1 10-20 / 5-5 15-30 / 5-5 20-40 / 5-5 25-50 / 5-5 25-50 / 5-5 50-100 / 5-5 50-100 / 5-5 75-150 / 5-5 75-150 / 5-5 100-200 / 5-5 100-200 / 5-5 200-400 / 5-5 200-400 / 5-5 300-600 / 5-5 300-600 / 5-5 Short-time current I th t (kA) 12,5 12,5 12,5 12,5 5 8 12,5 12,5 12,5 21 14,5 25 16 25 20 16 25 20 25 25 20 25 (s) 0,8 0,8 1 1 1 1 0,8 1 0,8 1 1 1 1 1 2 1 1 2 1 1 2 1 7,5VA 0,5s Fs<10 7,5VA 0,5s Fs<10 7,5VA 0,5s Fs<10 7,5VA 0,5s Fs<10 7,5 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 7,5 VA cl. 0,5 Fs<10 30 VA cl. 0,5 Fs<10 1VA 10P30 1VA 10P30 1VA 10P30 1VA 10P30 5 VA 5P10 5 VA 5P10 5 VA 5P10 5 VA 5P10 5 VA 5P10 5 VA 5P15 5 VA 5P15 - 7,5 VA 5P10 5 VA 5P15 5 VA 5P15 - 7,5 VA 5P10 5 VA 5P15 7,5 VA 5P15 - 15 VA 5P10 5 VA 5P15 7,5 VA 5P15 - 15 VA 5P10 5 VA 5P15 7,5 VA 5P15 - 15 VA 5P10 1st secondary 2nd secondary

For others characteristics see next page.


pag. 18/20

CONFIGURED CURRENT TRANSFORMER Type ARM3/N1 F - ARM3/N2 F Single and Double Primary Ratio Panels type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B

Dimensions Characteristics

Drawing n H 103005 Standard reference IEC 60044-1 Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV Rated continous thermal current 1,2 x In Frequency 50 or 60 Hz Rated secondary current standard 5 or 1 A Double primary ratio through primary coupling.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio .

Table of options:
N of secondaries for CT

1
ARM3/N1 F

2
ARM3/N2 F
1st measure secondary

STANDARD TYPE

Cl 0,5 Fs=10 VA
alternatively 5 7,5 10 15 20 20 30 30 30 30 30 2nd protection secondary

"K"
K=Ith/Ipn Ith max 25 kA for 1s

Ipn
Rated primary current [A]

measure secondary

protection secondary

Cl 0,5 Fs=10 VA

Cl 5P Fl=10 VA

Cl 5P Fl=10 VA

SR 10 to 800 10 to 300 10 to 300 10 to 200 10 to 150 10 to 100 10 to 50

DR 10-20 to 400-800 10-20 to 300-600 10-20 to 300-600 10-20 to 200-400 10-20 to 150-300 10-20 to 100-200 10-20 to 100-200

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50

100 150 200 250 300 400 500

For others characteristics please contact us.


pag. 19/20